Revenue metering - Schneider Electric

Download Report

Transcript Revenue metering - Schneider Electric

Monitor service
entrances and
substations
PowerLogic® ION8600
Add application photo in this area
Make the most of
your energy
Make the most
of
SM
your energy
Overview
● Monitor network interties, service entrances and substations
● Ideal for independent power producers and co-generation applications
● Accurately measures energy bi-directionally, in both generation and standby modes
● Gives utilities the tools to manage complex energy supply contracts
● Includes commitments to power quality
● Integrate with energy management and SCADA systems
Copyright © Schneider Electric 2008. All rights reserved.
2
Revenue metering
● ION8600 meters meet stringent IEC and ANSI revenue metering
standards on true RMS voltage, current, and power
● ANSI C12.20 0.2, Class 2, 10, & 20
● IEC 62053-22 Class 0.2S
● The meters perform power quality and compliance monitoring in
accordance with CBEMA/ITIC, IEEE 519 – 1992, and IEEE 1159 and
monitor flicker to IEC 61000-4-15, and harmonics to IEC 61000-4-7
● Multi-user, multi-level security protects the ION8600 meter, allowing you
to control and customize access for up to 16 users
Copyright © Schneider Electric 2008. All rights reserved.
3
Modularity and communications
● ION8600 meters use patented ION® technology, giving meters a
modular, flexible architecture that allows for extensive user
programmability
● Meters address complex monitoring and control applications, and avoid
obsolescence by adapting to changing needs
● The ION8600 offers complete communications: fiber, Ethernet, serial,
and modem
● Gateway functionality simplifies communications architecture and reduces
leased line or connection costs
● Ports communicate with a variety of protocols (ION, DNP 3.0, Modbus RTU,
Modbus TCP, MV-90)
● Meters have the capability to dial out when memory is near full, and to push
data through SMTP (email)
Copyright © Schneider Electric 2008. All rights reserved.
4
Front panel characteristics
Backlit LCD Display
Master Reset Pinhole
(located under front label)
Demand Reset Switch
Test Mode Button
(located under front label)
Alt/Enter Button
Navigation Buttons
Copyright © Schneider Electric 2008. All rights reserved.
5
Features
Feature
ION8600
A
ION8600
B
ION8600
C
■
■
■
■
■
■
Harmonics: individual, even, odd, up to
63rd
63rd
31st
Harmonics: magnitude, phase, & interharmonics
40th
■
■
Metering
Power, energy and demand
Power quality
Sag/swell, harmonics monitoring
Symmetrical components: zero, positive,
negative
■
Transient detection, microseconds (68 µs for
60 Hz, 78 µs for 50 Hz)
65/78
Sampling rate, maximum samples per cycle
256
256
256
■
■
■
10 MB
4 MB
2 MB
■
■
■
0.001
0.001
0.001
Uptime in number of nines
Logging and recording
Memory standard/optional
Min/max logging for any parameter
Timestamp resolution in seconds
Copyright © Schneider Electric 2008. All rights reserved.
6
Features
Feature
ION8600A
ION8600B
ION8600C
■
■
■
RS-232/485; RS-485; Ethernet; Optical; IRIG-B
■
■
■
Internal modem
1
1
1
3-port DNP 3.0 via serial, modem, Ethernet, I/R ports
■
■
■
Modbus RTU slave/master; Modbus TCP via Ethernet
■
■
■
EtherGate, ModemGate, MeterM@il, WebMeter
■
■
■
Internal KYZ outputs/Form A inputs
4/3
4/3
4/3
Ext. digital status inputs/counter/solid state outputs
8/8
8/8
8/8
Setpoints, number/minimum response time
65/ ½ cycle
65/ ½ cycle
65/ 1 sec
Math, logic, trig, log, linearization formulas
■
■
■
Call-out on single- and multi-condition alarms
■
■
■
MV-90 on serial, modem, & Ethernet ports, (if present)
■
■
■
Multi-year scheduling: hourly activity profiles
■
■
■
Transformer/line loss compensation; ITC
■
■
■
GPS time synchronization
Communications and I/O
Setpoints, alarming, and control
Revenue metering
Copyright © Schneider Electric 2008. All rights reserved.
7
Applications
Use the ION8600 to:
● Perform revenue metering
● Monitor both co-generation and IPP
● Perform energy pulsing and totalization
● Monitor compliance with international standards
● Analyze power quality
● Control demand and power factor
● Performing load curtailment
● Monitor and control your equipment
● Correct instrument transformers
Copyright © Schneider Electric 2008. All rights reserved.
8
Applications
● Revenue metering
● Revenue approved, bi-directional measurements; monitors four quadrants
● Monitor compliance with energy supply contracts
● Energy suppliers: offer customized rates, flexible billing, transformer/line
loss compensation, and web-based reporting
● Energy consumers: audit power requirements and confirm bills
● Highest revenue metering accuracy
● Advanced security for 16 different users – individual passwords and rights
Copyright © Schneider Electric 2008. All rights reserved.
9
Applications
● Co-generation and IPP monitoring
● Monitors bi-directional flow for both generation and stand-by modes
● Energy pulsing and totalization
● Use digital I/O for KYZ pulsing, end-of-interval and totalization
● Compliance monitoring
● Monitor compliance with international flicker and harmonics standards, IEC
61000-4-7/ 4-15
Copyright © Schneider Electric 2008. All rights reserved.
10
Applications
● Power quality analysis
● Detects, records, and communicates information – nature and
sequence of power quality events
● Identify the cause of transients, harmonics, sags and swells
● Measure percentage of system uptime in nines
● Waveform recording and compliance monitoring
● Monitor compliance with international flicker and harmonics standards
● Diagnose and benchmark power quality on the grid and at key
customer locations – allows utility personnel to make informed
decisions
● Analyze problems and avoid repeat interruptions
Copyright © Schneider Electric 2008. All rights reserved.
11
Applications
● Demand and power factor control
● Avoid penalties – load shedding, scheduling, peak shaving and capacitor
bank control
● Standard demand calculation methods: block, rolling block, thermal,
predicted
● Measure on any instantaneous value and record peak and minimum
Copyright © Schneider Electric 2008. All rights reserved.
12
Applications
● Load curtailment
● 800 user configurable channels via 50 data recorders (feature set A)
● Record energy, demand, voltage, current, power quality, etc.
● Implement load curtailment and distributed generation strategies
● Modbus Master enables detailed facility monitoring
●Identify inefficiencies; develop strategic load shedding applications
●Use like an RTU to intelligently poll downstream devices such as relays
or other metering products
Copyright © Schneider Electric 2008. All rights reserved.
13
Applications
● Equipment monitoring and control
● Record details of equipment status
● Use information from several meters to correlate system-wide events and
equipment operation
● Base maintenance schedules on operating history
● Meter all your utilities including gas, steam, water and more
Copyright © Schneider Electric 2008. All rights reserved.
14
Applications
● Instrument transformer correction
● Compensate for line loss, and power and instrument transformers
● Save money and improve accuracy
● Install on the low side of your transformers to compensate for less accurate
equipment
Copyright © Schneider Electric 2008. All rights reserved.
15