PPTX - Unitronics

Download Report

Transcript PPTX - Unitronics

Component Check
RS232 Cable
-Supplied
MJ10-22-CS25 (RJ11 to DB9 converter)
-Supplied
MJ10-22-CS35 (USB to Serial converter)
-Additional
Check physical connections
• Serial cable plugged into Port 1 on PLC
• Jumpers are set for RS232 communication
• Check part numbers
-Serial cable MJ10-22-CS25
-USB adapter MJ10-22-CS35
Port 1
USB programming cable
• Some of our units can be programmed
through a Mini-USB programming port
- (If equipped, IE- V1210/V1040/V570)
• No other hardware is required for USB
connection
Note that COM port 1 function is suspended when the USB
port is physically connected to the PC.
USB Driver
USB port supports only OS and project download.
• If requested to use Windows Update--do not
accept this option; "Skip obtaining driver software
from Windows Update".
• Install only the driver provided by VisiLogic.
• The USB cable must be disconnected during
the installation.
Driver Check
Check software settings
• Baud rate
- Standard-57600 baud
- Enhanced-115200 baud
• Check Device Manager to ensure
-Port has no errors or warnings
(PC port is confirmed here)
• Select “Get OPLC Info” button to
check/confirm PLC
Check for O/S updates
• Updates automatically
if required.
• Requires connection to
internet.
Has a new O/S been released?
You will receive one of 2 messages.
-Up to date.
-Updating
files
Check & perform an O/S update
Updating an OS
• The System Upgrade Wizard will guide you through the
update of the OS
O/S Updating
– A Progress Bar will show you the operations and
current steps in progress
Finish Update of O/S
• Successful OS Update
O/S Update Not Required