Oregon Joint Use Violation Examples

Standards Subcommittee

Utility Operator Basics

6       Climbing Space Grounding/Bonding Permitting Clearances Structural Strength: Guying, holes, loading calculations Tree Trimming   Climbable 8’ Clear Zone

40”

Power Space

Secondary/Primary Neutral

Worker Safety Clearance Zone Communication Space Public Safety Clearance Zone

Violations

U.C.

Dev. Equip. 1 Equip. 2 C000 MV COML COML P4321 Toward Suggested Action Raise CATV SEV.

B NESC Reference 235H2

Communication Mainline (COML) Communication Mainline (COML)

Violations

U.C. Dev. Equip. 1 Equip. 2 X000 PC WEO Toward Suggested Action Relocate/Move SEV.

B 236 NESC Reference

Wireless Equipment (WEO)

Violations

U.C. Dev. Equip. 1 Equip. 2 X000 PV ANT PDLP Toward Lower Suggested Action SEV.

B 235 NESC Reference

Power Drip-loop (PDLP) Antenna (ANT)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PG GRND PEDS Toward Lower Suggested Action SEV.

B NESC Reference 94B2c

Ground Rod (GRND) Ground Wire (GRWR)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 PV P000 DB STEP CON PEDS Toward Remove Repair Suggested Action SEV.

B B NESC Reference 217A2b 360A

Conduit-PVC (CON) Pole Step (STEP)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PV SOB PEDS Toward Raise Suggested Action SEV.

B NESC Reference 217A2c

Stand Off Bracket (SOB) Pedestrian Surface (PEDS)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PS ANC CURB Toward Suggested Action Relocate/Move SEV.

B NESC Reference 231B1

Anchor (ANC) Curb (CURB)

Violations

U.C.

Dev. Equip. 1 Equip. 2 C000 PS GUY ANC Toward Trim Suggested Action SEV.

B NESC Reference 012C

Down Guy (GUY) Anchor (ANC)

Violations

U.C.

Dev. Equip. 1 Equip. 2 C000 AB COMD Toward Remove Suggested Action SEV.

B NESC Reference 214B

Communication Drop (COMD)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PH POLE HYD Toward Suggested Action Relocate/Move SEV.

B NESC Reference 231A

Fire Hydrant (HYD) Pole (POLE)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PV PDLP COML Toward Suggested Action Raise Power SEV.

B NESC Reference 235C1

Power Drip-loop (PDLP) Communication Mainline (COML)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PV SEC COML P000 PR SEC Toward Suggested Action Place Split Duct Attach SEV.

B B NESC Reference 235C1 239A1

Power Secondary (SEC) Communication Mainline (COML)

Violations

U.C. Dev. Equip. 1 Equip. 2 X000 PV COFO SLT Toward Suggested Action Lower Fiber SEV.

B NESC Reference 238D

Power Street Light (SLT) Communication Fiber-optic (COFO)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 PV COMD PDLP Toward Suggested Action Lower Telco SEV.

B NESC Reference 235-5

Power Drip-loop (PDLP) Communication Drop (COMD)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 U COMD PEDS Toward Bury Suggested Action SEV.

B NESC Reference 230A2d

Pedestal (PED) Pedestrian Surface (PEDS) Communication Drop (COMD)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 MV COMD PEDS B1234 Toward Tighten Suggested Action SEV.

B 232 NESC Reference

Communication Drop (COMD) Unusual Support (JOHN) Pedestrian Surface (PEDS)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 PV COML PDLP Toward Suggested Action Lower Telco SEV.

B NESC Reference 235C1

Power Drip-loop (PDLP) Communication Mainline (COML)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 PC COMD Toward Suggested Action Relocate/Move SEV.

B 236 NESC Reference

Communication Drop (COMD)

Violations

U.C.

T000 Dev. Equip. 1 Equip. 2 PR P000 PV COMD SEC COML Toward Suggested Action Attach Place split Duct SEV.

B B NESC Reference 239D3 235C1

Power Secondary (SEC) Communication Mainline (COML) Communication Drop (COMD)

Violations

U.C.

T000 Dev. Equip. 1 Equip. 2 PC P000 PV TRM SEC COML Toward Suggested Action Relocate/Move Place Split Duct SEV.

B B 236 NESC Reference 235C1

Power Secondary (SEC) Communication Mainline (COML) Communication Terminal (TRM)

Violations

U.C. Dev. Equip. 1 Equip. 2 X000 PV COML SEC X000 PH COML POLE

Communication Mainline (COML)

Toward Lower Attach Suggested Action SEV.

B B NESC Reference 235C1 234B1

Power Secondary (SEC) Pole (POLE)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 MV PDLP COML P4321 Toward Shorten Suggested Action SEV.

B NESC Reference 235C2b(1)(a)

Communication Mainline (COML) Power Drip-loop (PDLP)

Violations

U.C.

Dev. Equip. 1 Equip. 2 C000 MV COMD SEC T000 MV COMD SEC P4321 P4321 Toward

Power Secondary (SEC)

Suggested Action Raise Power Raise Power SEV.

B B NESC Reference 235C2b(1)(a) 235C2b(1)(a)

Communication Drop (COMD)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 MV PDRP COML B1234 Toward Suggested Action Raise Power SEV.

B NESC Reference 233C1

Communication Mainline (COML) Power Service Drop (PDRP)

Violations

U.C. Dev. Equip. 1 Equip. 2 X000 MV COMD PDRP B1234 Toward Suggested Action Move 1st attachment SEV.

B NESC Reference 235C1

Communication Drop (COMD) Power Service Drop (PDRP)

Violations

U.C.

T000 Dev. Equip. 1 Equip. 2 MV COMD DRSR B1234 Toward Suggested Action Raise Telco SEV.

B 232 NESC Reference

Communication Drop (COMD) Drivable Surface (DRSR)

Violations

U.C.

Dev. Equip. 1 Equip. 2 P000 MV SEC ROOF P4321 Toward Suggested Action Raise Power SEV.

B NESC Reference 234C

Power Secondary (SEC) Roof (ROOF)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 BV PDRP PEDS B1234 Toward Suggested Action Raise Power SEV.

B NESC Reference 234C3d(1)

Power Service Drop (PDRP) Pedestrian Surface (PEDS)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 BV PDLP ROOF B1234 Toward Shorten Suggested Action SEV.

B NESC Reference 234C3d(1)

Power Drip-loop (PDLP) Roof (ROOF)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 AB COMD Toward Remove Suggested Action SEV.

B NESC Reference 214B

Communication Drop (COMD)

Violations

U.C. Dev. Equip. 1 Equip. 2 C000 BV COMD PDLP B1234 Toward Suggested Action Relocate/Move SEV.

B NESC Reference NEC

Communication Drop (COMD) Power Drip-loop (PDLP)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 BH PDRP WIN B1234 Toward Suggested Action Relocate/Move SEV.

B NESC Reference 234C3d(2)

Power Service Drop (PDRP) Window (WIN)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 PC TREE Toward Trim Suggested Action SEV.

B NESC Reference 217A4

Trees/Vegetation (TREE)

Violations

U.C. Dev. Equip. 1 Equip. 2 P000 AB XARM P000 AB PBRK Toward Remove Suggested Action Remove SEV.

B B NESC Reference 214B 214B

Cross-arm (XARM) Power Bracket (PBRK)

Violations

U.C. Dev. Equip. 1 Equip. 2 T000 PH C000 PH Pole Pole Pole Pole Toward Transfer Transfer Suggested Action SEV.

B B NESC Reference OPUC Joint Use Policy OPUC Joint Use Policy

Pole (POLE)