Transcript Document
MCS-Magnum Chiller Logic www.mcscontrols.com Rev A MCS-Magnum Block Diagram Memory Flash Memory (8MB) • • • • • • • • • Firmware Operation System Control Logic Communications Scan Keypad Write the LCD display Configuration Setpoints #of Compressors Refrigerant type Etc. Zilog MicroController RAM Memory (2MB) • • • • Control Variables Control States History/Trending Communication Alarm History • Microprocessor • Real Time Clock • Ethernet • RS485 • MCS-I/0 Inputs/Outputs • Relay outputs • Sensor inputs • Analog outputs HMI • Key pad/LCD MCS-Magnum Firmware Versions HVAC 16.XX - Chiller & Condensing Units CENT 16.XX - Centrifugal Chillers REFR 16.XX - Refrigeration Storage Units RTU 16.XX - Roof Top Package A/C Units MCS Control Options Up to 20 compressors/refrigeration circuits Up to 4 stages per compressor All Compressor Types Reciprocating Screw Centrifugal Scroll All Condenser Types Air-cooled Water-cooled Evaporative-cooled MCS Control Options All Evaporator Types Shell and tube Flooded barrel Plate heat exchanger Dx air coil Chilled Water Reset Hard wired Network Automatic MCS Control Options Two Independent Electronic Expansion Value (EXV) Controllers per Compressor Pump Down / Disable switches Low Suction PSI Unloading High Discharge PSI Unloading High Discharge Temperature Unloading High Ampere Unloading & Holding Low Evap Temp Unloading & Holding MCS Control Options Energy Efficient Compressor Staging Chiller Water Pump Control (Primary / Standby) Part Wind, Star Delta or Across the Line (Fix Time or Dynamic) Low & High Ambient Shutdown English, Metric, or Mixed Sensor Readings Compressor Auto Rotation (Lowest Run Hours or First on/First Off) MCS-Magnum Control Logic The Control logic runs every second: Reads all sensor inputs Checks chiller safeties Checks compressor(s) safeties Runs unit state controller Runs once for each compressor: Runs compressor state controller Runs EXV state controller Runs Condenser logic Stores graphing and trending data State Controller A State controller is a system that functions based on its current state Switches states based on sensor inputs The relay outputs and analog outputs are determined by the current state Simplified Unit State Controller LOADING State UNLOADING State RUN/STOP State HOLDING State State Controller The MCS-Magnum runs three state controls: Unit Control Compressor Control EXV Control These states along with their relevant information can be viewed in the System Status window of MCS-Connect State Controller in Connect Unit Control Information Current State Mode Step Delay Ref Type Wanted % Current Rate of Change Sensor Wanted/Actual Current Controlling Time Mode isthe either type used Value thatWanted is counted Refrigerant Ratecompressor ofThe change (up value to 60 of Number of current Time passed in capacity Cooling, heating, or down. When this value seconds) of the current Wanted Onpercentage versus controlling sensor the steps current zero, the controlling sensor ice making Numberreaches of capacity state controller steps Actually On will determine Background color changes if a change in the system based on proximity to capacity is required target temperature State Controller in Connect Compressor Control Current State Time PSI Diff FLA % Lead? Steps The leadnumber compressor Current Current percentage Time passed in calculated The of current of have ‘Yes’ in this oilfull pressure load amps stepswill the current that areaturned column state on for this compressor State Controller in Connect EXV Control Current State Time Valve Control % OnSuperHeat Suct. Supht ADJ ROCDelay The current The rate value When of change of this thevalue of reaches zero, Time passed inThe current percentage superheat superheat of for the this controller based on the will adjust the the current each compressor EXV time defined EXV based in the on the current state superheat status target setpoint State Controller in Connect Additional Circuit Information Unit Control States UNIT IN POWER UP System Reset or Power Returned (delay of 60 seconds or set point value) UNIT IS OFF System ready to run but no cooling capacity required UNIT IS HOLDING No change in capacity. UNIT UNLOADING Reducing chiller capacity - unloading. UNIT IS LOADING Increasing chiller capacity - loading UNIT UNLOADED Chiller is fully loaded - all available stages of cooling capacity are on. UNIT IS LOADED Chiller is fully unloaded - all stage of cooling capacity are off. RUN/STOP SW OFF RUN STOP sensor input is OFF - chiller turned off. OFF- NO EVAP FLOW FLOW SW sensor input is OFF - chiller turned off. SCHEDULED OFF Operating schedule is false. AMBIENT OFF Low Ambient Temperature - chiller turned off. UNIT IN LOCKOUT Chiller locked out, all points except alarm point are OFF NO RUN- I/O LOST Lost communication Chiller locked out Compressor Control States LOST IO LOCKED CMP LOCKED OUT SWITCHED OFF This state is entered when the Capacity Control State is NO RUN- I/O LOST. The compressor is in a lockout state This state is entered when the compressor is off due to the pump down switch being on or the compressor flow switch being off. UNLD and PMPDWN This state is entered when the pump down switch has been turned on or if this compressor is no longer Wanted On CMP ANTICYCE This state is entered when the UNLD and PMPDWN state has been completed CMP OFF/READY This state is entered when no capacity is required from this compressor, or the last state was CMP ANTICYCE, LOST I/O LOCKED, or SWITCHED OFF. OIL PMP LUBING This state is used to ensure proper oil flow prior to compressor startup CMP UNLOADED In this state the compressor is supplying its minimum cooling capacity. CMP IS HOLDING In this state, the required refrigeration capacity of system is being met; no movement of the slide valve is required. FAST UNLOADING For screw compressors only, this state is entered when the compressor is turned on. LO SUCT UNLOAD The capacity is being unloaded due to low suction pressure. LO SUCT HOLD Capacity is being held due to low suction pressure HI DISC UNLOAD The capacity is being unloaded due to a high discharge pressure, high discharge temperature, or low discharge superheat. HI DISC HOLD Capacity is being held due to high discharge temperature or pressure. SAFETY TRIPPED This state is entered when a safety trip occurs but a lockout is not generated. LO TMP UNLOAD This state is entered when the leaving liquid temperature is too low LO TMP HOLD This state in entered after releasing from LO TMP UNLOAD HI AMP HOLD This state occurs when a fully loaded compressor experiences an abnormally high amp draw. HI DIS TMP HLD This state is entered when a fully loaded compressor that has more than one step encounters a high discharge temperature. *Please see the MCS-Magnum manual for a complete list of compressor Control States EXV Control States LOCKED OUT EXV IS CLOSED PRE-PMPDWN EXV IN STARTUP EXV AT 100% EXV IS HOLDING EXV IS OPENING EXV IS CLOSING LOW SPRHT OPENING 4x OPENING 2x LO PSI OPN CLOSING 2x CLOSING 4x HI LVL CLS EXV MOP CLS EXV MOP HLD The compressor is in a Lockout state. The associated compressor is OFF and the valve is closed The valve has been in a closed state and the system is now requiring the valve action. At startup the valve will remain in this state for the time in Setpoint #20. At that time the state will be changed to holding, at this point the valve control logic will position the valve. This state will be entered when the valve opening reaches 100%. Refer to EXV Logic Chart, superheat is in control zone and ROC is acceptable. Refer to EXV Logic Chart, superheat is in control zone but rising too fast, ROC less than 1.0. Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, ROC greater than –0.5. Refer to EXV Logic Chart, force a course valve adjustment. Refer to EXV Logic Chart, superheat is above control zone. Refer to EXV Logic Chart, superheat is in control zone but rising too fast, the ROC is greater than 1.0. Refer to EXV Logic Chart, state indicates that a low suction pressure condition exists. The suction pressure is less than Setpoint #77 “LOW SUCTION” plus twice the value of Setpoint #79 “LOW SUCT RELOAD” and the superheat is greater than Setpoint #9 “SUPERHT TRGT” plus twice the value of Setpoint #10 “SPRHT ZONE+-“. Refer to EXV Logic Chart, superheat is in the control zone and the rate of change is acceptable, the ROC is less than -0.5 and greater than -1.0. Refer to EXV Logic Chart, superheat is in control zone but falling too fast, ROC less than -1.0. This state indicates that a high refrigerant level. This state is entered if Setpoint #109 “HiRefLevel” is active and the superheat is greater than the value of this Setpoint. Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to close. In this state the EXV valve’s opening will be reduced. Refer to EXV Logic Chart. Maximum operating pressure option is active and it is forcing the EXV to hold. Fixed Step Capacity Unit capacity can be controlled by turning on or off: Compressor(s) The ‘Steps’ result from Unloader(s) the relay turning ‘On or Off’ Hot Gas Bypass Fixed Step Capacity 100% Capacity 75% 50% 25% 0% 0 1 2 3 Number of Steps On 4 5 Variable Step Capacity Unit capacity can be controlled by modulating: Screw compressor slide Compressor(s) with a VFD Centrifugal with vanes The line results from modulating control Digital Scroll Variable Capacity 100% Capacity 75% 50% 25% 0% Zone Control Target (Setpoint #1) The desired value to maintain the controlling sensor at Control Zone+ & Control Zone- (Setpoint #2 & #3) Allowable range around the target Controling In The Zone Above the zone 48 47 In the zone In the zone Degrees (F) 46 45 Target 44 Control Zone 43 42 41 Time (seconds) Below the zone Chiller Control Decision Making Set points establish target / control zone How far from the target setpoint is current control sensor value How fast is it moving to or away from the control target The decision is then made to increase, decrease or maintain the cooling capacity Control based on: Entering temperature Leaving liquid temperature Suction PSI Controlling sensor’s rate of change (ROC) is calculated Rate of Change 120 miles 120 miles 5 hours 5 hours of driving Rate of Change In Chillers Rate of change is used as a hold mechanism, which holds the capacity if the temperature is moving quick enough Set points #27 Max ROC#28 Max ROC+ #29 ROC Interval - Max. (negative) ROC above control zone. - Max. (positive) ROC below control zone - ROC time period (in seconds, max 60s) Setpoints #27 & #28 define the speed limits for the change in temperature Negative Rate Of Change Positive Rate Of Change 300 300 200 200 100 100 0 0 0 5 10 0 5 10 Applied Rate of Change Logic Control above the zone Unit Control Starts in LOADING Current ROC > MAX ROCUnit Control Capacity Controlcontinues Above the Zone LOADING Current ROC ≈ MAX ROCUnit Control HOLDS 54 Degrees (F) 52 50 48 Current Value 46 Target 44 Control Zone 42 40 0 5 10 15 20 25 30 Time (seconds) 35 40 45 Applied Rate of Change Logic Control in the zone In Control Zone Max ROC- < ROC < MAX ROC+ Unit Control is HOLDING In Control Zone Current ROC < MAX ROC- In Control Zone Current ROC > MAX ROC+ Unit Control starts UNLOADING Capacity Control In Zone 48 Unit Control starts LOADING 47 Degrees (F) 46 45 44 Current 43 Target Control Zone 42 41 40 0 10 20 30 40 Time (seconds) 50 60 Applied Rate of Change Logic Control below the zone Capacity the Zone CurrentControl ROC < Below MAX ROC+ Unit 50 Control Starts UNLOADING Unit Control continues UNLOADING 47 Degrees (F) Current ROC ≈ 1°F/s Unit Control HOLDS 44 Current Value Target 41 Control Zone 38 35 0 5 10 Time (seconds) 15 20 MCS Safeties The MCS-Magnum is designed to take corrective action to prevent a safety from occurring. The MCS-Magnum checks for safeties every second. Safeties can apply to the entire package or individual circuits. If a safety does occur, the system will: generate an alarm message shut the circuit or package down attempt to restart (after a period of time) Note, time is unique to each safety. If the same safety trips within a period of time a lockout will be created MCS Safeties ITEM VALUE TIME SAFETY LOCKOUT HI DISC PSI HDISC P UNLD HDISC RELD 360 20 40 2 SEC - YES - YES (2X - 2HRS) - (AS REQD) - (AS REQD) LO SUCT PSI LSUCT P UNLD LSUCT P RELD UNSAFE SUCT 55 1 3 10 90 SEC 3 SEC YES - YES (2X - 2HRS) - (AS REQD) - (AS REQD) YES (1 TIME) MCS Safeties ITEM VALUE TIME SAFETY LOCKOUT HI DISC TMP HDISC T UNLD HDISC T RELD 215 2 5 10 SEC - YES - YES (2X - 2HRS) - (AS REQD) - (AS REQD) HI AMPS LOW AMPS 110 20 10 SEC 10 SEC YES YES YES (2X - 2HRS) YES (2X - 2HRS) LOW OIL DIFF UNSAFE OIL 70 15 45 SEC 3 SEC YES - YES (2X - 2HRS) YES (1 TIME) MCS Alarm Notifications Alarms are displayed most current first Reason for the alarm, for example “LOW SUCTION #1” a low suction alarm for circuit #1 was generated Each alarm is date/time stamped e.g. “MAY 30 13:17:33” A lock out situation will not be created unless the same alarm occurs twice within a specified time, except Phase Loss, EMG/STOP, unsafe suction Training Class Exercise 1 Load the compressor to 100% capacity Place the RUN/STOP in the RUN state set the CHIL WTR sensor input higher than the target to simulate a demand The Step Delay will be decremented by the distance from the current value to the target When the Step Delay reaches zero, the system calculates the ± % change required up to a maximum (SP 30 & 31) Training Class Exercise 2 Simulate a High Amp Unload When the Amps of the compressor reach half the value of SP ‘HI AMPS % it will start to unload If the HI AMPS % (SP 75) is 115 Start unloading begins at 107.5% Safety occurs at 115% of the FLA If FLA of compressor 1 (SP 171) is 102 then adjusting the amps between 109 and 116 will start unloading the compressor Questions?