Topic II. 4. Dry Weather Design Flowrates

Download Report

Transcript Topic II. 4. Dry Weather Design Flowrates

Topic II. 4. Dry Weather Design Flowrates
Basic Sewage Quantity Parameters
I. Domestic Sewage flowrates
 Specific sewage flowrate - qs, l/d.ca
qs = 0,9.q0
 Mean daily sewage flowrate - Qm.d, m3/d
Qm.d = qs.N/1000
 Maximal daily sewage flowrate - Qmax.d, m3/d
Qmax.d = qs.N.Kh/1000
Kh - coefficient of hourly variability
1
Basic Sewage Quantity Parameters
 Maximal hourly sewage flowrate - Qmax.h, m3/h
Qmax.h = qs.N.K0/24.1000
where
K0 = 1 + 2,5/ (Qm.d)0,22 ; Qm.d - in l/s
K0 - maximal coefficient of general variability
 Sewage flowrate module - qm , l/s.ha
qm = (Qm.d -  Qs,conc) / F.86400
2
Basic Sewage Quantity Parameters
II. Industrial Sewage Flowrates
 Mean daily sewage flowrate - Qm.d, m3/d
Qm.d = qind.Md/1000
 Maximal hourly sewage flowrate - Qmax.d, m3/h
Qmax.h = qind.Mh.Kh/1000
3
Sewage Design Flowrates
Separate Sewer System
(Dry Weather Flow)
 Sewage design flowrate - Qd, l/s
Qd = 2Qmax,h = 2(qm.f.K0 +  Qs,conc +  Qmax.h)
where
K0 = 1 + 2,5/(qm.f)0,22
4