No Slide Title

Download Report

Transcript No Slide Title

COMPACT Variable
Frequency Drives
 Honeywell.com
Buildings Consume Massive Amounts of Energy
• Commercial Buildings consume
massive amounts of Energy
– Electricity = 74% of the energy
consumed by commercial buildings
•
(source: US DOE, 2008 Building Energy Data Book)
• Half of electricity consumed by
buildings is used to move air
– More than half of the worlds energy is
consumed by pumps and fans
An electric motor is a fixed-speed machine
Honeywell Proprietary
 Honeywell.com
VFDs Greatly Reduce Electricity Use
• (VFDs) significantly reduce
electrical consumption
– Most pump and fan systems are
oversized to account for maximum loads
– Capacity usually exceeds demand
– Application of VFDs converts systems to
variable flow
• Green House Gas Reduction
– 80% of commercial building CO2
emission due to electricity consumption
VFDs provide the ability to vary the speed of a motor
Honeywell Proprietary
 Honeywell.com
What Does a VFD do?
Power
Supply
Variable Frequency
Drive
(VFD)
+
3~
Motor
V1
V3
V5
V2
V4
V6
C
-
Rectifier DC- circuit
Inverter unit
Honeywell Proprietary
 Honeywell.com
Why Do It? Less Energy = Greater Savings
Affinity laws Express relationship between rotational speed and flow, pressure and power
Flow is directly proportional to speed
Pressure is proportional to the square of speed
Power is proportional to the cube of speed
% Power Savings = (%Speed Reduction)3
Honeywell Proprietary
 Honeywell.com
Why Do It? Less Energy = Greater Savings
% Power Savings = (%Speed Reduction)3
Honeywell Proprietary
 Honeywell.com
Opportunities are Everywhere
•
•
•
•
•
•
•
•
Supply and return fans
Cooling Towers
Compressors
Stairway and parking ventilation
Boiler pumps and fans
Kitchen Hoods
Conveyors
Elevators
Honeywell Proprietary
 Honeywell.com
Optimize Capability, Minimize Waste
• Many Micro VFDs come loaded with features that do not fit the application
• Many Micro VFDs do not have the right combination of capabilities
• SmartDrive COMPACT - chose the options to meet the application:
–
–
–
–
Interface
Filter
Enclosure
Inputs and Outputs
• 3 Year Warranty
– Longer than all competitors
Honeywell Proprietary
 Honeywell.com
Optimize Capability, Minimize Waste
•
•
•
•
•
•
Chose only the options you need
Small installed size
Fast installation
Intuitive commissioning
Easy communication
3-Year Warranty
Honeywell Proprietary
 Honeywell.com
Available Sizes and Options
• Power Range
–
–
–
–
208/240VAC, 1~in/3~out, .25HP to 3HP
460VAC, 3~in/3~out, .5 to 7.5HP
NX series available for other sizes
Other niche markets we are examining
• 208/240 VAC 3~in/3~out
• 575VAC
• 110 VAC
• Application Interface (API)
– Limited API (Standard)
• Most Applications
• 1 Analog In, 1 Analog Out, 3 Digital In, 1 Relay Out
– Full API
• Advanced Applications
• 2 Analog In, 1 Analog Out, 6 Digital In, 2 Relay Out
• Enclosure - Open Chassis or NEMA 1
• Optional EMC Filter
Honeywell Proprietary
 Honeywell.com
Small Installed Size
FRAME
H
W
D
MI1
6.2”
2.6”
3.9”
MI2
7.7”
3.5”
4.0”
MI3
10.2”
3.9”
4.3”
Honeywell Proprietary
 Honeywell.com
COMPACT Naming Matrix
Honeywell Proprietary
 Honeywell.com
Inputs/Outputs and Communications
• Two Application Interfaces (API) available
– Full API
• LCD, 2 Analog In, 1 Analog Out, 6 Digital In, 1 Digital Out, 2 Relay Outputs
– Limited API
• LCD, 1 Analog In, 1 Analog Out, 3 Digital In, 1 Relay Output
• Modbus connection standard in both API
• Additional custom API configurations are available
Honeywell Proprietary
 Honeywell.com
Standard and Expanded Inputs/Outputs
STANDARD
EXPANDED
Honeywell Proprietary
 Honeywell.com
Control Wiring
Honeywell Proprietary
 Honeywell.com
Fast Installation
• Din Rail and Screw Mountable
• Book shelf, Side-by-side installation
Din Rail Clip
– No side clearance required
Screw Holes
Screw Holes
Book Shelf Mounting
Screw Holes
Screw Holes
Honeywell Proprietary
 Honeywell.com
Intuitive Commissioning
• Click-Wheel Interface
• Intelligent menu navigation
• Status Indicators
– Ready, Run, Stop, Alarm, Fault
• Control Indicators
– Forward, Reverse, I/O, Keypad, Fieldbus
• Menu Indicators
– Reference, Monitor, Parameter, Fault
•
Honeywell Proprietary
 Honeywell.com
Startup Wizard
Honeywell Proprietary
 Honeywell.com
Startup Wizard
Honeywell Proprietary
 Honeywell.com
MCA – Micro Communications Adapter
• Upload and Download parameters without powering the drive
• PC Connection to the drive for
– Commissioning
– Control
– Monitoring
Honeywell Proprietary
 Honeywell.com
PC Programming Tool
•
•
•
•
•
•
Commission
Control
Upload/Download
Monitor/Trend
Faults
Print/Save
Honeywell Proprietary