S8910UNIVERSALIGNITIONMODULETrainingModule

Download Report

Transcript S8910UNIVERSALIGNITIONMODULETrainingModule

S8910U1000
Universal Electronic Ignition
Modules
Training Module
What you will learn
• Ignition Types
• S8910U1000
- Features and Benefits
- Installation and Set Up
- Troubleshooting
- S8910U Advantage
• Product Cross Reference Information
2
Ignition Sources
• There are 3 different ways a burner can be ignited:
- 1) Standing Pilot Ignition
- 2) Intermittent Pilot Ignition
 Intermittent Pilot - S8610U
- 3) Direct Burner Ignition
 Hot Surface Ignition – S8910U
 Direct Spark Ignition – S87
3
S8910U1000
Universal Hot Surface Ignition Module
• What is the S8910U1000?
- Electronic control of direct hot
surface Ignition systems used on
gas fired furnaces, boilers, and
other heating appliances
- Operating control of a direct
ignition system using a 120 Vac hot
surface igniter
- No spark generator
- Simple relay to power igniter
- Two wires to gas valve
One Part Number:
S8910U1000
5
S8910U Features – The Universal Choice
• Features
- Universal Compatibility
 Replaces over 100 Honeywell and competitor models.
 “Personality” Plug-Ins- match the ignition sequence of the model being
replaced using the plug in selector tabs and cross reference chart for an
instant equivalent of the old control.
- Application Flexibility
 Use with Single Rod or Dual Rod Systems
 Works with both Natural or LP gas
- Easy Installation
 Easy-to-use instructions plus the adaptation accessories required to adapt the
existing hot surface ignition module
• Accessory kit includes: White-Rodgers adapter, Robertshaw ground lead, four ¼”
female .032 quick-connects, one 3/16” female .032 quick connects, four selection tabs
and seven wire labels.
6
The Universal Choice continued…..
- LED diagnostics
 Quickly troubleshoot and diagnose any problems with the system
- Ignition Trials
 Provides one or three ignition trials (4-second or 7-second trials) per
call for heat
 Prepurge of 32-seconds or less
 Up to 90-seconds between purge cycle times
- Excellent industry acceptance
 The Honeywell brand is recognized as a top performer in the industry
7
S8910U Features
BRN/GND
24 GND
MV
24 V
8
LED
SENSE
MV
IGNITION
TRIAL
SELECTOR
TAB
HOT
SURFACE
IGNITER
SENSE JUMPER WIRE
Installation and Set Up
Installation of the S8910U
•
Mount the module
-
•
Do not mount with terminals facing up
protect the module from exposure to water, moisture, corrosive
chemicals and excessive dust and grease.
Install selection tab (“personality plug-ins”)
-
The number of trials for ignition and trial time is determined by the
selection tabs.
 Four selection tabs are included with the S8910U. (A,B,C,D)
 Without a selection tab, the module operates at four-second trial
time and one ignition.
•
•
•
Selection tabs A and B — 4 seconds.
Selection tabs C and D — 7 seconds.
Wire the module
- Use diagrams in installation instructions for wiring
10
Selection Tab Installation
See Tables 1 through 3 in installation instructions (Form 68-1061) for correct
tab selection.
Select and Install the correct tab, push firmly in place and discard the
remaining tabs.
11
Selection Tab Cross Reference
12
Select Timing & Tries
!
24V
VALVE
LED
L2
TRIAL: 7 SEC
1 TRY
(C)
13
HSI
L1
HSI
SENSE
S8910U HOT SURFACE IGNITION
VALVE
Honeywell
24V
WARNING
GND
Troubleshooting
LED Indicator Light
!
LED
24V
VALVE
Meaning
Normal operation
Lockout
Flame signal
Internal
LED
VALVE
L2
HSI
L1
HSI
SENSE
15
S8910U HOT SURFACE IGNITION
Flashes
Pulse
1
2
3
24V
WARNING
GND
Troubleshooting of the S8910U
LED shows system status for the current call for
heat:
- Pulsing heartbeat is the normal operating mode during a call for heat (24V
-
terminal is powered). The system can be in any of the normal operating modes
including prepurge, warm-up, ignition trial, between trial purge, or normal run.
One flash indicates the S8910U is in an ignition lockout mode. The most
probable cause is the main burner failing to light or failure to detect the flame.
Run the appliance through a call for heat and if the burner does not light, check
the:
 gas supply
 input voltage
 hot surface igniter
 gas control
 Wiring
- If the main burner lights, but goes out at the end of ignition trial, check the:
 igniter/sensor
 flame rod
 burner ground connections
 wiring
16
Troubleshooting of the S8910U
LED – Continued
• Two flashes indicates the flame rectification signal is weak. The most probable
causes are:
- contaminated or mis-located igniter/sensor or flame rod
- poor flame sense lead-wire insulation or connections
- poor gas pressure
• If the flame rectification signal is strong when the appliance lights, but weak
while heat is being delivered, check for overheating of the igniter/sensor,
flame rod ceramic or flame sense leadwires.
• Three flashes indicate an internal error. The most probable cause is an S8910U
logic failure. Start a new call for heat and if the three-flash signal returns, replace
the S8910U.
17
Product Cross Reference
Product Cross Reference
• Where do I find Honeywell electronic ignition cross
reference and selection information?
- www.customer.honeywell.com
- Honeywell Application Selection and Cross
Reference Guide – Form 63-9575
- Honeywell Laminated Truck Visor – Form 63-9581
- Honeywell Gas Counter Mat – Form 63-9580
- Honeywell Residential Technical Support: 1-800-468-1502
19
Product Cross Reference Guide
Forms 63-9575 and 63-9581 – information also found in product installation sheets.
20
www.customer.honeywell.com
• See Cross Reference Search box in right column
21
The S8910U Advantage
• When promoting the S8910U keep these advantages in mind:
 The S8910U replaces over 100 Honeywell and competitor’s ignition
modules; reduces inventory by stocking one versus many and saves
time and money looking for the right part.
 Easy to use instructions and adaptation accessories saves the
contractor valuable time and resources.
 Personality” Plug-Ins - match the ignition sequence of the model being
replaced using the plug in selector tabs for a true Universal replacement.
 The S8910 is application flexible and can be used with single rod or dual
rod systems, and natural or LP gas.
 The diagnostic LED makes troubleshooting simple, identifying ignition
lockout, flame rectification signal and control failure, solving the
problem quickly and satisfying the customer.
22
S8910U
Universal Electronic Ignition
Knowledge Test
Universal Electronic Ignition Knowledge Test
• Now that you completed this training module, take the
short quiz to test your knowledge.
24
HONEYWELL - CONFIDENTIAL
File Number
Test
1. The S8910U1000 is a hot surface ignition module?
T or F
2. The S8910U is application flexible and works with
single or dual rod systems? T or F
3. The S8910U can be used with LP gas only? T or F
4. The LED light displays the following: normal
operation, lockout, weak flame signal and internal
error? T or F
5. If the internal error signal is still present after a
new call for heat the S8910 can be repaired, it
does not have to be replaced? T or F
25
HONEYWELL - CONFIDENTIAL
File Number
Test
6. The S8910U has “personality plug-ins” to match
the ignition sequence of the control being
replaced? T or F
7. An ignition sequence must be chosen as there is
no factory set sequence? T or F
8. The adaptation accessory kit includes parts to
convert from White Rodgers and Robertshaw
controls? T or F
9. The Honeywell S8910U replaces over one hundred
Honeywell and competitive ignition modules? T or
F
10. The Honeywell S8910U is widely recognized in the
industry as a top performer in the industry? T or F
26
HONEYWELL - CONFIDENTIAL
File Number
Answer Key
1. T
2. T
3. F
4. T
5. F
6. T
7. F
8. T
9. T
10. T
27