W650 Wind Protection System

Download Report

Transcript W650 Wind Protection System

G650
Generator Protection & Control System
Protection, Control and Monitoring
for Generator Interconnection
g
Multilin
Copyright © 2006 GE Multilin
1
GE Consumer & Industrial
Multilin
G650 Generator Protection & Control System
Agenda
•
•
•
•
•
•
•
•
•
•
•
G650 Protection Applications
Features and Benefits
Protection Functions
Control Functions
User Programmable Control
Logic
HMI Monitoring and Control
Metering and Monitoring
Communications
EnerVista Software
Ordering Information
Summary
Copyright © 2006 GE Multilin
2
GE Consumer & Industrial
Multilin
G650 Generator Protection & Control System
Cost Effective Integrated Solution
for:
• Protection and Control of Small to Medium
sized Generators
• Distributed Generator Management
• Generator Interconnect Protection
• Generator Sets Mains Failure Detection
Copyright © 2006 GE Multilin
3
GE Consumer & Industrial
Multilin
G650 Generator Protection & Control Solution
Best Value for Price Solution Available
• Basic and Enhanced Protection Options available to
suit your Generation Protection Requirements
• Ready for basic breaker Trip and Close Control with
no programming required
• Provides IEC61131-3 Programmable Logic for
customizing
interaction with the Prime Mover
Control System
• High End Fault, Disturbance and Sequence of Events
recording capability
• Supports open communications protocols such as
Modbus and DNP for system integration
• Large graphical built-in interface providing local control
Copyright © 2006 GE Multilin
4
GE Consumer & Industrial
Multilin
G650 . . . Protection features
Basic Protection Option
• Timed & Instantaneous Overcurrent
• Directional Overcurrent
• Voltage Restraint Overcurrent
• Under and Overvoltage
• Directional Power
• Under and Overfrequency
• Frequency rate of change
• Generator Thermal Model
• Generator Current unbalance
• Loss of Excitation
• Accidental Generator Energization
Copyright © 2006 GE Multilin
5
GE Consumer & Industrial
Multilin
G650 . . . Protection features
Enhanced Protection Option
All Basic Protection Elements Plus:
• Sensitive Ground Overcurrent
• Volts/Hz
• Power Factor limiting
• Loss of Mains detection
• Breaker Failure
• VT Fuse failure
• Restricted Ground Fault
Copyright © 2006 GE Multilin
6
GE Consumer & Industrial
Multilin
G650 . . . Control functions
Built-In Control Functions
• Synchrocheck Element for ensuring synchronism
before closing the Breaker onto the system
• Control of switching between the 3 available Setting
Groups
• Analog Comparators allowing users to create
their
own customized control elements
• Trip Circuit Supervision ensuring integrity
of the
Tripping Circuit
• Contact Seal-In preventing damage to the trip
contact due to opening when the Trip Circuit is active
Trip Circuit Supervision ensures the circuit is available
for Tripping when required
Copyright © 2006 GE Multilin
7
GE Consumer & Industrial
Multilin
G650 . . . Control logic
Pre-Configured Control Logic
The G650 comes preconfigured with Control Logic for standard Tripping and Closing
operation. Users are only required to configure the protection or control element they wish
to use.
User Programmable Control Logic
The IEC 61131-3 programmable Logic Editor allows users to develop their own Logic
equations and create their own customized Distributed Generation Control Applications
Copyright © 2006 GE Multilin
8
GE Consumer & Industrial
Multilin
G650 . . . Front panel HMI
User Friendly and Intuitive HMI
Copyright © 2006 GE Multilin
9
GE Consumer & Industrial
Multilin
G650 . . . Front panel HMI
Customizable single line diagrams
• ANSI Symbols library
• Editable using PC program
• Available only in 16 x 40 character display
Customizable Single Line Diagram
Copyright © 2006 GE Multilin
10
GE Consumer & Industrial
Multilin
G650 . . . Metering & status values
Accurate Metering of Power System
Values
•
•
•
•
•
•
•
Current (+/- 0.5%)
Voltage (+/- 1%)
Power - Real, Reactive, Apparent(+/-1%)
Energy (+/-1%)
Demand (+/-1%)
Power Factor (+/- .02)
Frequency (+/-30mHz 50Hz, 36mHz
Real 60Hz)
Time Status of I/O Data
View Real-Time Metering Data using the
650 Setup Program
•Contact Inputs
•Contact Outputs
•Virtual Inputs
•Virtual Outputs
•Trip Circuit Supervision Status
Analyze Input and Output states using
the Viewpoint Monitoring software HMI
Copyright © 2006 GE Multilin
11
GE Consumer & Industrial
Multilin
G650 . . . Fault recording
The High Sampling Rates and Large amount of storage capacity
make the G650 ideal for all your Fault and Disturbance Recording
needs
Sequence of Event Records
•
•
Stores the last 479 events
Time stamped to 1mSec accuracy
Oscillography Waveform capture
•
•
•
•
•
Stores up to 20 fault records
Sampling rate of 64 samples/cycle
Records 9 Analog channels
Records 16 Digital Channels
Programmable Oscillography Trigger
Timestamping of Events with 1ms accuracy
Data Logger
•
•
•
Long term trending of measure data
1 second to 60 minute sample resolution
16 recordable analog channels
High-Sample recording of Generator Faults
Copyright © 2006 GE Multilin
12
GE Consumer & Industrial
Multilin
G650 . . . Communications
Multiple Communication Mediums and Protocols Simplifying
Configuration & Integration
RS232 Serial Front Port
•
•
300 to 115,200 Baud Rates
Modbus RTU, DNP3.0 Protocols
RS485 Serial Ports
•
•
•
300 to 115,200 Baud Rates
Copper, Glass Fiber, Plastic Fiber mediums
Modbus RTU, DNP3.0 Protocols
CANbus I/O Ports
•
•
Asynchronous I/O data sharing
Copper, Glass Fiber mediums
Ethernet Ports
•
•
•
10/100Mbit TX Copper
Redundant 100Mbit FX Fiber
Modbus TCP/IP, DNP3.0, HTTP, TFTP
Protocols
Copyright © 2006 GE Multilin
13
GE Consumer & Industrial
Multilin
G650 . . . EnerVista Software
Device Setup & Document Management Toolset




Easily configure GE Multilin devices from a single Application
Create and Edit setting files Offline, or in Real Time
Manage your Support Documents & Software Tools
Receive Automatic Notification of new updates
Easy to Use Monitoring and Data Recording for
Small Systems





Pre-configured screens for Instant Monitoring
Single-Line monitoring
Annunciator Alarms
Trending Reports
Automatic Fault Data Collection
Communications Server




OPC/DDE Server
Send device data to HMI, DCS, and SCADA systems
Contains memory maps for GE Devices and firmware
Automatic Fault Data Collection
Copyright © 2006 GE Multilin
14
GE Consumer & Industrial
Multilin
G650 . . . Viewpoint Monitoring
Software
PLUG-AND-PLAY MONITORING
Pre-configured screens
for instant monitoring
SINGLE-LINE MONITORING AND CONTROL
Create and View SingleLine monitoring screens
in minutes
AUTOMATIC EVENT AND WAVEFORM RETRIEVAL
Effortless Data Archiving
Global COMTRADE VIEWER
View Waveforms
Recorded From your
Devices
TRENDING REPORTS
Historical Record of
Monitored Data
AUTOMATIC EVENT AND WAVEFORM RETRIEVAL
Instant Alarm Notification
Copyright © 2006 GE Multilin
15
GE Consumer & Industrial
Multilin
G650 . . . Ordering options
Copyright © 2006 GE Multilin
16
GE Consumer & Industrial
Multilin
G650 . . . Summary
• Ideal for Distributed Generator Applications
•
•
Contains all required protection features for small to medium sized generators
Provides configurable logic for creating customized generator system control
schemes
• Cost Effective and Scalable Solution where a low price of protective relaying is key
driver
•
•
Basic and Enhanced Protection Options to suit individual application
Graphical User Interface and Communication options to suite integration
requirements
• Industry Leading Fault Recording Capability
•
•
•
Large capacity and highly accurate Sequence of Event Recording
Waveform Fault recoding with High Sampling rates (64 samples/cycle) and multiple
record storage
Long term Data Logger recording of system disturbance events (up to 1
sample/second)
• Most features available in the Distributed Generation Protection market segment
•
•
•
Programmable Control Logic
Ethernet Communications
High End Fault Recording
Copyright © 2006 GE Multilin
17
GE Consumer & Industrial
Multilin