Induction Motor – Scalar Control By Dr. Ungku Anisa Ungku Amirulddin Department of Electrical Power Engineering College of Engineering Dr.
Download ReportTranscript Induction Motor – Scalar Control By Dr. Ungku Anisa Ungku Amirulddin Department of Electrical Power Engineering College of Engineering Dr.
Slide 1
Induction Motor – Scalar Control
By
Dr. Ungku Anisa Ungku Amirulddin
Department of Electrical Power Engineering
College of Engineering
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
1
Slide 2
Outline
Introduction
Speed Control of Induction Motors
Pole Changing
Variable-Voltage, Constant Frequency
Variable Frequency
Constant Volts/Hz (V/f) Control
Open-loop Implementation
Closed-loop Implementation
Constant Airgap Flux Control
References
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
2
Slide 3
Introduction
Scalar Control - control of induction machine
based on steady-state model (per phase SS
equivalent circuit)
Rs
Is
Lls
Llr’
+
+
Vs
–
Dr. Ungku Anisa, July 2008
Ir ’
Lm
Im
EEEB443 - Control & Drives
E1
Rr’/s
–
3
Slide 4
Introduction
Te
Pull out
Torque
(Tmax)
Intersection point
(Te=TL) determines the
steady –state speed
Te
TL
Trated
What if the load must
be operated here?
s
sm
1
Dr. Ungku Anisa, July 2008
rated
rotors
rotor’
0
EEEB443 - Control & Drives
r
Requires speed
control of motor
4
Slide 5
Speed Control of IM
Given a load T– characteristic, the steady-state speed can be
changed by altering the T– curve of the motor
Te
3R
s
2
'
r
Vs
2
2
2
'
s s
Rr
2
X ls X lr
R s
s
P
4
3
f
P
1
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Varying voltage
(amplitude)
Varying line
frequency
Pole Changing
5
Slide 6
Speed Control of IM
Pole Changing
Machines must be specially manufactured (i.e. called pole changing
motors or multi-speed motors)
Need special arrangement of stator windings
Only used with squirrel-cage motors
Because number of poles induced in squirrel cage rotor will follow
number of stator poles
Two methods:
Multiple stator windings
stator has more than one set of 3-phase windings
only energize one set at a time
simple, expensive
Consequent poles
Discrete step change in speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
6
Slide 7
Speed Control of IM
Pole Changing
Consequent poles
single winding divided into
few coil groups
No. of poles changed by
changing connections of coil
groups
Change in pole number by
factor of 2:1 only
A two-pole stator winding for pole changing.
Notice the very short pitch (60 to 90) of
these windings.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
7
Slide 8
Speed Control of IM
Pole Changing
Consequent poles
Close up view of one phase of a
pole changing winding.
In Figure (a): the 2-pole
configuration, one coil is a north
pole and the other is a south
pole.
In Figure (b): when the
connection on one of the two
coils is reversed, they are both
north poles, and the magnetic
flux returns to the stator halfway
between the two coils. The
south poles are called
consequent poles. Hence the
winding is now 4-pole.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
8
Slide 9
Speed Control of IM
Variable-Voltage (amplitude),
Constant Frequency
Controlled using:
Transformer (rarely used)
Thyristor voltage controller
thyristors connected in anti-parallel
motor can be star or delta connected
voltage control by firing angle control
(gating signals are synchronized to
phase voltages and are spaced at 60
intervals)
Only for operations in Quadrant 1 and
Quadrant 3 (requires reversal of phase
sequence)
also used for soft start of motors
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
9
Slide 10
Speed Control of IM
Variable-Voltage (amplitude), Constant Frequency
Voltage can only be reduced from rated Vs (i.e. 0 < Vs ≤ Vs,rated)
From torque equation, Te Vs2
When Vs , Te and speed reduces.
If terminal voltage is reduced to bVs, (i.e. Vs = bVs,rated) :
Te
3R
'
r
bV
2
s
2
'
s s
Rr
2
X ls X lr
R s
s
Note: b 1
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
10
Slide 11
Speed Control of IM
Variable-Voltage
(amplitude), Constant
Frequency
Suitable for applications
where torque demand
reduces with speed
(eg: fan and pump drives
where TL m2)
Suitable for NEMA Class D
(high-slip, high Rr’) type
motors
High rotor copper loss,
low efficiency motors
get appreciable speed
range
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Practical
speed range
11
Slide 12
Speed Control of IM
Variable Voltage (amplitude),
Constant Frequency
Disadvantages:
limited speed range when
applied to Class B (low-slip) motors
Excessive stator currents at low
speeds high copper losses
Distorted phase current in machine
and line (harmonics introduced by
thyristor switching)
Poor line power factor
(power factor proportional to firing
angle)
Hence, only used on low-power,
appliance-type motors where
efficiency is not important
e.g. small fan or pumps drives
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
12
Slide 13
Speed Control of IM
Variable Frequency
Speed control above rated (base) speed
Requires the use of PWM inverters to control frequency of motor
Frequency increased (i.e. s increased)
Stator voltage held constant at rated value
Airgap flux and rotor current decreases
Developed torque
decreases
Te (1/s)
For control below
base speed –
use Constant
Volts/Hz method
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
13
Slide 14
Constant Volts/Hz (V/f) Control
Airgap flux in the motor is related to the induced stator voltage
E1 :
ag
E1
f
Vs
f
Assuming small voltage drop
across Rs and Lls
For below base speed operation:
Frequency reduced at rated Vs - airgap flux saturates
(f ,ag and enters saturation region oh B-H curve):
- excessive stator currents flow
- distortion of flux wave
- increase in core losses and stator copper loss
Hence, keep ag = rated flux
stator voltage Vs must be reduced proportional to reduction in f
(i.e. maintaining Vs / f ratio)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
14
Slide 15
Constant Volts/Hz (V/f) Control
Max. torque remains almost
constant
For low speed operation:
can’t ignore voltage drop across
Rs and Lls (i.e. E1 Vs)
poor torque capability
(i.e. torque decreased at low
speeds shown by dotted lines)
stator voltage must be boosted
– to compensate for voltage
drop at Rs and Lls and maintain
constant ag
ag
E1
f
Vs
f
T max
Vs
2
s
For above base speed operation
(f > frated):
stator voltage maintained at
rated value
Same as Variable Frequency
control (refer to slide 13)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
15
Slide 16
Constant Volts/Hz (V/f) Control
Vs
Vs vs. f relation in Constant Volts/Hz drives Boost - to
compensate for
voltage drop at Rs
and Lls
Vrated
Linear offset curve –
• for high-starting
torque loads
• employed for most
applications
Linear offset
Boost
Dr. Ungku Anisa, July 2008
Non-linear offset
curve –
• for low-starting
torque loads
Non-linear offset – varies with Is
EEEB443 - Control & Drives
frated
f
16
Slide 17
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
fs = Kfs,rated s = Ks,rated
(1)
(Note: in (1) , speed is given as mechanical speed)
KV s , rated , when f s f s , rated
Stator voltage: V s
V s , rated , when f s f s , rated
(2)
Voltage-to-frequency ratio = d = constant:
d
Dr. Ungku Anisa, July 2008
V s ,rated
s ,rated
EEEB443 - Control & Drives
(3)
17
Slide 18
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
Hence, the torque produced by the motor:
Te
3R
'
r
Vs
2
s s
R
K
R s
s
'
r
2
2
X ls
X lr
2
(4)
where s and Vs are calculated from (1) and (2)
respectively.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
18
Slide 19
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
The slip for maximum torque is:
'
s max
Rr
2
Rs K
2
X ls
X lr
(5)
2
The maximum torque is then given by:
T max
Vs
3
2 s R
s
2
Rs K
2
2
X ls
X lr
2
(6)
where s and Vs are calculated from (1) and (2)
respectively.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
19
Slide 20
Constant Volts/Hz (V/f) Control
Rated (Base)
frequency
Constant
Torque Area
(below base speed)
Field Weakening Mode (f > frated)
• Reduced flux (since Vs is constant)
• Torque reduces
Constant Power Area
(above base speed)
Note:
Operation restricted
between synchronous
speed and Tmax for
motoring and braking
regions, i.e. in the
linear region of the
torque-speed curve.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
20
Slide 21
Constant Volts/Hz (V/f) Control
Constant Torque Area
Constant Power Area
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
21
Slide 22
Example
A 4-pole, 3 phase, 400 V, 50 Hz, 1470 rpm induction
motor has a rated torque of 30 Nm. The motor is used to
drive a linear load with characteristic given by TL = K,
such that the speed equals rated value at rated torque. If
a constant Volts/Hz control method is employed,
calculate:
The constant K in the TL - characteristic of the load.
Synchronous and motor speeds at 0.6 rated torque.
If a starting torque of 1.2 times rated torque is required, what
should be the voltage and frequency applied at start-up? State
any assumptions made for this calculation.
Answers:
K = 0.195, synchronous speed = 899.47 rpm & motor speed = 881.47 rpm,
At start up: frequency = 1.2 Hz, Voltage = 9.6 V
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
22
Slide 23
Constant Volts/Hz (V/f) Control –
Open-loop Implementation
PWM
Voltage-Source
Inverter
(VSI)
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
23
Slide 24
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Most popular speed control method because it is easy to
implement
Used in low-performance applications
where precise speed control unnecessary
Speed command s* - primary control variable
Phase voltage command Vs* generated from V/f relation
(shown as the ‘G’ in slide 23)
Boost voltage Vo is added at low speeds
Constant voltage applied above base speed
Sinusoidal phase voltages (vabc*) is then generated from Vs* &
s* where s* is obtained from the integral of s*
vabc* employed in PWM inverter connected to motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
24
Slide 25
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Problems in open-loop drive operation:
Motor speed not controlled precisely
primary control variable is synchronous speed s
actual motor speed r is less than s due to sl
sl depends on load connected to motor
r
P
P
2
2
m
s sl
sl cannot be maintained since r not measured
can lead to operation in unstable region of T- characteristic
stator currents can exceed rated value – endangering inverterconverter combination
Problems (to an extent) can be overcome by:
Open-loop Constant Volts/Hz Drive with Slip Compensation
Closed-loop implementation - having outer speed loop with
slip regulation
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
25
Slide 26
Constant Volts/Hz (V/f) Control –
Open-loop Implementation
Open-loop Constant Volts/Hz Drive with Slip Compensation
- Slip speed is estimated and added to the reference speed r*
Vdc = Vd
Idc
Slip
Compensator
sl
r*
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
26
Slide 27
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Open-loop Constant Volts/Hz Drive with Slip Compensation
How is sl estimated in the
Slip Compensator?
Using T- curve, sl Te
sl can be estimated by
estimating torque where:
Te
Pag
s
Pin PSCL inverter
s
(8)
Pin V dc I dc
sl
Te
T
e , rated
Dr. Ungku Anisa, July 2008
losses
sl , rated
(7)
Note: In the figure,
slip= sl = slip speed
syn= s = synchronous speed
(9)
EEEB443 - Control & Drives
27
Slide 28
Constant Volts/Hz (V/f) Control –
Closed-loop Implementation
Open-loop system
(as in slide 23)
Slip Controller
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
28
Slide 29
Constant Volts/Hz (V/f) Control –
Closed-loop Implementation
Reference motor speed r* is compared to the actual speed r
to obtain the speed loop error
Speed loop error generates slip command sl* from PI
controller and limiter
Limiter ensures that the sl* is kept within the allowable slip
speed of the motor (i.e. sl* slip speed for maximum torque)
sl* is then added to the actual motor speed r to generate
synchronous speed command s* (or frequency command)
s* generates voltage command Vs* from V/f relation
Boost voltage is added at low speeds
Constant voltage applied above base speed
Scheme can be considered open loop torque control (since
T s) within speed control loop
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
29
Slide 30
Constant Airgap Flux Control
Constant V/f control employs the use of variable frequency
voltage source inverters (VSI)
Constant Airgap Flux control employs variable frequency
current source inverters or current-controlled VSI
Provides better performance compared to Constant V/f
control with Slip Compensation
airgap flux is maintained at rated value through stator current
control
Speed response similar to equivalent separately-excited dc
motor drive but torque and flux channels still coupled
Fast torque response means:
High-performance drive obtained
Suitable for demanding applications
Able to replace separately-excited dc motor drives
Above only true is airgap flux remains constant at rated value
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
30
Slide 31
Constant Airgap Flux Control
Constant airgap flux in the motor means:
ag
E1
2 f
Assuming small voltage drop
across Rs and Lls
L m I m constant
For ag to be kept constant at rated value, the magnetising current Im
must remain constant at rated value
Hence, in this control scheme stator current Is is controlled to
maintain Im at rated value
Controlled to maintain Im at rated
Rs
Lls
Is
Llr’
+
+
Vs
Ir ’
Lm
maintain at rated
–
Dr. Ungku Anisa, July 2008
E1 Vs
Rr’/s
Im
–
EEEB443 - Control & Drives
31
Slide 32
Constant Airgap Flux Control
From torque equation (with ag kept constant at rated value),
since ss = sl and ignoring Rs and Lls,
2
'
2
Rr
P Vs
P E1
Te 3
3
2
'
2
s
2 sl
s
Rr
2
X ls X lr
R s
s
'
Rr
2
R '
2
r
s s L lr
sl
By rearranging the equation:
2
PE
Te 3 1 2
2 s R '
r
sl
R r'
sl
P 2
T
3
ag
e
2
2
2
L lr
R r'
sl
R '
r
sl
2
L lr
2
Te sl sl can be varied instantly instantaneous (fast)
Te response 32
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Slide 33
Constant Airgap Flux Control
Constant airgap flux requires control of magnetising current Im which is
not accessible
From equivalent circuit
(on slide 31):
'
j s L lr
'
Im
Rr
j s ( L lr L m )
'
Is
s
R
'
r
Is
s
j sl T r 1
r
j sl
1 r
T r 1
Im ,
(10)
From equation (10), plot Is against sl when Im is kept at rated value.
Drive is operated to maintain Is against sl relationship when frequency
is changed to control speed.
Hence, control is achieved by controlling stator current Is and stator
frequency:
Is controlled using current-controlled VSI
Control scheme sensitive to parameter variation (due to Tr and r)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Note : T r
Lr
R
'
r
'
, r
L lr
Lm
, sl
elec
s
elec
r
33
Slide 34
Constant Airgap Flux Control Implementation
Current Controlled VSI
3-phase
supply
Rectifier
C
Current controller options:
• Hysteresis Controller
• PI controller + PWM
r* +
PI
-
IM
Current
controller
slip
|Is|
i*a
i*b
+
s
r
+
Dr. Ungku Anisa, July 2008
Voltage
Source
Inverter
(VSI)
r
EEEB443 - Control & Drives
i*c
Equation (10)
(from slide 33)
34
Slide 35
Current-Controlled VSI
Implementation
Hysteresis Controller
i*a
i*b
i*c
+
Voltage
Source
Inverter
(VSI)
+
+
Motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
35
Slide 36
Current-Controlled VSI
Implementation
PI Controller + Sinusoidal PWM
i*a
+
i*b
i*c
PI
+
PWM
PI
+
PWM
PI
•Due to interactions between phases
(assuming balanced conditions)
actually only require 2 controllers
Dr. Ungku Anisa, July 2008
Voltage
Source
Inverter
(VSI)
EEEB443 - Control & Drives
PWM
Motor
36
Slide 37
Current-Controlled VSI
Implementation
PI Controller + Sinusoidal PWM (2 phase)
i*a
i d*
i*b
abcdq
PI
dq abc
i q*
PI
PWM
Voltage
Source
Inverter
(VSI)
i*c
iq
id
abcdq
Motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
37
Slide 38
References
Krishnan, R., Electric Motor Drives: Modeling, Analysis and Control,
Prentice-Hall, New Jersey, 2001.
Bose, B. K., Modern Power Electronics and AC drives, Prentice-Hall,
New Jersey, 2002.
Trzynadlowski, A. M., Control of Induction Motors, Academic Press,
San Diego, 2001.
Rashid, M.H, Power Electronics: Circuit, Devices and Applictions, 3rd
ed., Pearson, New-Jersey, 2004.
Nik Idris, N. R., Short Course Notes on Electrical Drives,
UNITEN/UTM, 2008.
Ahmad Azli, N., Short Course Notes on Electrical Drives,
UNITEN/UTM, 2008.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
38
Induction Motor – Scalar Control
By
Dr. Ungku Anisa Ungku Amirulddin
Department of Electrical Power Engineering
College of Engineering
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
1
Slide 2
Outline
Introduction
Speed Control of Induction Motors
Pole Changing
Variable-Voltage, Constant Frequency
Variable Frequency
Constant Volts/Hz (V/f) Control
Open-loop Implementation
Closed-loop Implementation
Constant Airgap Flux Control
References
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
2
Slide 3
Introduction
Scalar Control - control of induction machine
based on steady-state model (per phase SS
equivalent circuit)
Rs
Is
Lls
Llr’
+
+
Vs
–
Dr. Ungku Anisa, July 2008
Ir ’
Lm
Im
EEEB443 - Control & Drives
E1
Rr’/s
–
3
Slide 4
Introduction
Te
Pull out
Torque
(Tmax)
Intersection point
(Te=TL) determines the
steady –state speed
Te
TL
Trated
What if the load must
be operated here?
s
sm
1
Dr. Ungku Anisa, July 2008
rated
rotors
rotor’
0
EEEB443 - Control & Drives
r
Requires speed
control of motor
4
Slide 5
Speed Control of IM
Given a load T– characteristic, the steady-state speed can be
changed by altering the T– curve of the motor
Te
3R
s
2
'
r
Vs
2
2
2
'
s s
Rr
2
X ls X lr
R s
s
P
4
3
f
P
1
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Varying voltage
(amplitude)
Varying line
frequency
Pole Changing
5
Slide 6
Speed Control of IM
Pole Changing
Machines must be specially manufactured (i.e. called pole changing
motors or multi-speed motors)
Need special arrangement of stator windings
Only used with squirrel-cage motors
Because number of poles induced in squirrel cage rotor will follow
number of stator poles
Two methods:
Multiple stator windings
stator has more than one set of 3-phase windings
only energize one set at a time
simple, expensive
Consequent poles
Discrete step change in speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
6
Slide 7
Speed Control of IM
Pole Changing
Consequent poles
single winding divided into
few coil groups
No. of poles changed by
changing connections of coil
groups
Change in pole number by
factor of 2:1 only
A two-pole stator winding for pole changing.
Notice the very short pitch (60 to 90) of
these windings.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
7
Slide 8
Speed Control of IM
Pole Changing
Consequent poles
Close up view of one phase of a
pole changing winding.
In Figure (a): the 2-pole
configuration, one coil is a north
pole and the other is a south
pole.
In Figure (b): when the
connection on one of the two
coils is reversed, they are both
north poles, and the magnetic
flux returns to the stator halfway
between the two coils. The
south poles are called
consequent poles. Hence the
winding is now 4-pole.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
8
Slide 9
Speed Control of IM
Variable-Voltage (amplitude),
Constant Frequency
Controlled using:
Transformer (rarely used)
Thyristor voltage controller
thyristors connected in anti-parallel
motor can be star or delta connected
voltage control by firing angle control
(gating signals are synchronized to
phase voltages and are spaced at 60
intervals)
Only for operations in Quadrant 1 and
Quadrant 3 (requires reversal of phase
sequence)
also used for soft start of motors
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
9
Slide 10
Speed Control of IM
Variable-Voltage (amplitude), Constant Frequency
Voltage can only be reduced from rated Vs (i.e. 0 < Vs ≤ Vs,rated)
From torque equation, Te Vs2
When Vs , Te and speed reduces.
If terminal voltage is reduced to bVs, (i.e. Vs = bVs,rated) :
Te
3R
'
r
bV
2
s
2
'
s s
Rr
2
X ls X lr
R s
s
Note: b 1
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
10
Slide 11
Speed Control of IM
Variable-Voltage
(amplitude), Constant
Frequency
Suitable for applications
where torque demand
reduces with speed
(eg: fan and pump drives
where TL m2)
Suitable for NEMA Class D
(high-slip, high Rr’) type
motors
High rotor copper loss,
low efficiency motors
get appreciable speed
range
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Practical
speed range
11
Slide 12
Speed Control of IM
Variable Voltage (amplitude),
Constant Frequency
Disadvantages:
limited speed range when
applied to Class B (low-slip) motors
Excessive stator currents at low
speeds high copper losses
Distorted phase current in machine
and line (harmonics introduced by
thyristor switching)
Poor line power factor
(power factor proportional to firing
angle)
Hence, only used on low-power,
appliance-type motors where
efficiency is not important
e.g. small fan or pumps drives
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
12
Slide 13
Speed Control of IM
Variable Frequency
Speed control above rated (base) speed
Requires the use of PWM inverters to control frequency of motor
Frequency increased (i.e. s increased)
Stator voltage held constant at rated value
Airgap flux and rotor current decreases
Developed torque
decreases
Te (1/s)
For control below
base speed –
use Constant
Volts/Hz method
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
13
Slide 14
Constant Volts/Hz (V/f) Control
Airgap flux in the motor is related to the induced stator voltage
E1 :
ag
E1
f
Vs
f
Assuming small voltage drop
across Rs and Lls
For below base speed operation:
Frequency reduced at rated Vs - airgap flux saturates
(f ,ag and enters saturation region oh B-H curve):
- excessive stator currents flow
- distortion of flux wave
- increase in core losses and stator copper loss
Hence, keep ag = rated flux
stator voltage Vs must be reduced proportional to reduction in f
(i.e. maintaining Vs / f ratio)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
14
Slide 15
Constant Volts/Hz (V/f) Control
Max. torque remains almost
constant
For low speed operation:
can’t ignore voltage drop across
Rs and Lls (i.e. E1 Vs)
poor torque capability
(i.e. torque decreased at low
speeds shown by dotted lines)
stator voltage must be boosted
– to compensate for voltage
drop at Rs and Lls and maintain
constant ag
ag
E1
f
Vs
f
T max
Vs
2
s
For above base speed operation
(f > frated):
stator voltage maintained at
rated value
Same as Variable Frequency
control (refer to slide 13)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
15
Slide 16
Constant Volts/Hz (V/f) Control
Vs
Vs vs. f relation in Constant Volts/Hz drives Boost - to
compensate for
voltage drop at Rs
and Lls
Vrated
Linear offset curve –
• for high-starting
torque loads
• employed for most
applications
Linear offset
Boost
Dr. Ungku Anisa, July 2008
Non-linear offset
curve –
• for low-starting
torque loads
Non-linear offset – varies with Is
EEEB443 - Control & Drives
frated
f
16
Slide 17
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
fs = Kfs,rated s = Ks,rated
(1)
(Note: in (1) , speed is given as mechanical speed)
KV s , rated , when f s f s , rated
Stator voltage: V s
V s , rated , when f s f s , rated
(2)
Voltage-to-frequency ratio = d = constant:
d
Dr. Ungku Anisa, July 2008
V s ,rated
s ,rated
EEEB443 - Control & Drives
(3)
17
Slide 18
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
Hence, the torque produced by the motor:
Te
3R
'
r
Vs
2
s s
R
K
R s
s
'
r
2
2
X ls
X lr
2
(4)
where s and Vs are calculated from (1) and (2)
respectively.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
18
Slide 19
Constant Volts/Hz (V/f) Control
For operation at frequency K times rated frequency:
The slip for maximum torque is:
'
s max
Rr
2
Rs K
2
X ls
X lr
(5)
2
The maximum torque is then given by:
T max
Vs
3
2 s R
s
2
Rs K
2
2
X ls
X lr
2
(6)
where s and Vs are calculated from (1) and (2)
respectively.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
19
Slide 20
Constant Volts/Hz (V/f) Control
Rated (Base)
frequency
Constant
Torque Area
(below base speed)
Field Weakening Mode (f > frated)
• Reduced flux (since Vs is constant)
• Torque reduces
Constant Power Area
(above base speed)
Note:
Operation restricted
between synchronous
speed and Tmax for
motoring and braking
regions, i.e. in the
linear region of the
torque-speed curve.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
20
Slide 21
Constant Volts/Hz (V/f) Control
Constant Torque Area
Constant Power Area
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
21
Slide 22
Example
A 4-pole, 3 phase, 400 V, 50 Hz, 1470 rpm induction
motor has a rated torque of 30 Nm. The motor is used to
drive a linear load with characteristic given by TL = K,
such that the speed equals rated value at rated torque. If
a constant Volts/Hz control method is employed,
calculate:
The constant K in the TL - characteristic of the load.
Synchronous and motor speeds at 0.6 rated torque.
If a starting torque of 1.2 times rated torque is required, what
should be the voltage and frequency applied at start-up? State
any assumptions made for this calculation.
Answers:
K = 0.195, synchronous speed = 899.47 rpm & motor speed = 881.47 rpm,
At start up: frequency = 1.2 Hz, Voltage = 9.6 V
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
22
Slide 23
Constant Volts/Hz (V/f) Control –
Open-loop Implementation
PWM
Voltage-Source
Inverter
(VSI)
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
23
Slide 24
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Most popular speed control method because it is easy to
implement
Used in low-performance applications
where precise speed control unnecessary
Speed command s* - primary control variable
Phase voltage command Vs* generated from V/f relation
(shown as the ‘G’ in slide 23)
Boost voltage Vo is added at low speeds
Constant voltage applied above base speed
Sinusoidal phase voltages (vabc*) is then generated from Vs* &
s* where s* is obtained from the integral of s*
vabc* employed in PWM inverter connected to motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
24
Slide 25
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Problems in open-loop drive operation:
Motor speed not controlled precisely
primary control variable is synchronous speed s
actual motor speed r is less than s due to sl
sl depends on load connected to motor
r
P
P
2
2
m
s sl
sl cannot be maintained since r not measured
can lead to operation in unstable region of T- characteristic
stator currents can exceed rated value – endangering inverterconverter combination
Problems (to an extent) can be overcome by:
Open-loop Constant Volts/Hz Drive with Slip Compensation
Closed-loop implementation - having outer speed loop with
slip regulation
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
25
Slide 26
Constant Volts/Hz (V/f) Control –
Open-loop Implementation
Open-loop Constant Volts/Hz Drive with Slip Compensation
- Slip speed is estimated and added to the reference speed r*
Vdc = Vd
Idc
Slip
Compensator
sl
r*
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
26
Slide 27
Constant Volts/Hz (V/f)
Control – Open-loop Implementation
Open-loop Constant Volts/Hz Drive with Slip Compensation
How is sl estimated in the
Slip Compensator?
Using T- curve, sl Te
sl can be estimated by
estimating torque where:
Te
Pag
s
Pin PSCL inverter
s
(8)
Pin V dc I dc
sl
Te
T
e , rated
Dr. Ungku Anisa, July 2008
losses
sl , rated
(7)
Note: In the figure,
slip= sl = slip speed
syn= s = synchronous speed
(9)
EEEB443 - Control & Drives
27
Slide 28
Constant Volts/Hz (V/f) Control –
Closed-loop Implementation
Open-loop system
(as in slide 23)
Slip Controller
Note: e= s = synchronous speed
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
28
Slide 29
Constant Volts/Hz (V/f) Control –
Closed-loop Implementation
Reference motor speed r* is compared to the actual speed r
to obtain the speed loop error
Speed loop error generates slip command sl* from PI
controller and limiter
Limiter ensures that the sl* is kept within the allowable slip
speed of the motor (i.e. sl* slip speed for maximum torque)
sl* is then added to the actual motor speed r to generate
synchronous speed command s* (or frequency command)
s* generates voltage command Vs* from V/f relation
Boost voltage is added at low speeds
Constant voltage applied above base speed
Scheme can be considered open loop torque control (since
T s) within speed control loop
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
29
Slide 30
Constant Airgap Flux Control
Constant V/f control employs the use of variable frequency
voltage source inverters (VSI)
Constant Airgap Flux control employs variable frequency
current source inverters or current-controlled VSI
Provides better performance compared to Constant V/f
control with Slip Compensation
airgap flux is maintained at rated value through stator current
control
Speed response similar to equivalent separately-excited dc
motor drive but torque and flux channels still coupled
Fast torque response means:
High-performance drive obtained
Suitable for demanding applications
Able to replace separately-excited dc motor drives
Above only true is airgap flux remains constant at rated value
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
30
Slide 31
Constant Airgap Flux Control
Constant airgap flux in the motor means:
ag
E1
2 f
Assuming small voltage drop
across Rs and Lls
L m I m constant
For ag to be kept constant at rated value, the magnetising current Im
must remain constant at rated value
Hence, in this control scheme stator current Is is controlled to
maintain Im at rated value
Controlled to maintain Im at rated
Rs
Lls
Is
Llr’
+
+
Vs
Ir ’
Lm
maintain at rated
–
Dr. Ungku Anisa, July 2008
E1 Vs
Rr’/s
Im
–
EEEB443 - Control & Drives
31
Slide 32
Constant Airgap Flux Control
From torque equation (with ag kept constant at rated value),
since ss = sl and ignoring Rs and Lls,
2
'
2
Rr
P Vs
P E1
Te 3
3
2
'
2
s
2 sl
s
Rr
2
X ls X lr
R s
s
'
Rr
2
R '
2
r
s s L lr
sl
By rearranging the equation:
2
PE
Te 3 1 2
2 s R '
r
sl
R r'
sl
P 2
T
3
ag
e
2
2
2
L lr
R r'
sl
R '
r
sl
2
L lr
2
Te sl sl can be varied instantly instantaneous (fast)
Te response 32
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Slide 33
Constant Airgap Flux Control
Constant airgap flux requires control of magnetising current Im which is
not accessible
From equivalent circuit
(on slide 31):
'
j s L lr
'
Im
Rr
j s ( L lr L m )
'
Is
s
R
'
r
Is
s
j sl T r 1
r
j sl
1 r
T r 1
Im ,
(10)
From equation (10), plot Is against sl when Im is kept at rated value.
Drive is operated to maintain Is against sl relationship when frequency
is changed to control speed.
Hence, control is achieved by controlling stator current Is and stator
frequency:
Is controlled using current-controlled VSI
Control scheme sensitive to parameter variation (due to Tr and r)
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
Note : T r
Lr
R
'
r
'
, r
L lr
Lm
, sl
elec
s
elec
r
33
Slide 34
Constant Airgap Flux Control Implementation
Current Controlled VSI
3-phase
supply
Rectifier
C
Current controller options:
• Hysteresis Controller
• PI controller + PWM
r* +
PI
-
IM
Current
controller
slip
|Is|
i*a
i*b
+
s
r
+
Dr. Ungku Anisa, July 2008
Voltage
Source
Inverter
(VSI)
r
EEEB443 - Control & Drives
i*c
Equation (10)
(from slide 33)
34
Slide 35
Current-Controlled VSI
Implementation
Hysteresis Controller
i*a
i*b
i*c
+
Voltage
Source
Inverter
(VSI)
+
+
Motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
35
Slide 36
Current-Controlled VSI
Implementation
PI Controller + Sinusoidal PWM
i*a
+
i*b
i*c
PI
+
PWM
PI
+
PWM
PI
•Due to interactions between phases
(assuming balanced conditions)
actually only require 2 controllers
Dr. Ungku Anisa, July 2008
Voltage
Source
Inverter
(VSI)
EEEB443 - Control & Drives
PWM
Motor
36
Slide 37
Current-Controlled VSI
Implementation
PI Controller + Sinusoidal PWM (2 phase)
i*a
i d*
i*b
abcdq
PI
dq abc
i q*
PI
PWM
Voltage
Source
Inverter
(VSI)
i*c
iq
id
abcdq
Motor
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
37
Slide 38
References
Krishnan, R., Electric Motor Drives: Modeling, Analysis and Control,
Prentice-Hall, New Jersey, 2001.
Bose, B. K., Modern Power Electronics and AC drives, Prentice-Hall,
New Jersey, 2002.
Trzynadlowski, A. M., Control of Induction Motors, Academic Press,
San Diego, 2001.
Rashid, M.H, Power Electronics: Circuit, Devices and Applictions, 3rd
ed., Pearson, New-Jersey, 2004.
Nik Idris, N. R., Short Course Notes on Electrical Drives,
UNITEN/UTM, 2008.
Ahmad Azli, N., Short Course Notes on Electrical Drives,
UNITEN/UTM, 2008.
Dr. Ungku Anisa, July 2008
EEEB443 - Control & Drives
38