CB200e Cabinet Extinguishant
Control Panels
• Designed for cabinet extinguishant systems
• 2 zone extinguishant co-incidence operation
• Selectable discharge circuit delay (0-10-20-30
seconds)
• Alarm circuit and C/O fire relay included
• Actuator and Solenoid compatible
• One man test facility
CB200 Conventional Control Panels
• Earth fault monitoring
• Surface or semi-flush mounting as standard
• Ample termination space
• Flame Resistant Polycarbonate enclosure
• Complies with EMC and LVD Directives
Cabinet Specifications
Semi-flush is available as
standard because of the
construction of the CB200
enclosure.
Panel dimensions are
detailed in the Application
Guide.
The removable gland plate and cable entry
grommets obviate the need to drill wiring
holes in the panel on site.
Mechanical Assembly
Installer’s
logo or
brand
image may
be added.
This drawing shows the ample
wiring space incorporated into
the CB200 panel design.
PCB terminal
support for
mechanical
reliability.
Electronics are completely
removable for convenience
on site during fitting of the
back box.
+
-
-
+
There is space for two 12V
2.1AH batteries - suitable
for the 24hr standby
requirements on an 8 zone
system.
Typical Wiring Schematic
This is a typical
CB200e wiring
illustration as it
appears in the
product
documentation.
3K9 EOL
RESISTOR
3K9 EOL 22uF EOL
RESISTOR CAPACITOR
ANUAL CALL POINT
2A M
1A
ACTUATOR
POLARISING
COIL
DIODE
SUPPRESSION
DIODE
Apollo S60 detectors are illustrated, but
the CB200e panel supports a wide variety
of other manufacturers’ detectors - details
in the Application Guide.
WITH 680 OHM
RESISTOR FITTED
1
2
APOLLO S60 DETECTOR BASE
WITH SCHOTTKY DIODE
ACTUATOR
COIL
L1OUT
L2
L1 IN
12V
BATTERY
12V
BATTERY
FROM MAINS
TRANSFORMER
ZONE 2
ALARM
AUX FIRE RELAY ACTUATOR
N/ C ACT- ACT+ ALM- ALM+ Z2- Z2+
N/ O P
24V BATT. EARTH SECONDARY PROC. FAULT RESET
ZONE 1
AC IN
AND ONE MAN TEST
Z1Z1+ BAT- BAT+ IN
(SEE MANUAL)
~
~
BUZZER
DISABLE
PROCESSOR
RESET