ClearFire-LC Hydronic Boiler Solution

ClearFire-V - Steam ClearFire-H - Steam ClearFire-C - Condensing ClearFire-W - Near Condensing 2

ClearFire Family

Capacities from 400 to 12,000 MBH

ClearFire-LC - Condensing

Overview

Total integration in a small footprint with unprecedented power for hydronic applications • New in 2013, the revolutionary CFLC line provides maximum flexibility for larger facilities with enhanced efficiency • The larger capacity design allows the most effective installation by using fewer units as opposed to banks of smaller boilers, thus reducing capital cost, complexity and maintenance • Rounds out the ClearFire product offering 3

ClearFire-LC

• • • • • • • • •

Features

Fully condensing hydronic boiler Ultra-low emissions True counter-flow heat transfer – up to 99% efficiency Maximized effective heating surface Reduce energy consumption by as much as 40 –50% compared to traditional non-condensing boiler systems Standard 5:1 turndown Compact footprint and application versatility for maximum design flexibility Complete factory integrated package Standard design: • • • ASME Section IV Hot Water 160# MAWP, 250F MAWT cULus Listed, ASME CSD-1 4

ClearFire-LC

ClearFire-LC Capacity

Six sizes ranging from 4,000 to 12,000 MBTU/hr Can support facilities requiring as much as 96,000 MBH in one condensing heating plant – when implementing our integrated lead-lag control with up to 8 boilers

4000 5000 6000 8000 10000 12000 = = = = = = 4,000 MBTU/hr 5,000 MBTU/hr 6,000 MBTU/hr 8,000 MBTU/hr 10,000 MBTU/hr 12,000 MBTU/hr

5

ClearFire-LC Applications

• • • • Building Heating, Process Heating Institutional: hospitals, schools, universities Larger office, hotels or corporate campuses Hybrid hydronic heating systems – new and retrofit Any hydronic system requiring fewer number of condensing boilers 6

7

ClearFire-LC

Premix Gas Burner True Counter-Flow Arrangement

8

ClearFire-LC

Optimized Heat Exchanger

EX Spiral Tubes SS AluFer® Tubes

Large Water Volume Low Water side Pressure Drop Low Flow Tolerant

9

ClearFire-LC

Optimized Heat Exchanger

Water Supply Outlet Thermal Shock Resistant No Minimum Return Temp Water Return Inlets

Low Temperature Return Inlet High Temperature Return Outlet

10

ClearFire-LC

Dual Temperature Returns

Enhanced Condensing Performance More Energy Saving Opportunities

Low Emissions – Linear PID Modulation Combustion Air Inlet Venturi Fuel Train Variable Speed Premix Blower

11

ClearFire-LC

Premix Burner, Ultra-Low Emissions

Full Modulation With 1:1 Fuel-Air Ratio Control Flue Gas Outlet Flue & Condensate Collection Chamber

ClearFire-LC

Integrated Control

Falcon Hydronic Control Built-In Lead-Lag (Up To 8 Boilers), Outdoor Reset & Pump/Valve Control

12

Building Energy Management System Interface To Minimize Energy Wasting Short Cycling