Transcript Slide 1
Da ik in E u r o p e Ac a d e m y Learning, our way VRV III Product Selection Piping selection Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Selection Considerations • Cooling Load calculations • Noise Levels • Heating Load calculations • Pipe Runs • Internal and Ambient temp • Unit Dimensions • Building layout drawings • Orientation • Room Usage • Fresh Air Requirements • Air and temperature distribution • Aesthetics • Planning Restrictions • Possible future site expansion Total or sensible capacity selection ? Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Outdoor and Indoor Unit selection is based on using the capacity index Indoor unit size Capacity index To select indoor unit and unit combinations, to size pipe work and refnet joints, we use ‘Index’ numbers: For example the index no of FXZQ20M7V1B is 20 20 20 25 25 32 31.25 40 40 50 50 63 62.5 80 80 100 100 125 125 140 140 200 200 250 250 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Maximum Number of Indoor Units Connected to One Outdoor Unit Outdoor untis Indoor units Cooling only Heat pump Heat recovery VRV III VRV III VRV II RXQ5P7W1B RXQ8P7W1B RXQ10P7W1B RXQ12P7W1B RXQ14P7W1B RXQ16P7W1B RXQ18P7W1B - RXYSQ4P7V3B RXYSQ5P7V3B RXYSQ6P7V3B RXYQ8P7W1(B) REYQ8M7W1B RXYQ10P7W1(B) REYQ10M7W1B RXYQ12P7W1(B) REYQ12M7W1B RXYQ14P7W1(B) REYQ14M7W1B RXYQ16P7W1(B) REYQ16M7W1B RXYQ18P7W1(B) REYQ18M7W1B RXYQ20P7W1(B) REYQ20M7W1B RXYQ22P7W1(B) REYQ22M7W1B RXYQ24P7W1(B) REYQ24M7W1B RXYQ26P7W1(B) REYQ26M7W1B RXYQ28P7W1(B) REYQ28M7W1B RXYQ30P7W1(B) REYQ30M7W1B RXYQ32P7W1(B) REYQ32M7W1B RXYQ34P7W1(B) REYQ34M7W1B RXYQ36P7W1(B) REYQ36M7W1B RXYQ38P7W1B REYQ38M7W1B RXYQ40P7W1B REYQ40M7W1B RXYQ42P7W1B REYQ42M7W1B RXYQ44P7W1B REYQ44M7W1B RXYQ46P7W1B REYQ46M7W1B RXYQ48P7W1B REYQ48M7W1B RXYQ50P7W1B RXYQ52P7W1B Daikin Europe, Consulting RXYQ54P7W1B - Maximal connectable For VRVIII 6 8 9 22 25 30 36 40 44 42 47 51 53 56 60 64 64 64 64 64 64 64 64 64 64 64 sales 64 I.U combination index Mininum Maximum 50 62,5 70 100 125 150 175 200 225 250 275 300 325 350 375 400 425 450 475 500 525 550 575 600 625 650 675 130 162,5 182 260 325 390 455 520 585 650 715 780 845 910 975 1040 1105 1170 1235 1300 1365 1430 1495 1560 1625 1690 1755 For VRVII 8 13 16 19 20 20 20 20 20 22 32 32 32 32 32 34 36 38 40 40 40 40 section - Da ik in E u r o p e Ac a d e m y Learning, our way Maximum Number of Indoor Units Connected to BS Boxes (required for Heat Recovery Systems) Branch selector box Total index No of indoor units connectable R410a BSVQ100MVE BSVQ160MVE BSVQ250MVE Min – Max 20 - 100 8 Min – Max 100 - 160 8 Min – Max 160 – 250 5 Size 50 is the smallest to be connected System type No of BS boxes connectable REYQ8M 13 REYQ10M 16 REYQ12 – 20M 20 REYQ22M 22 REYQ24 – 32M 32 REYQ34M 34 REYQ35M 36 REYQ38M 38 REYQ40 – 48M 40 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Indoor unit Selection FXCQ Based on High Fan Speed For “Low Fan” Speed, capacity reduction is not published, but the correction factors from next slide may be used. Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Correction factors to calculate the unit 's capacity at low fan tap. Class 20 25 32 40 50 63 80 100 125 Class 20 25 32 40 50 63 80 100 125 200 250 FXCQ-M Correction factor Cooling Heating 81% 77% 81% 78% 81% 78% 83% 81% 83% 81% 86% 84% 88% 85% 84% 81% FXMQ-M Correction factor Cooling Heating 89% 89% 89% 89% 87% 88% 91% 91% FXZQ-M Correction factor Cooling Heating 86% 83% 86% 83% 86% 84% 82% 79% 81% 77% 87% 87% 87% 87% 84% 85% 90% 90% FXHQ-M Correction factor Cooling Heating 89% 88% 87% 85% 86% 83% FXFQ-M Correction factor Cooling Heating 85% 82% 85% 82% 85% 82% 82% 79% 79% 75% 84% 81% 83% 81% 88% 85% 87% 85% FXKQ-M Correction factor Cooling Heating FXAQ-M Correction factor Cooling Heating 71% 66% 73% 68% 72% 67% 83% 81% 87% 85% 82% 79% FXLQ-M Correction factor Cooling Heating 91% 89% 91% 89% 83% 81% 85% 83% 86% 84% 83% 81% 88% 88% 85% 86% 86% 82% 89% 88% Daikin Europe, Consulting sales section FXSQ-M Correction factor Cooling Heating 81% 78% 81% 78% 82% 79% 86% 83% 82% 79% 83% 79% 87% 85% 86% 84% 82% 79% FXNQ-M Correction factor Cooling Heating 91% 89% 91% 89% 83% 81% 85% 83% 86% 84% 83% 81% Da ik in E u r o p e Ac a d e m y Learning, our way Indoor Unit Selection Select indoor units for room layout provided “Example (FXCQ) of where information can be found” Starting from Engineering data book EEDE06-2 page 795: Noise Levels details Engineering data book EEDE06-2 page 815 Unit Dimensions Engineering data book EEDE06-2 page 798 Air Distribution Engineering data book EEDE06-2 page 818 Make a record of Model, Fan speed, Total and Sensible Cooling duties Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Indoor Unit Selection 18 m N Room A 8.0kw Sensible Cooling 3m 3m 3m Room E 1.65 kw Sensible Room D 2.5 kw Sensible Room A - General Office Room B - Meeting Room Room C - Manager Room D - Small office Room E - Reception Internal design 23 deg C db 16 deg C wb Ambient design 29 deg C db Room C 2.1 kw Sensible 6m Room B 4.2 kw Sensible 6m 6m 3m Rooms A, B and E 400mm ceiling void Room C 200 mm ceiling void Room D no void (restricted floor space) Ceiling Height 2.7m Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Indoor Unit Selection Possible Solution Internal design 23 deg C db 16 deg C wb Ambient design 29 deg C db Required Sensible Total Sensible Room A 3 x FXFQ40M 8.0 kW High Speed 10.8 kW 9.0 kW Room B 1 x FXSQ80M 4.2 kW Low Speed 5.97 kW 4.73 kW Room C 1 x FXLQ40M 2.1 kW Low Speed 3.06 kW 2.3 kW Room D 1 x FXAQ40M 2.5 kW High Speed 3.60 kW 3.31 kW Room E 1 x FXSQ32M 1.65 kW Low Speed 2.31 kW 1.88 kW Note: The low speed duties were calculated based on the correction factors shown in the previous table. Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection Considerations • Remember the maximum index connectable • Remember the maximum number of indoor units • Cooling Only, Heat Pump or Heat Recovery • Positioning • Noise levels • Service Access space required Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection 18 m Room A 6m FXFQ40M Room E 3m FXSQ32M FXFQ40M FXFQ40M Room D FXAQ40M Room C FXLQ40M Room B 6m FXSQ80M Condensing Unit Base 3m 6m Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection Example: using Inverter 2 pipe Heat Pump Room A 3 x FXFQ40M Room B 1 x FXSQ80M Room C 1 x FXLQ40M Room D 1 x FXAQ40M Room E 1 x FXSQ32M Total Index 120 80 40 40 31.25 311.25 Suitable Condensing Unit RXYQ10P7W1 Indoor Unit Combination Index Outdoor Unit RXYQ5P7W1 RXYQ8P7W1/REYQ8M RXYQ10P7W1/REYQ10M Minimum Maximum 62.5 100 125 162.5 260 325 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection Example: using Inverter 2 pipe heat pump Room A 3 x FXFQ40M Room B 1 x FXSQ80M Room C 1 x FXLQ40M Room D 1 x FXAQ40M Room E 1 x FXSQ32M Total Index 120 80 40 40 31.25 311.25 Suitable Condensing Unit RXYQ10P7W1 Look up condensing unit duty from EEDE06–2 page 196 At indoor temperature of 16 deg C wb and outdoor temp 29 deg C db Total Cooling with index of 308 = 24,8 kW Total Cooling at index of 336 = 27.0 kW Index connected = 336 – 311.25 = 24.75 27,0 kW – 24,8 = 2.2 kW 27.0 kW – 1.944 kW 336 – 308 = 28 = 25.055 kW 2.2 kW/28 = 0.0785 kW 24.75 x 0.0785 = 1.944 kW Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection Example: using Inverter 2 pipe heat pump (Back to the original data selected at high speed) Corrected Index Total Sensible Total Sensible Room A = 3 x FXFQ40M (high speed) 120 10.80kW 9.0kW 9,66kW 8,04kW Room B = 1 x FXSQ80M (low speed) 80 5.97 kW 4.73 kW 5,60 kW 4.44kW Room C = 1 x FXLQ40M (low speed) 40 3.06 kW 2.3kW 2.73 kW 2.05kW Room D = 1 x FXAQ40M (high speed) 40 3.6kW 3.3Kw 3.22Kw 2.96Kw Room E = 1 x FXSQ32M (low speed) 31.25 2.37kW 1.88kW 2.08kW 1.69 kW Total index 311.25 Calculate corrected indoor unit capacity RXYQ10M total cooling = 25.05kW FXFQ40M = (40 x 25.05) = 3.22 kW total 311. 25 Reduce sensible by the same proportion prior to correction calculation Don’t forget to apply correction for low speed when necessary: FXSQ80 = (80 x 25.05) x 0.87 = 5,60 kW total 311.25 FXSQ80 = 4.73 x 5,60 = 4.44 kW sensible Daikin Europe, Consulting sales section 5.97 Da ik in E u r o p e Ac a d e m y Learning, our way Condensing Unit Selection Example: using Inverter 2 pipe heat pump Required Sensible Corrected Total Sensible Room A = 3 x FXFQ40M 8.0 kW High Speed 9,66kW 8,04kW Room B = 1 x FXSQ63M 4.2 kW Low Speed 5,60 kW 4.44kW Room C = 1 x FXLQ40M 2.1 kW Low Speed 2.73 kW 2.05kW Room D = 1 x FXAQ40M 2.5 kW High Speed 3.22Kw 2.96Kw Room E = 1 x FXSQ25M 1.65 kW Low Speed 2.08kW 1.69 kW Are we finished ? Daikin Europe, Consulting sales section Not yet ? Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Length Correction Example: using Inverter 2 pipe heat pump Look up capacity correction ratio on page 294 of EEDE06-2 Table RXYQ10P For Room B FXSQ80M Run = 20m Level difference = Outdoor unit 3m below indoor unit Capacity reduction factor = 0.98 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Length Correction 18 m Room A 6m FXFQ40M Room E 3m FXSQ32M FXFQ40M FXFQ40M Room D FXAQ40M Room C FXLQ40M Room B 6m FXSQ80M Condensing Unit Base 3m 6m Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way (Change in Cooling Capacity) Pipe Length Correction (H=m) Outdoor situated above Indoor units 0.90 50 0.87 0.85 0.92 40 0.95 30 0.98 20 1.0 10 0 Example: 0 Outdoor unit 3m below Indoor unit 0 10 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 0 100 110 ……..190 m 1.0 20 30 Outdoor situated below Indoor units 40 0.98 0.95 0.92 0.90 (H=m) Daikin Europe, Consulting sales section 0.87 0.85 Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Length Correction Example: using Inverter 2 pipe heat pump Corrected Total Sensible Pipe length Correction factor required Pipe length corrected Total Sensible Room A = 1 x FXFQ40M = 1 x FXFQ40M = 1 x FXFQ40M 9,66kW 8,04kW 15M 11M 7M 0.99 0.99 0.99 3,18kW 3,18kW 3,18kW 2.66kW 2.66kW 2.66kW Room B = 1 x FXSQ80M 5,60 kW 4.44kW 20M 0.98 5,49kW 4.35kW Room C = 1 x FXLQ40M 2.73 kW 2.05kW 16M 0.98 2,68kW 2.02kW Room D = 1 x FXAQ40M 3.22Kw 2.96Kw 10M 0.99 3.18kW 2,93kW Room E = 1x FXSQ32M 2.08kW 1.69 kW 4M 1.00 2.06kW 1.67kW Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Additional correction due to Defrost operation Defrost operation protects the outdoor unit coil against freezing: • • • • • • Happens in heating mode Performs once max every 2 hours Duration: between 4 and 8 min During defrost: outdoor/indoor units’ fans are stopped No heating is delivered during defrost Limited cooling is delivered (heat recovery models) • Capacity tables do not take account of this capacity reduction • The heating capacity should be ammended by a correction factor: Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Summary of selection after corrections Example: using Inverter 2 pipe heat pump Required sensible Result total Result sensible Room A = 3 x FXFQ40M 8.0 kW High Speed 10,66kW 8,04kW Room B = 1 x FXSQ80M 4.2 kW Low Speed 5,49kW 4.35kW Room C = 1 x FXLQ40M 2.1 kW Low Speed 2,68kW 2.02kW Room D = 1 x FXAQ40M 2.5 kW High Speed 3.18kW 2,93kW Room E = 1 x FXSQ32M 1.65 kW Low Speed 2.06kW 1.67kW If selected fan coil unit corrected duty is too low, then that unit has to be re-selected and the complete procedure repeated Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Would this suit Heat Recovery? Room A FXFQ40M Room E FXSQ32M FXFQ40M FXFQ40M Room D FXAQ40M Room C FXLQ40M Room B FXSQ80M Meeting Room Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRVII Heat Recovery: selection of BS Boxes Min – Max 100 - 160 BSVQ160MVE Room A FXFQ40M Room E FXFQ40M FXFQ40M Room D FXSQ32M FXAQ40M Condensing Unit Base with REYQ10M BS Box Room B Room C FXSQ80M FXLQ40M BSVQ100MVE Daikin Europe, Consulting sales section Min – Max 20 - 100 Da ik in E u r o p e Ac a d e m y Learning, our way VRV III “P7” Series Selection by VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express VRV Selection Software Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Material list Model Qty Description REYQ12M 1 Heat recovery VRV M R410A REYQ8M 1 Heat recovery VRV M R410A BSVQ100M 4 Branch selector unit R410A BSVQ160M 3 Branch selector unit R410A FXAQ40M 1 A - Wall mounted unit FXFQ50M 2 F - 4-way blow ceiling mounted cassette FXFQ80M 2 F - 4-way blow ceiling mounted cassette FXSQ40M 2 S - Concealed ceiling mounted FXSQ80M 3 S - Concealed ceiling mounted KHRQ22M20T7 3 REFNET branch piping kit KHRQ23M29T7 4 REFNET branch piping kit KHRQ23M64T7 1 REFNET branch piping kit DCS601A51 1 I controller BRC1D517 8 Wired remote control BYC125KJW1 4 Decoration panel Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV Express Indoor unit details Name Model Tmp C Rq TC Av TC Rq SC Av SC Tmp H Rq HC Av HC Airflow Soun d MC A WxHxD Wg ht °C kW kW kW kW °C kW kW l/s dBA A mm kg First Floor - Room 101 FXFQ50M 22.0 4.0 4.9 3.5 3.8 21.0 2.0 4.5 183-267 27-32 0.3 840x246x840 24 First Floor - Room 102 FXFQ50M 22.0 4.0 4.9 3.5 3.8 21.0 2.0 4.5 183-267 27-32 0.3 840x246x840 24 First Floor - Room 103 FXFQ80M 22.0 5.5 7.8 4.9 5.5 21.0 3.2 7.1 250-333 31-36 0.5 840x246x840 25 First Floor - Room 104 FXFQ80M 22.0 5.5 7.8 4.9 5.5 21.0 3.2 7.1 250-333 31-36 0.5 840x246x840 25 First Floor - Room 105 FXSQ80M 22.0 5.5 7.8 4.9 6.2 21.0 3.2 7.1 358-450 37-43 1.4 1400x300x800 51 First Floor - Room 106 FXSQ40M 22.0 3.0 3.9 2.5 2.9 21.0 2.0 3.5 150-192 32-38 0.6 700x300x800 30 Second Floor - Room 201 FXSQ40M 22.0 3.0 3.7 2.5 2.8 21.0 2.0 3.6 150-192 32-38 0.6 700x300x800 30 Second Floor - Room 203 FXSQ80M 22.0 6.0 7.5 5.2 6.0 21.0 4.5 7.2 358-450 37-43 1.4 1400x300x800 51 Second Floor -Room 204 FXSQ80M 22.0 6.0 7.5 5.2 6.0 21.0 4.5 7.2 358-450 37-43 1.4 1400x300x800 51 Second Floor - Room 205 FXAQ40M 22.0 3.0 3.7 2.5 2.9 21.0 1.8 3.6 150-200 34-39 0.4 1050x290x230 14 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV III “P” Series Field Pipe work Application Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way VRV refrigerant piping system is based on REFNETS Advantages of REFNET system: Short dimensioning time Short installation time REFNET joint REFNET header NEVER install joint after a section header ! Daikin Europe,aConsulting sales Da ik in E u r o p e Ac a d e m y Learning, our way Refnet installation recommendations Joints are to be mounted …. Vertically …..Horizontally + 30° Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way REFNET piping system Select refnets according to the capacity Adjust the pipe size according to the capacity Possibly prototypes match pipe and refnet using adaptors Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Refrigerant Pipe Work Maximum “Actual” Piping Limitations A Can become 90 m in certain conditions A For level differences above 50m; • One size up of main liquid pipe • Option kit 40M 90M 190M Max EQUIVALENT LENGTH 165M 15M •Total piping length = 1000M •No Oil traps •No Liquid traps •No Solenoid valves •No Sight glasses •No Driers •No Additional oil •Max pressure test 38.5 bar Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Field Piping Limitations VRV III P series (Heat pump Inverter) if Can be 90m RXYQ…P 1. “Longest” – “shortest” branch = b+c+d+e+l-f <=40m 2. f, g,h, j, k, l, m, n <= 40m 3. Pipes b, c, d, e between first and last kit are sized up 4. For the total piping calculation the actual length of b, c, d, e is counted double 40m 165m a b c d e 90m f FXHQ….M g FXCQ….M h FXCQ….M j FXSQ….M k l n NEVER INSTALL A JOINT AFTER A HEADER m FXAQ….M 15m FXLQ….M Daikin Europe, Consulting sales section FXLQ….M FXLQ….M Da ik in E u r o p e Ac a d e m y Learning, our way VRVII “M” Series Field Piping Limitations (Heat Recovery) REYQ….M 150m 40M 50m BSVQ. .M FXHQ….M BSVQ. .M FXCQ….M BSVQ. .M FXCQ….M BSVQ. .M BSVQ. .M BSVQ. .M BSVQ. .M FXSQ….M BSVQ. .M BSVQ. .M 15m FXLQ….M FXLQ….M Daikin Europe, Consulting sales section FXLQ….M FXLQ….M FXLQ….M Da ik in E u r o p e Ac a d e m y Learning, our way Piping joints required at the first branch VRV III VRV II H/R Refnet joints for 2 pipe Outdoor system type KHRQ22M20T RX(Y)Q5 KHRQ22M29T9 RX(Y)Q8~10 KHRQ22M64T RX(Y)Q12~18 + RXYQ20~22 KHRQ22M75T RXYQ24~54 Refnet joints for 3 pipe Outdoor system type KHRQ23M29T7 REQY8 – 10 KHRQ23M64T7 REYQ12 – 22 Daikin Europe, Consulting sales section KHRQ23M75T7 REYQ24> Da ik in E u r o p e Ac a d e m y Learning, our way Piping Joints other than the first branch VRV III VRV II H/R Refnet joints for 2 pipe Connectable index KHRQ22M20T <200 KHRQ22M29T9 200 - <290 KHRQ22M64T 290 - <640 KHRQ22M75T >640 Refnet joints for 3 pipe Connectable index KHRQ23M20T7 <200 KHRQ23M29T7 200 - <290 KHRQ23M64T7 290 - <640 Daikin Europe, Consulting sales section KHRQ23M75T7 640> Da ik in E u r o p e Ac a d e m y Learning, our way Selection of Piping Joints 1st joint corresponds to outdoor unit 2nd Joint according to class total Possibly, this results into a bigger joint than the 1st joint ! Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Piping Headers PLEASE NOTE : Refnet header for 2 pipe Connectable index KHRQ22M29H <290 KHRQ22M64H 290 - <640 KHRQ22M75H 640> Refnet header for 3 pipe Connectable index KHRQ23M29H7 <200 KHRQ23M29H7 200 - <290 KHRQ23M64H7 290 - <640 KHRQ23M75H7 640> Class 250 CANNOT be connected to a header Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Size connections to the outdoor units Heat Pump model Outdoor model Gas pipe Liquid pipe RX(Y)Q5 15.9mm 9.5mm RX(Y)Q8 19.1mm 9.5mm RX(Y)Q10 22.2mm 9.5mm RX(Y)Q12, 14, 16 28.6mm 12.7mm RX(Y)Q18 +RXYQ20-22 28.6mm 15.9mm RXYQ24 34.9mm 15.9mm RXYQ26-34 34.9mm 19.1mm RXYQ36-54 41.3mm 19.1mm Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Sizing between refnet branch kits for heat pump models Piping Total unit capacity Gas (outer diameter) Liquid (outer diameter) <150 15.9mm 9.5mm 150-->200 19.1mm 9.5mm 200 - >290 22.2mm 9.5mm 290 - <420 28.6mm 12.7mm 420 - <640 28.6mm 15.9mm 640 - <920 34.9mm 19.1mm >920 41.3mm 19.1mm Adjust the pipe size according to the capacity Possibly, this results into a bigger pipe than the one coming from the outdoor unit ! Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Refrigerant pipe Size Connections to Indoor Units The pipe size of the indoor unit Total indoor unit capacity Gas Liquid 20, 25, 32, 40, 50 12.7mm 6.4mm 63, 80, 100, 125 15.9mm 9.5mm 200 19.1mm 9.5mm 250 22.2mm 9.5mm Please note: all the above connections are flared other than the gas pipe connection on Daikin Europe, the 200 an 250 models being brazed style Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Size connections to the outdoor units for Heat recovery Outdoor model Gas pipe Liquid pipe Discharge pipe REYQ8 19.1mm 9.5mm 15.9mm REYQ10 22.2mm 9.5mm 19.1mm REYQ12 28.6mm 12.7mm 19.1mm REYQ14, 16 28.6mm 12.7mm 22.2mm Pipe Sizing between refnet branch kits for Heat recovery Total unit capacity Gas Discharge Liquid <63 12.7mm 9.5mm 6.4mm 63 - <200 15.9mm 12.7mm 9.5mm 200 - <290 22.2mm 19.1mm 9.5mm 290 - <420 28.6mm 19.1mm 12.7mm 420 - <640 28.6mm 28.6mm 15.9mm 640 - <920 34.9mm 28.6mm 19.1mm >920 41.3mm 28.6mm Daikin Europe, Consulting sales section 19.1mm Da ik in E u r o p e Ac a d e m y Learning, our way Equivalent length = a reference for a pressure drop of an component in the pipe work = length of linear pipes + allowances for fittings The following allowances should be allocated to the following components: Branch selector box = 4m Refnet header = 1m Refnet joint = 0.5m 41.3mm 1 – 5/5 bend = 0.7m 34.9mm 1 – 3/8 bend = 0.66m 28.mm 1 – 1/8 bend = 0.5m 22.2mm 7/8 bend = 0.4m 19.1mm 3/4 bend = 0.25m 12.7mm 1/2 bend = 0.22m 9.5mm 3/8 bend = 0.18m Overall Equivalent length = =(Equivalent length of main pipe work x 0.5) + Equivalent length of branch pipe work Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way What happens when the overall equivalent length from the condensing unit to any indoor unit exceeds 90 m ? Increase diameter of the Liquid AND the Gas pipes between the condenser and the first refnet Increase only gas for RX(Y)Q5P7 Increase only liquid for RXYQ12,14,24, 36~54 P REYQ : The WHOLE RANGE Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Equivalent length: example of calculation Equivalent length 80m E. Length 40m Overall Equivalent length = (80m x 0.5) + = 80m 40m (No increase in pipe size required) Section to be increased in size Equivalent length 110m E. Length 40m (110m x 0.5) Overall Equivalent length = + = 95m 40m (An increase in main pipe work size is required) Section to be increased in size Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Piping Between modules forming a Condensing unit Heat pump (P7 series) To indoor units No oil equalization line required for P7 models = Liquid Line = Gas Line Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Piping Between modules forming a Condensing unit Heat recovery (M series) To indoor units = ¼” (6.4mm) Oil Equalising Line (only for REYQ18 or more) = Liquid Line = Gas Line = Discharge Line Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe limitations between modules forming a Condensing unit A B C Branch Maximum pipe length A 10m (13 m equiv.) or less B 10m (13 m equiv.) or less C 10m (13 m equiv.) or less Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Sizing Between Outdoor Units Heat pump branch kit Two unit connection kit BHFQ22P1007 Three unit connection kit BHFQ22M1517 Heat recovery branch kit Two unit connection kit KHFQ23M907 Three unit connection kit BHFQ23M1357 Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Sizing Between Outdoor Units VRVIII Daikin Europe, Consulting sales section ~ 54 Da ik in E u r o p e Ac a d e m y Learning, our way Pipe Sizing Between Outdoor Units VRVII H/R Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Additional Refrigerant Charge Calculation for VRVIII takes in consideration the total lengths of liquid piping (m) TOTAL 22.2 = TOTAL 19.1 = TOTAL 15.9 = TOTAL 12.7 = TOTAL 9.5 = TOTAL 6.4 = x 0.37 = + x 0.26 = + x 0.18 = + x 0.12 = + x 0.059 = + x 0.022 = = R (additional kg R410) R should be rounded off in units of 0,1 kg Daikin Europe, Consulting sales section Da ik in E u r o p e Ac a d e m y Learning, our way Additional Refrigerant Charge Calculation for VRVII H/R takes in consideration the total lengths of liquid piping (m) TOTAL 22.2 = TOTAL 19.1 = R= TOTAL 15.9 = TOTAL 12.7 = TOTAL 9.5 = TOTAL 6.4 = x 0.35 = + x 0.25 = + x 0.17 = + x 0.11 = + x 0.054 = + x 0.022 = 0 kg (8-16 HP) x 1.15 Daikin Europe, Consulting sales section 3 kg (18-32 HP) 6 kg (34-48 HP) Da ik in E u r o p e Ac a d e m y Learning, our way Field Pipe sizing & Additional “Refrigerant” Charging Example of centralizing table SUCTION 15 5 B V F 1 32 ADDITIONAL REFRIGERANT CHARGE CALCULATION TOTAL 12.7 = X 0.11 = + TOTAL 9.5 = X 0.054 = TOTAL 6.4 = C W 10 10 D X 4 H 2 N 40 U V W X Y Z 1 2 3 4 5 6 O 25 X 0.022 = 6 6 6 Z L 4 J 5 4 3 1 E Y I 6 M HEADER JOINT + G 1 BRANCH SELECTOR BOX LIQUID R S T K 1 1 SUCTION L M N O P Q 6 U LIQUID A B C D E F G H I J K R_____ M A DISCHARGE 1 P 80 40 6 Q 1 40 15m 2 2 2 R S T 40 No additional oil required! Daikin Europe, Consulting sales section 40 40 Da ik in E u r o p e Ac a d e m y Learning, our way R-410A Piping material material Size ø6,4 “The material, wall thickness, tensile strength, ductility, corrosion resistance, forming and testing methods shall be suitable for the refrigerant used and withstand the pressure and stresses which may occur” The same requirements are valid for refnet headers and joints Minimum thickness O t(mm) 0,80 ø 9,5 O 0,80 ø12,7 O 0,8 ø15,9 O 0,99 ø19,1 1/2H 0,80 ø22,2 1/2H 0,80 ø28,6 1/2H 0,99 ø34,9 1/2H 1,21 ø41,3 1/2H 1,43 C1220- O : Annealed ½ H: Half Hard For half hard pipes the maximum allowed tensile stress is 61N/mm² for this reason, the 0.2% proof strength of the half hard pipe shall be minimum 61N/mm² The bending radius is more or equal to 3 times the diameter of the pipe The maximum working pressure for R-410A VRV P-series is 38 bar Daikin Europe, Consulting sales section