Welcome to Daikin Europe N.V.
Download
Report
Transcript Welcome to Daikin Europe N.V.
EWWD170-600DJYNN
EWWD170-600DJYNN
Water Cooled Chiller
166 kW ÷ 604 kW
Single Screw Compressor
17-Jul-15
2
TABLE OF CONTENT
A. Unit position into the range
B. Operating Limits
C. Compressor features
D. Refrigerant Circuit
E. Dry-eXpansion shell & tube evaporator
F. Control & remote control
G. Unit delivery
H. EWWD-DJYNN Options Summary
1. Standard options
2. Options on request
17-Jul-15
3
A. UNIT POSITION INTO THE RANGE (1/3)
EWWD-DJYNN: unit efficiency level
4.90
500
190
280
230
4.70
400
550
460
380
4.50
650
320
EER
4.30
4.10
170
210
320
380
420
260
460
500
3.90
300
600
3.70
EWWD-DJYNN
3.50
100
200
300
400
EWWD-DJYNN/A
500
600
700
kW
17-Jul-15
4
A. UNIT POSITION INTO THE RANGE (2/3)
EWWD-DJYNN: cooling range
EWWD
DJYNN/A
EWWD
DJYNN
1 Compressor
2 Compressors
1 Compressor
100
200
2 Compressors
300
400
500
600
700
kW cooling @ Evap. 12/7°C - Cond. 30/35°C
17-Jul-15
5
A. UNIT POSITION INTO THE RANGE (3/3)
EWWD-DJYNN: sizes distribution
186.4 223.3
165.5 201.2
276.5 306.7
252.8280.4
366.3
408.2 443.6
333.9 372.2 402.5
448.3
496
493.7
540.5
603.9
555.7
EWWD-DJYNN
EWWD-DJYNN/A
100
17-Jul-15
200
300
400
kW
500
600
700
6
B. OPERATING LIMITS
Operating range EWWD-DJYNN
Condenser leaving temperature - °C
55
50
45
40
35
30
25
20
-10
-8
-6
-4
-2
0
2
4
6
8
10
12
14
16
18
Evaporator leaving temperature - °C
Note: Glycol is necessary for evaporator leaving water temperatures below +3°C
17-Jul-15
7
C. COMPRESSOR FEATURES (1/3)
EWWD-DJYNN – Single Screw Compressor
“ Frame3200 ” single
screw compressor
axial balanced loads
radial balanced loads
2 specular compression cycles
infinitely variable cooling capacity control
integrated oil separator
direct driven screw (no gear)
6 electrical terminals for Y-D as standard
fully semi-hermetic design
composite material on gate rotors
discharge
17-Jul-15
compression
suction
8
C. COMPRESSOR FEATURES (2/3)
EWWD-DJYNN – Single Screw Compressor
radial
balancing
axial balancing
“ Compressor ”
better chilled
water stability
Composite material (carbon base
composition) to improve compressor
reliability and energy performances
17-Jul-15
Stepless slide valve (oil controlled) to
change compressor capacity to
match exactly the plant thermal
request
9
C. COMPRESSOR FEATURES (3/3)
EWWD-DJYNN – Single Screw Compressor
The integral oil separator is bolted to the rear of
the main casing. The impingement type
separator is fitted with a knitted stainless steel
mesh element.
Six electrical terminals to allow as
standard a star-delta (Y-D) compressor
start
17-Jul-15
“ Frame 3200 ”
Fully semi-hermetic design to allow
ordinary maintenance and to replace
easily each component if necessary
10
D. REFRIGERANT CIRCUIT
EWWD-DJYNN single compressor circuit
17-Jul-15
11
E. Dry-eXpansion shell & tube evaporator
1) One pass configuration on refrigerant side (R-134a)
copper tube
internally enhanced
Better oil circulation and compressor oil return at part load operation
2) Higher water volume content (Vs PHE Plate Heat Exchanger)
More thermal inertia for the chiller
Smaller external water tank installation (when required)
No freezing risk at any chiller load
17-Jul-15
No “water hammer” phenomena damage
12
F. CONTROL AND REMOTE CONTROL (1/4)
EWWD-DJYNN – Electrical Panel Features
Main switch: only on OFF position, it allows the access inside the panel.
Control keypad and display are located outside on the front door.
17-Jul-15
13
F. CONTROL AND REMOTE CONTROL (2/4)
EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”
Motherboard with microprocessors
Unit Controller fully programmed and engineered by Daikin on Carel
hardware
P.I.D. logic (proportional, integrative, derivative)
Compressor regulated according leaving evaporator water temperature
(LEWT) to match customer set-point within ± 0.2°C
Easy visual interface with 4 rows and 20 characters display and 15 keypad
17-Jul-15
14
F. CONTROL AND REMOTE CONTROL (3/4)
EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”
STANDARD
SPN
High value control functions implemented as standard into the logic
17-Jul-15
15
F. CONTROL AND REMOTE CONTROL (4/4)
EWWD-DJYNN – Microprocessor Control “Microtech II C Plus”
Easy integration into building automation systems via separate digital
connection for unit start/stop and 4-20 mA signals for chilled water
reset and demand limiting;
Communications capabilities for remote monitoring, changing of
setpoint, trend logging, alarm and event detection, via a compatible
IBM-PC with PlantVisor 1.0 software;
BMS communication capability via Modbus, BacNet & LonWorks protocol
Remote communication via modem/GSM (up to 8 chillers with Gateway)
Compatibility with Daikin CSC II (Chiller Sequencing Control)
17-Jul-15
16
G. UNIT DELIVERY
EWWD-DJYNN – Unit delivery, moving and lifting
Unit is delivered EXW (Ex works);
Each unit is tested at full load before shipping;
Unit handling must be according to IOM manual.
17-Jul-15
17
H. EWWD-DJYNN:
Standard options
Available options
Heatpump version
OPPF: Power factor 0.9
Brine version
OP57: A/V meter
Dual setpoint
OPSS: Soft starter
Thermal relays compressors
OPNI: Cu/Ni heat exchanger
Under/over voltage controller
OPLN: Low noise version
Victaulic on condenser & evaporator
OPPR: Partial Heat Recovery
Flow switch for evaporator
OPTR: Heat Recovery
Setpoint reset and demand limit
Alarm from external device
Rubber type antivibration mounts
Main switch
Unit Types
/A: High Efficiency
Electronic expansion valve
Suction stop valve
17-Jul-15
18
1. OPTIONS AS STANDARD (1/2)
SUCTION LINE SHUT OFF VALVE – Suction shut-off valve
installed on the suction port of the compressor to facilitate
maintenance operation.
ALARM FROM EXTERNAL DEVICE – Microprocessor is able to receive an alarm
signal from an external device (pump etc…). User can decide if this alarm signal
will stop or not the unit.
FLOW SWITCH – Supplied separately to be wired and installed on the evaporator
water piping (by others).
COMPRESSOR THERMAL OVER RELAYS – Safety devices against compressor
motor overloading in addition to the normal protection envisaged by the electrical
windings.
17-Jul-15
19
1. OPTIONS AS STANDARD (2/2)
UNDER/OVER VOLTAGE CONTROLLER – Phase monitor to control the
minimum and maximum voltage value that the user can set.
RUBBER TYPE ANTIVIBRATION MOUNTS – Supplied separately, these are
positionned under the base of the unit for “floor installation”.
ELECTRONIC EXPANSION VALVE– It proposes features that makes it unique:
short openning and closing time, high resolution, positive shut-off function to
eliminate use of additional solenoid valve, highly linear flow capacity,
continous modulation of mass flow without stress in the refrigerant circuit and
corrosion resistance stainless steel body.
17-Jul-15
20
2. OPTIONS ON REQUEST (1/2)
OPSS: Soft start - Electronic starting device to reduce starting current. An overload
protection is included (no need of compressors thermal relays).
OPLN: Sound proof cabinet - Made of sheet metal and internally insulated, the sound
proof cabinet is around the compressor/s reach the best performance in noise reduction.
OPPF: Capacitor power factor correction - Installed on the electrical control panel to
ensure it conforms to the plant rules (Daikin advises maximum 0,9).
OP57: Ammeter and voltmeter - Digital meters of unit drawn amperes and voltage
values, installed on the electrical control panel.
17-Jul-15
21
2. OPTIONS ON REQUEST (2/2)
OPTR: 100% total heat recovery – Produced with tube bundle placed in a single
shell with the water condensers heads provided with 2 connections for
entering/leaving heat recovery water and 2 separate connections for
condensing water.
OPPR: Partial heat recovery – Produced with plate to plate heat exchangers
installed on discharge side of compressor gas. These allow hot water to be
produced up to a maximum temperature of +50°C
17-Jul-15
22
17-Jul-15
23