Protect233 - SIER Romania

Download Report

Transcript Protect233 - SIER Romania

Presentation
Protect 2
1
Allround UPS - Product portfolio
PROTECT 2. 33
PROTECT 3. 31
PROTECT 3. 33
PROTECT 4. 33
Power [ kVA ]
10
20 30 40 50 60 70 80 100 120 160 220 300 400 500 600 8001000
3 ph ~ / 3 ph ~ transformerless
3 ph ~ / 1 ph ~
3 ph ~ / 3 ph ~
2
PROTECT 2. 33 20kVA (10kVA)
weight :
250kg without battery
490kg with integrated battery
&
PROTECT 2. 33 40kVA (30kVA)
weight:
400 kg without battery
1500mm
600mm
3
New UPS Protect 2.33
10 / 20kVA
1500mm
30 / 40kVA
1900mm
4
What´s new ?

Transformerless
SBS
Mains
Loads
PulseRectifier
Inverter
2x
400Vdc

Charger
Booster
sinusodial
Input current

2x
Battery
Safe load bus
132V-
2x232Vdc
UPS
5
New UPS Protect 2.33
Normal-Mode (Mains available)
SBS
Mains
Loads
P-Rectifier
Inverter

Charger
2x 400Vdc
Booster

Battery
Safe load bus
2x 132-
2x 228VDC
UPS
6
BATTERY-Mode
SBS
Mains
Loads
P-Rectifier
Charger
Inverter
Booster
Safe load bus
Battery
UPS
7
BYPASS-Mode
SBS
Mains
Loads
P-Rectifier
Charger
Inverter
Booster
Safe load bus
Battery
UPS
8
New UPS Protect 2.33
IGBTAnsteuerung
L22.1
F5
L20.2
L22.2
F6
L20.3
L22.3
F4
V
W
IGBTAnsteuerung
IGBTAnsteuerung
Inverter
IGBTAnsteuerung
3 x 400V
IGBTAnsteuerung
C42.1
C1
C2
L20.1C3
U
L1,L2,L3
T21,T22,
T23
F1
T11,T12,
T13
K7
X3
U
F2
V
F3
W
N
IGBTAnsteuerung
IGBTAnsteuerung
IGBTAnsteuerung
IGBTAnsteuerung
IGBTAnsteuerung
C4,C5,C6
IGBTAnsteuerung
F42.2
OPTION
K40
Q10
X1
T80
T81
T82
IGBTAnsteuerung
•
C42.2
3 x 400V
F42.1
Rectifier
•
N
DC voltage
2 x 400V
800V
Battery U DC nominal
< 20kVA : 2 x 132V - 2 x 228V
< 40kVA : 2 x 192V - 2 x 228V
2 x 11
- 2 x 19blocks
UPS System
DC range
210 - "Protect
550V 2.33"
IGBTAnsteueru
ng
Q2
X2
L41.1
(+)
IGBTAnsteueru
ng
(M)
IGBTAnsteueru
ng
Booster and Charger
L41.2
(-)
IGBTAnsteueru
ng
27.02.2002 PSS E1M. Berghoff
02.04.02 PSS E1 Mbg
9
New UPS Protect 2.33
Rectifier
–
–
–
–
IGBT technology
sinusoidal input current
low THD I < 3% (low harmonics, compliant with actual
and future standards IEC 61000-3-12 / IEC 61000-3-4 /
IEEE 519)
Cos-Phi / Power factor >0.99
10
New UPS Protect 2.33
Sinusoidal Input Current
as build-in Feature
Input Voltage:
100 V / screen
t: 5 ms / screen
Input Current:
THDi < 3%
20A / screen
11
New UPS Protect 2.33
Booster / Charger
–
–
–
–
–
–
IGBT technology
DC/DC converter
charger mode : 2 x 400V DC => battery voltage
booster mode / line fail : battery voltage => 2 x 400V DC
charger capacity : 3kW (20kVA system)
Battery Charging Management AeBM
12
New UPS Protect 2.33
Inverter
–
–
–
–
IGBT technology
High-Speed ST 10 Controller for fast dynamic
regulation
output voltage with low THD U < 3% at nonlinear load
able to handle capacitive and inductive loads
13
New UPS Protect 2.33
Static Bypass / Manual Bypass
–
–
–
–
–
–
–
–
–
SCR technology (Thyristors)
convection cooled
fully 100% rated
overload / short circuit capacity 1000% -
synchronization to an alternate line voltage with high harmonic
content
THDu < = 10%: IEC 61000-2-4 Class 3 for industrial environment !
synchronization range adjustable
slew rate adjustable
Manual bypass switch integrated
14