Transcript Document
IFSA Conference 2008 Warehouse Protection Options Joachim Böke Viking s.a. K19 Sprinkler Concept Effective fire sprinkler protection - price - performance Approved by a recognized authority Flexibility in terms of installation and logistics Goals of logistics No limitation for goods like exposed expanded plastics / candles – HHS4 up to 8.5 m Flexible concerning transverse flue space, different types of pallets No in-rack sprinklers! • Less Space between sprinkler and stored material (10 cm – 15 cm) • No fixed horizontal beam levels • No water damage from damaged in-rack sprinklers K19 Sprinkler Concept New control mode ceiling sprinkler K19 (K275) “Enhanced control mode” Vertical barrier at every second rack upright Limitation of damage and fire spread! Storage of exposed expanded plastic and candles up to 8,5 m (and lower classes) No defined transverse flues needed between rack uprights Front view of the test rack vertical Barriers C C C M M M C M M C M C C C C M C M C C C C M M C M M C M C C M C C M M M M C C M C M M M C C M C Ignition 12,0 m M M M M M C M 6.5 m C M C M 2,3 m 3,7 m 5,1 m M M Back view of the test rack Pass / Fail criteria Horizontal fire spread limited to max 7 pallets in width or 6 meters (19.7’) No fire spread to the target rack Temperature at the ceiling can never exceed 300°C (572 °F) for more than one minute Rapid fire spread Test no. 3 - example 11 seconds: Fire surpasses the top of the 2nd storage level 31 seconds: Fire reaches the ceiling 34 seconds: Simultaneous opening of four first sprinklers Sprinkler and Temperature measurement Temperature measurement Sprinkler temperatures_Test 3 Sprinkler temperatures_Test 3 T1 T2 T3 T4 T5 T5b 200 150 100 50 250 Temperature (°C) Temperature (°C) 250 T6 T7 T8 T9 T10 T10b 200 150 100 50 0 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Time (min) 0 2 4 6 150 100 250 Temperature (°C) Temperature (°C) T11 T12 T13 T14 T15 T15b 200 150 100 50 0 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Time (min) T16 T17 T18 T19 T20 T20b 200 50 0 10 12 14 16 18 20 22 24 26 28 30 Time (min) Sprinkler temperatures_Test 3 Sprinkler temperatures_Test 3 250 8 0 2 4 6 8 10 12 14 16 18 20 22 24 26 28 30 Time (min) Results Conclusion Successful fire test Effective protection concept Design Concept and K19 Sprinkler have VdS approval Design Concept predominantly follows “spray sprinkler” installation rules Rack design (4,6 m: multiple row rack?!) max. 12 m max.8,5 m max. 8,5 m max 4,6 m!!!!! 0,2 m Vertical Barriers: non-combustible material or combustible material with special coating (2cm thick coated plywood). Automatic Enclosed Rack Protection Vertical carousels Vertical Lift Main Target • • Water based effective and adequate fire protection - Price - Lower installation cost - Lower maintenance cost - Performance - Connection to existing sprinkler system To be approved by (No approved water based system available) Fire tests • • • Fire test carried out in Sweden at SP Low pressure deluge system (connection to the sprinkler also possible) Tested material: HHS 3 and HHS 4 plastic boxes and mattresses Fire tests set up Fire tests • • • Three tests carried out Two tests with opening on the front (1 m high and the complete width of the rack) One additional test with 0,33 m² additional opening in the ceiling to test the limits of the system All tests are acceptable, damage and temperatures are higher at test 3 Test results Test no. 1 2 3 Smoke alarm 01:18 01:16 01:06 System activation time 02:55 02:19 02:21 Full system pressure 03:15 02:38 02:48 Elapsed time to full system pressure 00:20 00:19 00:27 Activation times [min:s] Average peak surface temperatures Back wall: 68°C 67°C 97°C Front wall: 38°C 35°C 62°C Left hand side short wall 34°C 34°C 37°C 100°C 40°C 47°C Right hand side short wall Inside temperatures test 1 and 2 Test 1 Test 2 1000 1000 C1 C2 C3 C4 C5 600 800 Temperature [°C] Temperature [°C] 800 C1 C2 C3 C4 C5 Pump failure 400 200 600 400 200 0 0 1 2 3 4 5 6 Time [min] 7 8 9 10 0 0 1 2 3 4 5 6 Time [min] 7 8 9 10 Fire at test 1 Damage after the tests (test 2) Protection concept • Suppress / control the fire inside the rack • Design: • At the sides - Open water spray nozzles with vertical spacing of about 2 m - Spray angle 90° vs. spray angle 120° • At the ceiling - Open K=21 window sprinklers, for cooling • Minimum operating pressure: 4 bar Nozzle arrangement Spray angel 90° 120° 90° 120° 90° 120° Thank you