Mortar Ancient Masonry History of Mortar Mud parging in Egypt – 4000 B.C. Alabaster with bitumen – 3000 B.C. Sand and gypsum mortar.

Download Report

Transcript Mortar Ancient Masonry History of Mortar Mud parging in Egypt – 4000 B.C. Alabaster with bitumen – 3000 B.C. Sand and gypsum mortar.

Mortar
Ancient Masonry
2
History of Mortar
Mud parging in Egypt – 4000 B.C.
Alabaster with bitumen – 3000 B.C.
Sand and gypsum mortar – 2500 B.C.
Sand lime mortar – 500 B.C.
1:3 lime:sand ratio established – 10 B.C.
3
Early American Masonry
4
History of Mortar
Sand lime mortar used in U.S. – 1700s
Portland cement invented – 1824
5
Modern Masonry
6
History of Mortar
Portland cement lime mortar – Early 1900s
Masonry cement mortar – 1930s
Mortar cement mortar – 1990s
7
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
8
ASTM’s Related to Mortar
Standard Specifications
C91 Standard Specification for Masonry Cement
C144 Standard Specification for Aggregate for Masonry Mortar
C270 Standard Specification for Mortar Unit Masonry
C887 Standard Specification for Packaged, Dry, Combined Materials
for Surface Bonding Mortar
C1142 Standard Specification for Extended Life Mortar for Unit
Masonry
C1329 Standard Specification for Mortar Cement
C1384 Standard Specification for Modifiers for Masonry Mortars
9
not in binder
10
not in binder
11
not in binder
12
not in binder
13
not in binder
14
not in binder
15
not in binder
16
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
17
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
1. Scope
1.1 This specification covers mortars for use
in the construction of non-reinforced and
reinforced unit masonry structures. Four
types of mortar are covered in each of two
alternative specifications: (1) proportion
specifications and (2) property
specifications.
18
Mortar Types
19
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
1.3 When neither proportion or property
specifications are specified, the proportion
specifications shall govern, unless data
are presented to and accepted by the
specifier to show that mortar meets the
requirements of the property
specifications.
20
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
21
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
2. Referenced Documents
2.1
C5
ASTM Standards
Specification for Quicklime for Structural
Purposes
C91
Specification for Masonry Cement
C109
Test Method for Compressive Strength of
Hydraulic Cement Mortars (Using 2-in. or Cube
Specimens)
C110
Test Methods for Physical Testing of Quicklime,
Hydrated Lime, and Limestone
C128
Test Method for Density, Relative Density
(Specific Gravity), and Absorption of Fine
Aggregates
C144
Specification for Aggregate for Masonry Mortar 22
not in binder
C144 – 02
Standard Specification for
Mortar for Unit Masonry1
4.4 When an aggregate fails the gradation
limits specified in 4.1 and 4.2, it may be
used provided the mortar can be prepared
to comply with the aggregate ratio, water
retention, and compressive strength
requirements of the property
specifications of Specification C 270.
23
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
C150
C188
C207
C305
C511
C595
C780
Specification for Portland Cement
Test Method for Density of Hydraulic Cement
Specification for Hydrated Lime for Masonry
Purposes
Practice for Mechanical Mixing of Hydraulic
Cement Pastes and Mortars of Plastic
Consistency
Specification for Moist Cabinets, Moist Rooms,
and Water Storage Tanks Used in the Testing of
Hydraulic Cements and Concretes
Specification for Blended Hydraulic Cements
Test Method for Preconstruction and
Construction Evaluation of Mortars for Plain and
24
Reinforced Unit Masonry
not in binder
C780 – 02
Standard Test Method for
Preconstruction and Construction Evaluation of Mortars
for Plain and Reinforced Unit Masonry1
1.4 The test results obtained under this test
method are not required to meet the
minimum compressive values in
accordance with the property
specifications in Specification C 270.
25
not in binder
C780 – 02
Standard Test Method for
Preconstruction and Construction Evaluation of Mortars
for Plain and Reinforced Unit Masonry1
26
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
C952
C1072
C979
C1157
C1180
C1324
C1329
C1357
Test Method for Bond Strength of Mortar to
Masonry Units
Test Method for Measurement of Masonry
Flexural Bond Strength
Specification for Pigments for Integrally Colored
Concrete
Performance Specification for Hydraulic Cement
Terminology of Mortar and Grout for Unit
Masonry
Test Method for Examination and Analysis of
Hardened Mortar
Specification for Mortar Cement
Test Methods for Evaluating Masonry Bond
27
Strength
not in binder
C1072 – 00a
Standard Test Method for
Measurement of Masonry Flexural Bond Strength1
28
not in binder
C1148 – 92a (Reapproved 2002)
Standard Test Method for
Measuring the Drying Shrinkage of Masonry Mortar1
29
not referenced
not in binder
C1180 – 02
Standard Terminology for
Mortar and Grout for Unit Masonry1
mortar, n—a mixture consisting of
cementitious materials, fine aggregate,
water, and with or without admixtures, that is
used to construct unit masonry assemblies.
30
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
2.2 Masonry Industry Council:
Hot and Cold Weather Masonry Construction Manual,
January 1999
31
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
32
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
3. Specification Limitations
3.1 Specification C 270 is not a specification
to determine mortar strengths through
field testing.
33
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
3.3 The compressive strength values
resulting from field tested mortars do not
represent the compressive strength of
mortar as tested in the laboratory nor that
of the mortar in the wall. Physical
properties of field sampled mortar shall
not be used to determine compliance to
this specification and are not intended as
criteria to determine the acceptance or
rejection of the mortar.
34
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
35
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4. Materials
4.1 Material used as ingredients in the mortar
shall conform to the requirements
specified in 4.1.1 to 4.1.4
36
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4.1.1 Cementitious Materials
37
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4.1.2 Aggregates
38
How sand affects mortar
November
1994
Well-graded sand features a well-distributed mix of
particles of varying sizes, which minimizes voids (see
illustration). Sand that is too fine has more surface area to
coat. Coarser sand particles result in larger voids to fill. As
a result, mortar made with sand that is too fine or too
coarse contains more water per unit volume, which
decreases the mortar’s strength. Excessively coarse or
fine sand also makes mortar less workable.
39
not in binder
C144 – 03
Standard Specification for
Aggregate for Masonry Mortar1
4.4 When an aggregate fails the gradation
limits specified in 4.1 and 4.2, it may be
used provided the mortar can be
prepared to comply with the aggregate
ratio, water retention, and compressive
strength requirements of the property
specifications of Specification C 270.
40
November
1994
How sand affects mortar
Masonry specialist John Melander of the
Portland Cement Association (PCA) says
that in many regions, most sands do not
meet ASTM C144 gradation limits and must
be qualified under this procedure.
41
not in binder
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4.1.3 Water
42
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4.1.4
Admixtures – Admixtures such as coloring
pigments, air-entraining agents, accelerators,
retarders, water-repellent agents, antifreeze
compounds , and other admixtures shall not
be added to mortar unless specified.
Coloring pigments shall conform to
Specification C979. Calcium chloride, when
explicitly provided for in the contract
documents, is permitted to be used as an
accelerator in amounts not exceeding 2% by
weight of the portland cement content or 1%
by weight of the masonry cement content, or
43
both, of the mortar.
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
Note 1 – If calcium chloride is allowed, it
should be used with caution as it may have
a detrimental effect on metals and on some
wall finishes.
44
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
4.1.4 Admixtures
45
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
46
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
5. Requirements
5.1 Unless otherwise stated, a cement/lime
mortar, a mortar cement mortar, or a
masonry cement mortar is permitted.
47
Requirements
48
ASTM C 270
Material Requirements
Measuring and Mixing
Proportion Specification
• Proportion in Accordance
with Table 1
• No Mortar Tests Required
Property Specification
• Laboratory Tests of Mortar
Required to Meet Table 2
• Control Field Proportions to
Laboratory Established Mix
Design
49
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
TABLE 1 Proportion Specification Requirements (default)
Proportions by Volume (Cementitious Materials)
Mortar
CementLime
Mortar
Cement or
Masonry
Cement
Type
Portland
Cement or
Blended
Cement
Mortar Cement
or Masonry
Cement
M
S
N
Hydrated Lime
or Lime Putty
M
1
-
-
-
¼
S
1
-
-
-
over ¼ to ½
N
1
-
-
-
over ½ to 1¼
O
1
-
-
-
over 1¼ to 2½
M
1
-
-
1
-
M
-
1
-
-
-
S
½
-
-
1
-
S
-
-
1
-
-
N
-
-
-
1
-
O
-
-
-
1
-
Aggregate Ratio
(Measured in Damp,
Loose Conditions)
Not less than 2¼ and
not more than 3 times
the sum of the
separate volumes of
cementitious materials
50
Type S Mortar
PCL
PC HL Ratio
Sand
1
¼
3
1 + ¼ = 1¼ x 3 = 3¾
1 : ¼ : 3¾
51
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
TABLE 1 Proportion Specification Requirements (default)
Proportions by Volume (Cementitious Materials)
Mortar
CementLime
Mortar
Cement or
Masonry
Cement
Type
Portland
Cement or
Blended
Cement
Mortar Cement
or Masonry
Cement
M
S
N
Hydrated Lime
or Lime Putty
M
1
-
-
-
¼
S
1
-
-
-
over ¼ to ½
N
1
-
-
-
over ½ to 1¼
O
1
-
-
-
over 1¼ to 2½
M
1
-
-
1
-
M
-
1
-
-
-
S
½
-
-
1
-
S
-
-
1
-
-
N
-
-
-
1
-
O
-
-
-
1
-
Aggregate Ratio
(Measured in Damp,
Loose Conditions)
Not less than 2¼ and
not more than 3 times
the sum of the
separate volumes of
cementitious materials
52
Type S Mortar
MC
MC
1
Ratio
3
1x3=
Sand
3
1:3
53
Type S Mortar
Example – Make 1 cubic yard of mortar
1cy = 27cf
MC Sand
1
3
=
x
27
x = 9cf = 9 sacks of masonry cement
9cf sacks + 27cf sand = 27cf or 36cf ?
54
Masonry Information
Masonry Mortars
55
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
TABLE 2 Property Specification Requirements
Mortar
Cement
Lime
Mortar
Cement
Masonry
Cement
Type
Average
Compressive
Strength at 28
days, min, psi
Water
Retention,
min, %
Air
Content,
max, %
M
2500
75
12
S
1800
75
12
N
750
75
14
O
350
75
14
M
2500
75
12
S
1800
75
12
N
750
75
14
O
350
75
14
M
2500
75
18
S
1800
75
18
N
750
75
20
O
350
75
20
Aggregate Ratio
(Measured in Damp,
Loose Conditions)
Not less than 2¼ and
not more than 3½
times the sum of the
separate volumes of
cementitious
materials
56
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
57
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
6. Test Methods
58
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
6. Test Methods
59
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
Note 4 – Air content of non-air-entrained
portland cement-lime mortar is generally
less than 8%.
60
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
6. Test Methods
61
Air Content
PCL
3 to 5%
Bond Strengths
Similar
Mortar Cement
Masonry Cement
8 to 12%
12 to 18%
Type S PCL
>
Type S Mas Cem
3000psi
2200psi
Less
62
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
63
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
7. Construction Practices
7.1 Storage of Materials – Cementitious
materials and aggregates shall be stored
in such a manner as to prevent
deterioration or intrusion of foreign
material.
64
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
7.2 Measurement of Materials – The method
of measuring materials for the mortar
used in construction shall be such that the
specified proportions of the mortar
materials are controlled and accurately
maintained.
65
Gauging the Amount of Sand
1 cu ft = 7 to 8 shovels
1 : 3 (21 to 24 shovels)
66
Gauging the Amount of Sand
Gauging
Uses: 20 shovels/batch mixer
Gage: 5 shovels/bucket
0.67 ft3
5 gallon
bucket
20/5 = 4 buckets/mixer
0.67ft3 x 4 = 2.68ft3
2¼ ft3 < 2.68 ft3 < 3 ft3
yes
67
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
7.3 Mixing Mortars – All cementitious
materials and aggregate shall be mixed
between 3 and 5 min in a mechanical
batch mixer with the maximum amount of
water to produce a workable consistency.
68
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
7.4 Tempering Mortars – Mortars that have
stiffened shall be retempered by adding
water as frequently as needed to restore
the required consistency. No mortars
shall be used beyond 2 ½ h after mixing.
69
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
7.5 Climatic Conditions – Unless superseded
by other contractual relationships or the
requirements of local building codes, hot
and cold weather masonry construction
relating to mortar shall comply with the
Masonry Industry Council’s “Hot and Cold
Weather Masonry Construction Manual.”
70
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
71
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
8. Quality Assurance
8.1 Compliance to this specification is verified
by confirming that the materials used are
as specified, meet the requirements as
given in Section 2.1, and added to the
mixer in the proper proportions.
72
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
8.2 Test Method C780 is suitable for the
evaluation of masonry mortars in the field.
However, due to the procedural differences
between Specification C270 and C780, the
compressive strength values resulting from
field sampled mortars are not required nor
expected to meet the compressive strength
requirements of the property specification of
Specification C270, nor do they represent the
compressive strength of the mortar in the
wall.
73
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
While visual observation of the batching process is
important, it is not practical or necessary for an
inspector to watch the proportioning of every batch.
One thing that can be done – with quick results – is
sample the fresh mortar as mixed and calculate how
much sand it contains relative to cement. As long as
the individual ingredients all meet their own standards,
the only thing to check to assure mortar quality is its
proportions. This is exactly what the mortar aggregate
ratio does and the process is described in ASTM
C780.
74
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
ASTM C780 … contains guidance for testing masonry
mortars. The mortar aggregate ratio, Annex 4, entails
sampling the fresh mortar as mixed, then separating
the materials and calculating how much sand it
contains relative to cement.
75
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
The Basic Test
1. Take a sample of wet mortar and one of sand.
2. Place sample of mortar into two jars of alcohol.
(Alcohol stops cement hydration.) Place sand into
a different jar or a plastic bag.
76
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
3.
4.
Agitate the mortar jars to mix the alcohol
throughout the sample, breaking up the cement
and sand.
For mortar jar #1, the alcohol is burned off in the
lab, and the remaining material is oven dried to
determine the water content.
77
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
5.
For mortar jar #2 and jar #3 with sand, wet sieve
each sample. For the mortar sample, the finer
materials are assumed to represent the
cementitious materials and are washed through a
sieve to leave the sand particles behind. The
sand sample allows for a correction of fine
particles.
78
not in binder
Masonry Today
Mortar Testing for Quality Assurance: Best
Practices
6.
7.
Weigh the sample in various conditions: wet, oven
dried, after removal of alcohol. This allows the
determination of weight of the dry mortar and dry
aggregates.
Calculate the mortar aggregate ratio. A simple
ratio of sand ratio of sand to cement should give
something very close to the mortar proportions
originally chosen, such as 3:1.
79
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
8.3 Test Method C1324 is available to
determine the proportions of materials in
hardened masonry mortars. There is no
ASTM method for determining the
conformance of a mortar to the property
specifications of Specification C270 by
testing hardened mortar samples taken
from a structure.
80
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
Note 12 – Where necessary, testing of a wall
or a masonry prism from the wall is
generally more desirable than attempting to
test individual components.
81
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
82
Function
Hold units together
Accommodate unit
tolerances
83
Function
Provide water
penetration resistance
Hold units apart
84
Function
Variety of colors and textures
85
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
86
Properties
Plastic (Mason)
Hardened (Designer)
Workability
Flow
Water Retentivity
Stiffening Characteristics
Board Life
Bond
Extensibility/Plastic Flow
Compressive Strength
Durability
87
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.4
Masonry mortars have two distinct, important
sets of properties, those of plastic mortars and
those of hardened mortars. Plastic properties
determine a mortar’s construction suitability,
which in turn relate to the properties of the
hardened mortar and, hence, of finished
structural elements. Properties of plastic
mortars that help determine their construction
suitability include workability and water
retentivity. Properties of hardened mortars that
help determine the performance of the finished
masonry include bond, durability, elasticity, and
88
compressive strength.
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.5.1 Workability – Workability is the most
important property of plastic
mortar…Workability is a combination of
several properties, including plasticity,
consistency, cohesion, and adhesion,
which have defied exact laboratory
measurement. The mason can best
assess workability by observing the
response of th mortar to the trowel.
89
Workability
Most important
plastic property
Supports weight
of units
Adheres to vertical
surfaces
Spreads easily
90
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.5.3 Flow – Initial flow is a laboratory measured
property of mortar that indicates the
percent increase in diameter of the base of
a truncated cone of mortar when it is
placed on a flow table and mechanically
raised ½ in. and dropped 25 times in 15 s.
91
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.5.4 Water Retentivity – Water retentivity is a
measure of the ability of mortar under suction to
retain its mixing water. This mortar property
gives the mason time to place and adjust a
masonry unit without the mortar stiffening.
Water retentivity is increased through higher lime
or air content, addition of sand fines within
allowable gradation limits, or use of water
retaining materials.
92
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.5.5 Stiffening Characteristics – Hardening of
plastic mortar relates to the setting
characteristics of the mortar, as indicated
by resistance to deformation.
93
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.1 Bond – Bond is probably the most important single
physical property of hardened mortar. It is also the
most inconstant and unpredictable. Bond actually
has three facets; strength, extent and durability.
Because many variables affect bond, it is difficult
to devise a single laboratory test for each of these
categories that will consistently yield reproducible
results and which will approximate construction
results. These variables include air content and
cohesiveness of mortar, elapsed time between
spreading mortar and laying masonry unit, suction
of masonry unit, water retentivity of mortar,
pressure applied to masonry joint during
placement and tooling, texture of masonry unit’s
94
bedded surfaces, and curing conditions.
Bond
Complete and intimate contact between mortar and
unit is essential for good bond
95
Masonry Information
Mortar Cement: Product Data Sheet
Bond Strength: The mortar cement
specification is the only ASTM masonry
material specification that includes bond
strength performance criteria.
96
Board Life
Retempering
97
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.3.1 The compressive strength of mortar
depends largely upon the cement content
and the water-cement ratio. The
accepted laboratory means for
measuring compressive strength is to
test 2 in. cubes of mortar.
98
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.3.2 …Often overlooked is the size/shape of
mortar joints in that the ultimate
compressive load carrying capacity of a
typical 3/8 in. bed joint will probably be
well over twice the value obtained when
the mortar is tested as a 2 in. cube…
2x
2 in. cube
=
3/8 in. jt.
99
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.3.2 …Mortars should typically be weaker
than the masonry units, so that any
cracks will occur in the mortar joints
where they can more easily be repaired.
100
Durability
Barracks at Fort Wayne in Detroit
101
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.4
Durability – The durability of relatively dry
masonry which resists water penetration is not a
serious problem. The coupling of mortars with
certain masonry units, and design without
exposure considerations, can lead to unit or
mortar durability problems. It is generally
conceded that masonry walls, heated on one side,
will stand many years before requiring
maintenance, an indication of mortar’s potential
longevity. Parapets, masonry paving, retaining
walls, and other masonry exposed to freezing
while saturated represent extreme exposures and
102
thus require a more durable mortar.
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.6.4.1 …Properly entrained air in masonry mortar
generally increases its resistance to freeze-thaw
damage where extreme exposure (such as
repeated cycles of freezing and thawing while
saturated with water) exists.
103
Masonry Information
Masonry Cement: Product Data Sheet
The ability to endure the extremes of repeated
freeze-thaw cycles without deterioration is critical
to the long-term performance of mortar. Research
shows that air entrainment levels of at least 10 to
12 percent are needed to provide effective
resistance to freeze-thaw deterioration in masonry
mortars. Masonry cement mortars have greater
resistance to freeze-thaw deterioration than nonair-entrained-portland cement-lime mortars. This
superior performance can be attributed to the
controlled air content of masonry cement mortars.
104
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.9.3.2 Mortar generally bonds best to masonry units
having moderate initial rates of absorption (IRA),
from 5 to 25g/min-30 in.2, at the time of laying.
More than adequate bond can be obtained,
however, with many units having IRA’s less than
or greater than these values.
A measure of the suction of
water upward into a dry
brick from a bed face during
one minute of exposure.
105
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.9.3.3 The extraction of too much or too little of the
available water in the mortar tends to reduce the
bond between the masonry unit and the mortar. A
loss of too much water from the mortar can be
caused by low water retentivity mortar, high
suction masonry units, or dry, windy conditions.
When this occurs, the mortar is incapable of
forming a complete bond when the next unit is
placed. Where lowering the suction by prewetting
the units is not proper or possible, the time lapse
between spreading the mortar an laying of a
masonry unit should be kept to a minimum. When
a very low suction masonry unit is used, the unit
tends to float and bond is difficult to accomplish. 106
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
There is no available means of increasing the
suction of a low suction masonry unit, and
thus the time lapse between spreading the
mortar and placing the unit may have to be
increased.
X1.9.3.4 Mortars having higher water retentivity are
desirable for use in summer or with masonry
units having high suction. Mortars having
lower water retentivity are desirable for use in
winter or with masonry units having low
suction.
107
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X1.9.5.2 Tooling of the mortar joint should be done
when its surface is thumb-print hard utilizing
a jointer having a diameter slightly larger
than the mortar joint width. Joint
configurations other than concave can result
in increased water permeance of the
masonry assemblage. Striking joints with the
same degree of hardness produces uniform
joint appearance. Finishing is not only for
appearance, but to seal the interface
between mortar and masonry unit, while
densifying the surface of the mortar joint. 108
Mortar Joints
Exterior/Interior
Concave
109
Mortar Joints
Exterior/Interior
Concave
Vee
110
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
111
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
112
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
Beaded
113
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
Beaded
Struck
114
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
Beaded
Struck
Flush
115
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
Beaded
Struck
Flush
Raked
116
Mortar Joints
Exterior/Interior
Concave
Vee
Grapevine
Interior
Weathered
Beaded
Struck
Flush
Raked
Extruded
117
not in binder
TABLE 2. MORTAR PROPERTIES
Cementitious Materials
Portland Cement:Lime
Type
Mortar Cement
Masonry Cement
S
N
O
S
N
S
N
Initial
110
110
108
114
115
113
115
Final
90.0
100
99.0
92.0
87.0
89.0
100
Water Retention, %
81.8
90.9
91.7
80.7
75.6
78.8
87.0
Cone Penetration, mm
56
57
58
53
51
53
64
7 day, psi
3718
1745
674
2722
2471
2635
1069
28 day, psi
4248
2132
882
3220
3285
3157
1472
Air Content, %
1.5
1.1
1.4
8.7
9.3
13.8
15.8
Flow
Compressive Strength2
1Average
of three measurements
on 2” cubes
2Measured
118
not in binder
TABLE 3. FLEXURAL BOND STRENGTHS
Cementitious Material and Mortar Type
Brick IRA
gm/30
in2/min
1.00
4.30
15.1
Flexural Bond Strength
Data
Portland Cement:Lime Mortar Cement
Masonry
Cement
S
N
O
S
N
S
N
Average of 30, psi
92.40
80.96
65.03
94.18
82.17
77.42
61.94
Standard Deviation, psi
19.22
15.98
9.65
19.61
11.87
11.85
7.28
Coefficient of Variation
19.62
18.05
13.76
18.93
14.31
14.77
11.52
Average of 30, psi
109.0
105.4
80.47
120.7
127.2
122.0
104.6
Standard Deviation, psi
16.96
11.72
10.38
17.03
22.97
19.59
21.10
Coefficient of Variation
14.68
10.75
12.72
13.22
17.85
15.37
20.11
Average of 30, psi
101.4
115.1
94.00
Standard Deviation, psi
24.00
20.65
9.21
Coefficient of Variation
22.92
16.94
9.58
119
Masonry Information
Masonry Cement: Product Data Sheet
Several factors influence drying shrinkage of
masonry mortars, including water content, rate of
drying, sand properties, moisture content and
absorption of the masonry units, and cementitious
material properties. Results of laboratory tests
shown in Fig. 1 indicate that the drying shrinkage
of masonry cement mortars is about half that of
portland cement-lime mortars.
120
Masonry Information
Masonry Cement: Product Data Sheet
121
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
122
Selection
MIM suggests the mortar type selected be
the weakest that will satisfy structural
requirements.
123
Compatibility
Mortar type should be correlated with the
particular masonry unit to be used because
certain mortars are more compatible with
certain masonry units.
124
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
TABLE X1.1 Guide for the Selection of Masonry Mortars
Mortar Type
Location
Building Segment
Recommended
Alternative
Exterior, above
grade
Load-bearing wall
Non-load bearing wall
Parapet wall
N
O
N
S or M
N or S
S
Exterior, at or
below grade
Foundation wall,
retaining wall,
manholes, sewers,
pavements, walks, and
patios
S
M or N
Interior
Load-bearing wall
Non-bearing partitions
N
O
S or M
N
Interior or
Exterior
Tuckpointing
See Appendix
X3
See Appendix
125
X3
Recommendations
Above Grade
Wall System
Veneer
Reinforced
Unreinforced
Mortar Type
N
N or S
S
Below Grade
S or M
126
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
TABLE X1.1 Guide for the Selection of Masonry Mortars
Mortar Type
Location
Building Segment
Recommended
Alternative
Exterior, above
grade
Load-bearing wall
Non-load bearing wall
Parapet wall
N
O
N
S or M
N or S
S
Exterior, at or
below grade
Foundation wall,
retaining wall,
manholes, sewers,
pavements, walks, and
patios
S
M or N
Interior
Load-bearing wall
Non-bearing partitions
N
O
S or M
N
Interior or
Exterior
Tuckpointing
See Appendix
X3
See Appendix
127
X3
Recommendations
Above Grade
Wall System
Veneer
Reinforced
Unreinforced
Mortar Type
N
N or S
S
128
Recommendations
Above Grade
Wall System
Veneer
Reinforced
Unreinforced
Mortar Type
N
N or S
S
129
1999
Spec
Unit Strength Method
Table 2 – Compressive strength of masonry based on the compressed
strength of concrete masonry units and type of mortar used in construction
Net area compressive strength of
concrete masonry units, psi
Type M or S
mortar
Type N mortar
Net area
compressive
strength of
masonry, psi
1250
1300
1000
1900
2150
2800
3050
2000
3750
4050
2500
4800
5250
3000
1900
1500
1350
130
Recommendations
Above Grade
Wall System
Veneer
Reinforced
Unreinforced
Mortar Type
N
N or S
S
131
1999
Code
Table 2.2.3.2 – Allowable flexural tension for clay and concrete masonry, psi
Mortar types
Masonry type
Normal to bed joints
Solid units
Hollow units
Ungrouted
Fully grouted
Parallel to bed joints in
running bond
Solid units
Hollow units
Ungrouted and partially
grouted
Fully grouted
Portland cement/lime
or mortar cement
Masonry cement or air
entrained portland
cement/lime
M or S
N
M or S
N
40
30
24
15
25
68
19
58
15
41
9
29
80
60
48
30
50
38
30
19
80
60
48
30 132
Mortar
Products
ASTM C 270
Scope
Referenced Documents
Specification Limitations
Materials
Requirements
Test Methods
Construction Practices
Quality Assurance
Function
Properties
Selection
Tuckpointing
Application
133
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X3.3 Selection Guide – Use tuck pointing
mortar of the same or weaker
composition as the original mortar.
See Table X3.1.
134
C270 – 03b
Standard Specification for
Mortar for Unit Masonry1
X3.5 Mixing:
X3.5.1 Dry mix all solid materials.
X3.5.2 Add sufficient water to produce a damp
mix that will retain its shape when pressed
into a ball by hand. Mix from 3 to 7 min,
preferable with a mechanical mixer.
X3.5.3 Let mortar stand for not less than 1hr nor
more than 1 ½ h for prehydration.
X3.5.4 Add sufficient water to bring the mortar to
the proper consistency for tuck pointing,
somewhat drier than mortar used for
laying the units.
X3.5.5 Use the mortar within 2 ½ h of its initial
mixing. Permit tempering of the mortar
135
within this time interval.
Moisture Resistance of Brick Masonry
Maintenance
Tuck-pointing Mortar Joints
136
137