PowerLogic ION8800 - Schneider Electric

Download Report

Transcript PowerLogic ION8800 - Schneider Electric

PowerLogic ION8800

energy revenue & power quality meter

A PowerLogic system can help you…

●Lower operations costs ● automated, accurate billing data acquisition lowers administrative costs and eliminates errors while making the data available to regulators, service providers, and end users.

●Improve network reliability ● sophisticated power quality monitoring and reporting provide the information needed to validate compliance, improve system stability, and minimize unplanned downtime.

●Streamline business planning ● detailed information on loading, capacity, stress, and more, remove the guesswork so you can more efficiently coordinate demand-side management programs and optimize capacity planning .

Schneider Electric - Division - Name – Date 2

The most advanced meter available

●The ION8800 energy and power quality meter is the newest high-end meter in the industry-leading family of PowerLogic products ● Designed for tariff metering and power quality monitoring in IEC markets ● Typically applied at interconnection points on medium, high, and ultra-high voltage networks Schneider Electric - Division - Name – Date 3

A modular design ●Retrofit compatible with IEC/DIN 43862 19” rack mount series ●Tailor the meter to the application with numerous I/O options

●Solid-state Form A and Form C digital outputs ●Mechanical alarm relay ●High and low voltage digital inputs

●3 base-model feature sets

●ION8800C - Basic tariff/energy revenue meter with sag/swell monitoring ●ION8800B – ION8800C + EN50160 compliance monitoring ●ION8800A – ION8800B + waveform capture and transient detection Schneider Electric - Division - Name – Date 4

Flexible multi-port communications

●Standard IEC1107 optical port ●Communication module options include ● 1 RS-485/RS-232 + 1 RS-485 serial ports ● Ethernet (10Base-T) or Fibre (10Base-FL) ●EtherGate: daisy-chain 31 devices to RS-485 ●Alarm notification via e-mail ●On-board web server with customizable web pages ● Modem (56 kbps) ●ModemGate: daisy-chain 31 devices to RS-485 ●Simultaneous communication on all ports Schneider Electric - Division - Name – Date Rear view of ION8800 meter picturing Essailec connector and communication module.

5

Energy and power quality metering in one

●The ION8800 meets IEC62053-22 Class 0.2S, the most stringent metering standard ●Measure power quality parameters according to IEC 61000-4-30 Class A, perform power quality compliance monitoring in accordance with EN 50160 standards, and measure flicker & interharmonics according to IEC 61000-4-15 & IEC 61000-4-7 ●Multi-user, multi-level security allows 16 designated users to gain access to the meter with security levels ranging from read access up to administrative rights Schneider Electric - Division - Name – Date 6

Meter characteristics (front panel)

LEDs for alarm, heartbeat, and energy Sturdy handles for easy racking Anti-tamper (revenue) lock Graphical LCD device setup & operational screens Menu control & demand reset buttons IEC1107 optical ports for energy pulsing SCADA (ION, DNP 3.0, DLMS, Modbus) Schneider Electric - Division - Name – Date 7

Meter characteristics (rear connections)

Field-upgradeable Communication module Ethernet (TCP/IP) Serial ports (RS-232 and RS-485) Modem (RJ11) port IEC/DIN 48362 Current inputs Voltage inputs and Digital I/O Schneider Electric - Division - Name – Date 8

Feature summary

Power Quality ION8800A ION8800B ION8800C

Sag/swell monitoring Symmetrical component: zero, positive, negative Harmonics: individual, even, odd, total (up to 63 rd ) Harmonics: magnitude, phase and interharmonics EN50160 compliance monitoring Flicker (IEC 62000-4-15) Configurable for IEEE519-1992, IEEE1159-1995 Transient detection Waveform capture g g g g g g g g g g g g g g g g g g Schneider Electric - Division - Name – Date 9

Feature summary

(cont.)

Communications & Logging/Recording ION8800A ION8800B ION8800C

Modbus TCP master / slave (Ethernet) Modbus RTU master / slave (serial ports) Historical logs, maximum number of channels Waveform logs, maximum number of channels Consecutive waveform cycles captured per MB

Revenue Metering & Standards

IEC 62053-22 class 0,2S compliant Time-of-Use Transformer/line loss compensation MV-90 on serial, modem, and Ethernet ports (if present) g / g g / g 800 96 900

ION8800A

g g g g g / g g / g 640 -

ION8800B

g g g g - / g - / g 32 -

ION8800C

g g g g Schneider Electric - Division - Name – Date 10

Feature summary

(cont.)

Communications and I/O

IEC1107 optical port (COM1) - standard in front of meter RS-485 port (COM2) - selectable on Essailec connector or communications module RS-232/485 port (COM3) - optional on communications module Internal PSTN modem (COM4) - optional on communications module Ethernet port - optional on communications module DLMS, DNP 3.0 & Modbus RTU Slave via serial, modem & optical port Modbus TCP through Ethernet port EtherGate, Webmeter, ModemGate, MeterM@il features IEC1107 Active/reactive visible LED energy optical pulse ports Digital pulse outputs (solid state Form A) (Optional) Digital pulse outputs (solid state Form C) Alarm relay output (Form C) Digital inputs (Optional)

All models

1 1 1 1 1 g g g g 8 4 1 3 Schneider Electric - Division - Name – Date 11

Feature summary

(cont.)

Setpoints, Alarming, and Control All models

Number of setpoints Minimum response time for setpoints Math, logic, trig, log, linearization formulas Call out on single condition & multiple condition alarms 65 ½ cycle g g

Logging and Recording All models

Memory capacity (standard / optional) Maximum data points per MB (channels x depth per recorder) Timestamp resolution in seconds Min/max logging for any parameter GPS time synchronization (standard on serial; optional on IRIG-B) Power line time synchronization 5MB /10MB 165,000 0.001

g g g Schneider Electric - Division - Name – Date 12

Application: network revenue metering

●Metering at generation, transmission, or distribution locations requires: ● Highest standards of accuracy ● Multiple communications ports ● Multiple protocols ● Security ● Compensation algorithms ● Billing system compatibility ● Power quality monitoring ● Web capabilities Schneider Electric - Division - Name – Date 13

Application: network revenue metering

●The ION8800 meets and exceeds network revenue metering requirements: ● IEC 62053-22 class 0,2S accuracy ● Ethernet, modem, and serial communications ● ION, Modbus and DLMS protocols ● Multi-user, multi-level security as well as anti-tamper seals on the meter ● Instrument transformer correction and Transformer/line loss calculation capabilities ● MV-90 compatibility on serial, modem, and Ethernet communications Schneider Electric - Division - Name – Date 14

Application: power quality monitoring

●EN50160 compliance reporting ●Analyze/troubleshoot based on IEC 61000-4-30 Class A ●Flicker to IEC 61000-4-15; harmonics/interharmonics to CEI 61000-4-7 ●Digital fault recording at 1024 samples/cycle ●17/20µs (60/50Hz) transient detection and capture Schneider Electric - Division - Name – Date 15

Application: engineering and operations

●The ION8800 integrates with SCADA software and supports substation automation: ● Feeder monitor aggregation and other PLC/RTU features within the substation ● Ethernet, modem, and serial communications ● ION, DNP 3.0, Modbus RTU master/slave, and Modbus TCP master/slave protocols ● WebMeter (onboard web server) and Meterm@il Schneider Electric - Division - Name – Date 16

The PowerLogic family

●Schneider Electric is the world’s largest provider of energy efficiency, power quality and reliability solutions ●PowerLogic offers enhanced, compatible and expanding breadth of capabilities and support ●Customers can leverage existing PowerLogic and ION investments and buy new PowerLogic products with confidence ●Compatible and expanding breadth of capabilities and support Schneider Electric - Division - Name – Date 17

For more information, visit powerlogic.com