Digital Energy

Download Report

Transcript Digital Energy

GE Digital Energy
Meter Products
By John S. Levine, P.E.
Levine Lectronics and Lectric
GE Multilin has full spectrum of advanced metering
EPM4600
EPM7000
EPM9900
EPM9800
PQM II
EPM9450
EPM 9650
EPM6100
EPM6000
Price
EPM2200
EPM7100
Basic Power
Monitoring
•
•
•
Advanced PQ Analysis
Power Quality & Cost Management
Replacement of
Analog Meters
Campus Monitoring
Energy Management
•
•
•
•
Generator over and
under voltage
Over frequency
monitoring
Continuous
monitoring
Voltage Studies
•
•
•
Monitoring
Transformer losses
Monitoring transients
Time of Use energy
use
2
Basic Power Monitoring:
EPM2200
The Need for the EPM2200
• Responded to Requests
for an Easier To Use
Meter
• Improvements in Accuracy
over its predecessor
• Available at a lower
starting price
4
Distinguishing Features
Basic Power Monitoring
• Very easy to set-up and
use
• Economical Volts/Amps,
Power and Energy Meter
• Optional Modbus
Communications
5
EPM 2200: Basic Power Monitoring
Easy Installation
ANSI C39.1 Standard
92mm DIN Standard
Bright 3 Line Display
Easy to Read
Auto Scaling (Kilo, Mega,
Giga)
4 Digits per line
Easy to Read Load Bar Graph
Auto-Scrolling
Measures over 40 Parameters
Easy to Navigate through
Parameters
6
EPM 2200: Example Applications
Generator
Panels
Switchgear
Economical Metering Solution
7
EPM 2200: Replacing Analog Meters
Current
Order Code:
Analog meter
becomes
PL2200A1X
Voltage
Switches used to view
different phases
8
EPM 2200: Firmware Features
9
EPM 2200: Order Codes
10
EPM 2200 GE Product Comparisons
EPM2200
EPM6000
11
EPM 6000 and EPM 2200
GE
EPM2200
Accuracy
ANSI Class
Bi-directional power
Harmonics THD
Configurable Alarm Threshold
KYZ Pulse Output
0.5%
GE
EPM6000
0.2%
C12.2
EPM 6000 Offers:
Higher Accuracy
Revenue Grade
THD Measurements
More Comm Options
RS-485 + Modbus RTU
Front Communications Port
Ethernet + Modbus TCP
DNP 3.0
EPM 2200 Offers:
Cost Effective
Measurement
12
Basic Power Management
Enhancements:
EPM6000
EPM6000 Ethernet Option
EPM6000 Ethernet Option
EPM 6010 BACnet Building
Automation Power Meter
EPM6010
Power Quality and
Management
EPM7000
EPM 7000
• Up to 4 Mb Data
Logging
• 512 samples/cycle
• Power quality
• Ethernet
• Web server
EPM 7000: Power Analysis and Data Logging
Easy Installation
ANSI C39.1 Standard
92mm DIN Standard
Bright 3 Line Display
Easy to Read
Auto Scaling (Kilo, Mega,
Giga)
4 Digits per line
IRDA Port
Auto-Scrolling
Easy to Read Load Bar Graph
Easy to Navigate through
Parameters
19
EPM 7000: Communications
Field Replaceable Modules.
• Ethernet
• 4 Bi-directional Analog Outputs
• 2 Relay Outputs + 2 Status
Inputs
• Four form A Pulse Outputs,
Four Status Inputs
• Fiber Optic Serial Port
20
EPM7000 Web Server
21
EPM7000:
Voltage and Waveform Recording
22
EPM7000: Firmware Options
Firmware Version
Feature
Multifunction Measurement with
with I/O expansion
2 MB Data-Logging
A
B
C
D
E
F
●
●
●
●
●
●
●
●
●
●
3 MB Data-Logging
●
4 MB Data-Logging
Harmonic Analysis
Limit and Control Functions
64 Samples per Cycle Waveform Capture
512 Samples per Cycle Waveform Capture
●
●
●
●
●
●
●
●
●
23
EPM7000: Order Codes
Current
Freq Inputs
Software Power Supply
I/O Slot 1 I/O Slot 1
Description
5|
|
|
|
|
50 Hz AC frequency system
6|
|
|
|
|
60 Hz AC frequency system
5A
|
|
|
|
10 Amp Secondary
1A
|
|
|
|
2 Amp Secondary
A
|
|
|
Multimeter Function Only
B
|
|
|
Data Logging Memory
C
|
|
|
Power Quality Harmonics
D
|
|
|
Limits and Control
E
|
|
|
64 Samples/Cycle Waveform Recording
F
|
|
|
512 Samples/Cycle Waveform Recording
HI
|
|
90-265VAC/VDC
LDC
|
|
18-60VDC
X
X
None
E1
E1
100BaseT Ethernet
C1
C1
Four Channel Bi-directional 0-1mA Outputs
C20
C20
Four Channel Bi-directional 0-20mA Outputs
F1
F1
Fiber Optic Serial Port - ST Terminated
F2
F2
Fiber Optic Serial Port - Versatile Link
RS1
RS1
Two Relay status Outputs / Two Status Inputs
PS1
PS1
Four Pulse Outputs / Four Status Inputs
PL7000
24
Submetering
Industrial Meters Product Positioning: 2014
Submetering
EPM 4600
Price
EPM 7100
EPM 6100
•
•
•
•
Basic Power
Monitoring
Wifi or 10/100TX
Multifunction Meter
THD% and Alarm
0.2% Accuracy
Multipoint Submeter
Data Logging
•
•
•
•
•
Data logging
Wifi or 10/100TX
Multifunction Meter
0.2% Accuracy
Dataloggging up to
2mb
•
•
•
•
Data logging (up to 32
MB)
Wifi, 10/100TX, RS485
USB
8 – 3 phase or
24 single phase
0.5% Accuracy
26
EPM 6100
Demand and Energy Submeter
with WiFi
EPM 6100
• 0.2% Accuracy
• 400+ Samples/Cycle
• WiFi or 10/100TX
or Serial RS485
• THD% and Alarms
EPM 6100
Large 0.56” LEDs
IrDA Port
Screen Selector
Load Bar
Auto Scale Indicator
EPM 6100: Profile
EPM 6100: Back
EPM 6100:
Internals
High Accuracy
Measurement
Circuitry
Voltage &
Current
Connections
RJ45
Jumper to
Select LAN
Or Serial
RS485
KYZ Pulse
EPM 7100
• Data Logging Up to 2MB
• RS485 Modbus
• Optional Wi-Fi, or Ethernet
• 0.2% Accuracy
EPM 4600
Multi-feed Power and Energy
Metering Solution with advanced
communications, logging and
touchscreen display
EPM 4600 Multi-feed Meter
What is it?
The GE EPM 4600 Multi-feed Power and Energy
Meter is a sub-metering solution that allows
owners and operators to quickly, accurately and
centrally measure power and energy usage of
specific areas to reduce operating expenses. This
leads to improved tenant attraction and retention
and greater efficiency throughout facilities.
The EPM 4600 can be used for both new and
retrofit installations for applications such as:
•Shopping Malls / Shopping Centers
•Apartments / Condominiums
•University Campuses
•Data Centers
•Hospital Loads
•LEED Projects
•Tenant Sub-Metering
•Industrial Circuit Cost Allocation
•Load Management and Load Curtailment
•Distribution Transformer Metering
Value Proposition
•Provides measurement of a baseline for Power and
Energy Management strategy implementation
•Capital and maintenance cost savings through
Consolidation of Metering Points and space saving,
High Density Design
•Provides the hardware basis to start a consultative
solution sell on a GE Energy Management Solution
35
A single EPM 4600 replaces 8 Three Phase
Meters or 24 single phase meters
•
•
•
Lower cost per meter point
Space Savings
Lower Installation costs
36
Key Features
Features& Benefits – PMCS v6.31
dKey
Feature
Revenue Grade
Accuracy
Standard/
Chargeable
Description
Benefit(s) to Customer
Standard
• Highly Accurate Revenue Grade Accuracy
- Compliant with revenue grade
certifications for billing purposes
• Meter Electrical Usage with 0.5%
Accuracy using Industry Standard Current
Sensors
Meets ANSI C12.20 and IEC 62053-22
Class 0.5%
- Test Pulses for Meter Accuracy Verification
Easy Installation
using standardized
CT wiring
Standard
Standard CT Wiring for Class 10 (5 Amp
Secondary) or Class 2 (1 Amp Secondary)
for
High Accuracy Measurements
- Ease of installation using market
standard components
Installation
Flexibility: Three
phase and Single
phase
configurations
Chargeable
The EPM 4600 comes in 2 configurations for
to handle eight 3 phase inputs or 24 single
phase inputs
- Decreases commissioning effort
and provide flexibility to install as
per the needs of an existing
electrical system.
Advanced Load
Profiling and
Logging
Chargeable
Load profiling and logging of measured
values to record data for further advanced
analysis
- Provides ability to collect and log
information for further advanced
energy management analysis
(Reporting, Billing)
Flexible
communications
options
Chargeable
Multiple communications options including
RS485, Ethernet / WIFI, USB
- Multitude of communications
options provides flexibility for
installation and existing
communications investment
- USB for local connectivity
37
Key Features
Benefits – PMCS v6.31
Features&(Cont’d)
dKey
Feature
Standard/
Chargeable
Flexible I/O
Standard
Description
Benefit(s) to Customer
• 4 Pulse Counting Inputs for Other
Commodities such as Water, Gas and
Condensate
- Flexible metering and connectivity
between existing and other
metering systems.
• 2 Relay Outputs for Control Operations
Field upgradable
Chargeable
• Field upgradable software options to
increase functionality from standard
transducer to comprehensive logger with
recording capability
- Upgradable solution with low
maintenance and ongoing installation
cost
Easy configuration
Standard
Easy configuration through GE
Communicator software
- Decreases commissioning effort
and provides easy installation and
low training effort for ongoing
maintenance
38
Key Features
& Benefits
– PMCS v6.31
4600 Physical
Layout
dEPM
39
Key Features
& Benefits
– PMCS v6.31
4600 Physical
Dimensions
dEPM
Class leading, Small Footprint perfect for Embedded
Power Distribution Panel Application
40
Key Features
& Benefits
– PMCS
v6.31
4600 Memory
Logging
Specifications
dEPM
Logging Memory
Software Option A:
Software Option B (2MB) :
Software Option C (32MB):
Transducer
100 to 300 Days of Logging
Up to 2400 Days of Logging
Notes on Logging:
• Logging is based on 4 bytes per reading + 7 byte time stamp
• 103 bytes per entry for 24 single phase inputs
• 39 bytes per entry for 8 three phase inputs
• Time base is 15 minute profiling
41
Key Features
& Benefits
– PMCS
4600 Optional
Touch
Screenv6.31
Displays
dEPM
•
•
•
•
Low power consumption, 65K color displays
Available in two sizes:
• 5.7” (PL4600-DIS5700)
• 3.5” (PL4600-DIS3500)
User-Friendly Installation and Setup
• Preconfigured Screens
• 22mm panel mount
• 24 VDC Power Supply
Local/Remote Display Connectivity
• Via Serial or optional Ethernet port on
EPM 4600
42
EPM
4600
Displays
–
Local/Remote
Key
Features
&
Benefits
– PMCS v6.31
d
Visualization
Connect displays via Serial and/or Ethernet for local or
remote visualization capability
43
Key Features
& Benefits
– PMCS
v6.31
4600 Displays
– Display
Screens
dEPM
Single Phase Energy Readings (EPM4600-S)
KWatts, KW Demand, KWatt-hours
Consolidate Pulse Inputs to Measure Various Energy Types
Three Phase Energy Readings (EPM4600-T)
KWatts Phase A, KWatts Phase B, KWatts Phase C
Limit Based Alarms
Single Phase Phasor Diagram (EPM4600-S)
Three Phase Phasor Diagram (EPM4600-T)
44
EPM 6000T & EPM 7000T
46
Product Family Comparisons
Comparisons
EPM6000/7000, PQMII, and EPM9650
48
GE Product Comparison
Basic Power
Monitoring
Power Quality and Cost
Management
Advanced Power Quality
Analysis
Feature
EPM6000
EPM7000
PQMII
EPM9450
EPM9650
Accuracy
0.2%
0.2%
0.4%
0.04%
0.04%
400+
400+
64
512
512
Max 4MB
296KB
512KB
Max 2MB
WebServer
Ethernet
Samples/cycle
Sag/Swell
Time of Use
Data Logging
THD Real-Time THD% only
40th order
32nd
128th Order
128th Order
49
EPM 9900
Advanced Power Meter with
Transient Recorder
EPM 9900
Industry Leading Revenue Meter Features
• Vivid Color LCD Display
• 1GB Memory for logging and analysis
• 10MHz Transient Recorder
• 1024 Samples/cycle
• Auto-calibrating 0.06% revenue
meter
•Fast Data Download
•Web Server
•Expandable I/O
•Upgradable Software Options
•Meets IEC 61000-4-30 Class A
standards
GE ITI
Instrument
Transformers
52
53
Questions?
Thank You !
EPM 9900
Industry Leading Revenue Meter Features
• Vivid Color LCD Display
• 1GB Memory for logging and analysis
• 10MHz Transient Recorder
• 1024 Samples/cycle
• Auto-calibrating 0.06% revenue
meter
•Fast Data Download
•Web Server
•Expandable I/O
•Upgradable Software Options
•Meets IEC 61000-4-30 Class A
standards
EPM 9900 - Accuracy
•
•
•
•
0.06% - Revenue Accuracy
ANSI C12.20, Class 0.2
IEC 62053.22 rated
IEC 687 Rated
• Auto Calibrating
• Compensation for:
• Transformer and Line Loss
• CT and PT
Accurate, Auto- calibrating, High-end Revenue Metering Features
56
EPM 9900 – Metering Functionality
• 4 Quadrant Meter






kWh delivered
kWh received
kVAh by quadrant
kVARh by quadrant
Qhour measurement
Demand for each measurement
• Time of Use metering





8 TOU schedules
Bi-directional consumption & demand
4 seasons/year
20 year calendar
Prior month & prior season for each period
• Pulse Accumulation and Integration
• Load aggregation




8 pulse inputs (self-wetted)
4 totalizing registers
Add internal values to total
Gas or water meters
Fulfilling High-end Revenue Metering
Requirements
57
EPM 9900 – Metering Functionality
•Multiple Demand Windows
•4 demand structures simultaneously
•Types of demand:
 Fixed window
 Rolling demand
 Predictive demand
 Thermal demand
 Intervals - 1 second to several hours
 Up to 255 subintervals
•Time Stamped Max. Demands
•kW demand delivered & received – max & min
•kVAR demand delivered & received – max & min
•kVAR coincident with kW demand
•kVA demand – max & min
•Amps - max & min
•Voltage - max & min
•Timing options
• EOI pulse out
• EOI pulse in
• IRIG-B input to external GPS clock
Fulfilling High-end Revenue Metering
Requirements
58
EPM 9900 – Metering Functionality
• System Events Log
• This feature logs any event that occurs in the meter, including:
•
Power up/down
•
Password access/modification
•
Change of the programmable settings
•
Change of a runtime firmware
•
Change of time by communication (Modbus, DNP)
•
Log downloads
•
Feature resets (logs, max/min, energy)
All these features are designed for anti-tampering purposes.
Fulfilling High-end Revenue Metering
Requirements
59
Benefits of Auto-Calibration
• Accuracy over Temperature. Meters drift over temperature.
Moreover, hysteresis in drift may compromise accuracy permanently
and require the meter to be returned for re-calibration. GE’s autocalibration insures that normal drift caused by ambient temperature
movement does not affect accuracy.
• Accuracy over Time. Since the majority of components within the
meter are being re-calibrated on a regular interval, the meter will hold
accuracy longer than non-calibrating meters.
• Better Out of Box Test Results. Components from new meters
sometimes need up to 1000 hours to stabilize. Using auto-calibration,
the components will be recalibrated over the life of the meter.
• Less Maintenance / Lower Ownership Cost. Since the meter autocalibrates, less meters will be removed from the field for calibration.
60
Commercial/Industrial Revenue
Metering Functions
•Monitor, control and alarm on peak demand for
conducting load shedding schemes and demand charge
reduction schemes
•Track power usage system wide with high accuracy to
reconcile with utility meter results
•Monitor PF distribution and enable PF correction to
balance loads and reduce VARs on the system
•Monitor and participate in demand response, utilizing
excess backup generation
•Meter energy efficiency initiatives for actual energy
savings
Rich Insight into Energy and Power Quality
System Metrics
61
EPM 9900 - Extensive Load Profiling and
Recording
Features include:
•1 GB of Memory
•User Configured file structure with 17
separate logs
•Up to 8 separate historical logs
•Each log can store 128 parameters
•Each log can store data for years before
filling
•A significant improvement over existing
technology
•Data stored in an industrial-grade solid
state flash drive designed for high
performance and temperature stability
Best in class storage/logging capabilities
62
EPM 9900 - Extensive Load Profiling and
Recording
Examples of Storage
Capability
3 voltage readings + time stamp = 24 bytes
storage interval = 15 minutes
log memory = 60 meg
storage in years = 70 years
24 readings + time stamp = 106 bytes
storage interval = 15 minutes
log memory =60 meg
storage in years = 16 years
24 readings + time stamp = 106 bytes
storage = 1 second
log memory = 60 meg
storage in days = 6.6 days
Large memory capacity for years
of reliable data recording and analysis
63
EPM 9900 - Blazing Fast Download Speed
and Ethernet Performance
Rapid Response™ Ethernet: Download data
almost 80 times faster than existing EPM 9000
Meter technology
Download speeds over Ethernet for EPM 9000 Series Meters:
500
400
350
400
300
300
250
9450 Meter
9650 Meter
9900 Meter
200
150
100
50
0
200
100
9450 Meter
9650 Meter
9900 Meter
0
kbytes per Second
Download Speed
Number of Seconds to
Download 2 Meg of Storage
over Ethernet
*Speeds on all meter downloads dependent on quality
and speed of existing network.
64
EPM 9900 – Precise Time Synchronization
•
IRIG-B: The EPM 9900 meter’s time can be synchronized to the signal from a GPS IRIG-B satellite. IRIG-B has a
pulse rate of 100 pulses-per-second with an index count of 10 msecs over its one second time frame. IRIG-B
sync has a time accuracy of better than 100 microseconds.
• Network Time Protocol server: You can set up the meter’s Ethernet port to synchronize time using a
Network Time Protocol (NTP) server. Typical accuracy is achieved to at least 1 msec, depending on network
configuration.
• Line Frequency clock synchronization: The EPM 9900 meter’s time can be synchronized to the AC
frequency.
• Internal clock crystal: The EPM 9900 meter’s internal clock crystal is accurate to 20ppm. It can be used if
IRIG-B is not connected and/or other synchronization methods are not being used.
• DNP time synchronization: Using Communicator EXTTM software, you can set the meter to request time
synchronization from the DNP Master. Requests can be made from once per minute to once per day.
65
EPM 9900 - Power Quality and System
Reliability Recording
• Measure power quality indices such as voltage
anomalies, harmonics, flicker, imbalances and
many other conditions
• Record waveform event on sags and swells,
including peak and duration of the event, with
microsecond resolution
• Analyze damaging high speed positive and
negative transients in the MHz range,
which can damage equipment
• Report on events using industry certified IEC
61000-4-30 Class A standards and EN50160
reports
66
EPM 9900 - System Reliability
Improvements
•
Monitor voltage reliability system wide to insure
proper voltage distribution
•
Analyze critical feeds to determine if power
distribution is optimized, i.e.; Is PF too high? Is
voltage reliable? Are there too many drops on
the line?
•
Conduct forensic analysis on feeds and
equipment to provide proactive awareness of
problems before they occur
•
Audit power system for weakness or
troubleshoot within the power system
•
Alert engineers by email or on a display when a
critical alarm occurs!
67
EPM 9900 - Power Quality and System
Reliability Recording
8 Channel Waveform Recorder
•
•
•
•
•
•
Standard Recording at 1024 Samples per cycle
16 Bit Analog to Digital Converter Resolution
Extensive Memory to record for years
High-speed input event recording
Outage detection
Extensive limit setting capabilities with multiple limits per selected
quantity
Waveform Memory Example – 128 samples per cycle
Sampling Rate = 128 samples per cycle
Channels = 8
Memory = 500 meg
Number of cycles = 245,000 cycle of recording
Number of minutes continuous = 68 minutes
Waveform Memory Example – 16 samples per cycle
•
•
•
•
•
Sampling Rate = 16
Channels = 8
Memory = 500 meg
Number of cycles = 1,960,000
Number of minutes continuous = 544 minutes
Advanced Power Quality Metering Features
68
EPM 9900 Meter Records Voltage
Transients at 10Mhz Resolution
4 Channel Transient Recorder
•
•
•
•
View both positive and negative transients
occurring on the voltage lines
The unit provides both magnitude and
duration of the transient
EPM 9900 uniquely replaces the lower
speed sample with the transient sample
on the waveform to optimize storage and
reduce file size.
Timing is as accurate as 20 nanoseconds.
High-speed sampling provides analysis invisible to lower
sampling speed meters
69
EPM 9900 - Blind Spots in Non-Transient
Recording Meters
Low-Speed Recorder Event
High-Speed Recorder Event
EPM 9900
Meter Picks up
Event
Event
Completely
Missed
Up to 1024
Samples per
Cycle
• Both meters store at 1024 samples per cycle.
• The EPM 9900 meter provides the event of the
transient.
• The transient is defined as an anomaly that occurred within
2 samples of the lower sampling speed of a waveform
capture.
166,000
Samples per
Cycle
Sampled;
stored at
same 1024
samples/cycle
• The minimum duration is dependent on the sampling
speed. The EPM 9900 meter’s sampling speed is
as fast as 20 nanoseconds. Any event that occurs
within two low-speed samples will be recorded and
stored for engineering analysis.
70
IEC 61000-4-30 Class A Power Quality
and Waveform Recording
• IEC 61000-4-30 class A standard
reporting; Flicker compliant with IEC
61000-4-15 and
IEC 61000-4-30
Nexus ® 1500 Auto-Calibrating Power Monitors
• Short term readings: PST-10
min/logging & monitoring
• Long term readings: PLT – 4 Hr/logging
& monitoring
• Log viewer: View graphed values; Pst
and Plt for Va, Vb and Vc or displayed
values, including max & min
• Polling: Pinst, Pst, Pst Max, Pst Min, Plt,
Plt Max, Plt Min values
• Utilizes 16 Bit Analog to Digital
conversion and high sampling rates to
provide accuracy throughout range
• High A/D resolution and sampling rates
are essential for good performance; lower
resolution of sampling results generally in
faulty measurements
Reliable, Highly Accurate, Compliance-Grade
Flicker Measurement
71
IEC 61000-4-30 Class A
Certified Compliance Reporting
What Is IEC 61000-4-30 Class A?
•
It is the definitive Industry Standard on Voltage Reliability Monitoring
•
It provides a comprehensive measurement of power quality including:
1.
Voltage Interruptions
2.
Harmonics (As per EN61000-4-7)
3.
Inter-harmonics
4.
Frequency
5.
Flicker (As per EN61000-4-15)
6.
Imbalances (Unbalances)
72
IEC 61000-4-30 Class A
Certified Compliance Reporting
Why is IEC 61000-4-30 Class A so Important?
•
It is designed to address the issue of multiple recorders using
differing DSP techniques producing differing results.
•
This Standard normalizes the digital signal processing so that all
monitors report the same results for the same occurrence
•
This eliminates confusion in the industry
•
False Claims -- There are multitudes of instruments making
false claims to be compliant with the class A standard. There is
only one Lab known to GE that can certify a monitor, Power
Standard Labs in Northern California
•
It is imperative to ask the monitoring company to providing it
certification documents.
73
EPM 9900
EN50160 Power Quality Reporting
Weekly Reports Insure Compliance with Power Quality Directives
•
Meter Generates a Weekly report based on
EN50160 Format using IEC 61000-4-30 Class
A Generated Calculations
•
Reports are stored in Compact Flash for many
years
•
Power Quality Compliance is easily sorted and
understood making compliance analysis
simple
•
Report Includes Voltage Dips, Frequency
Variations, Harmonics, Inter-Harmonics,
Flickers, and Unbalance.
•
Easy Pass / Fail Indication in total and per
criteria with graphing and binning.
74
EPM 9900 - ITIC/CBEMA Logging
•
Thousands of CBEMA Events
•
Transient Recording
•
Sag/Swell Analysis
•
Graphical Plotting in 3D Format
Waveform Display
Separate log for CBEMA Data Provides
Instantaneous Analysis
75
EPM 9900 Vivid Color LCD
Display
High Resolution LCD color display with
Touch-screen capability
 Bright TFT glass with high temperature rating
 Long-life LED backlight
 Vertical or Horizontal orientation
 Displays include:
• Real-time viewing: voltage, current, power, demand
• Accumulated energy and TOU
• Flicker readings
• Alarms
• Phasor analysis
• Harmonic spectrum analysis and waveforms
• Real-time trending
• Log status
• Configuration settings
The interface is simple to
understand and navigate
76
EPM 9900 - RTU Master Capability
RTU Master Makes EPM 9900
into an RTU
Mastering - Set Up Modbus registers to allow the Nexus
meters to poll registers from slave devices
Logging - Once the profile is set up and the meter is
polling data from the slave devices, then the data can be
logged in the historical log profiles for later retrieval
Modbus RTU Serial
 Alarming – The modus registers can also have limits
set points that could be used trigger alarms set-points,
send emails or log events in internal memory
Communication – All Data is available via multiple
communication paths including RS485 and Ethernet
 Perfect for Distribution Automation – Utilizing EPM
meters, distribution feeders can be automated WITHOUT
changing protective equipment.
77
EPM 9900 - Meter Face-Mounted Coms and Display
256-Color LCD Display
ANSI
Optical Port
Watt/hr
Pulse
Touch-screen
Overlay
Backlight
Button
VAR/hr
Pulse
High-speed
USB Port
Powerful, Yet Simple-to-Use Front Panel Interface
78
EPM 9900 Meter Rear Mounted Communication
Optional Upgrade Cards
Optional Dual
RS485 Outputs
and 4 KYZ
Pulse Outputs
Optional Second
100BaseT Ethernet:
Combination
RJ45/Fiber Optic Card
Standard
10/100BaseT
Ethernet RJ45
Port (Autodetecting Tx
and Rx)
Slots 3 and 4
Provide up to
12 Relay
Outputs
IRIG-B Satellite
Clock: 1msec
Time Sync
Color-coded
Voltage Inputs
8 High-Speed
Status Inputs
Upgradeable and Powerful Inputs and Outputs
79
EPM 9900 Communication
Options
Nexus ® 1500 Auto-Calibrating Power Monitors
Standard Inputs and
Outputs
•
•
•
•
•
•
ANSI Optical Port
High-speed USB Port
100BaseT Ethernet RJ45 Port
(Auto-detecting polarity)
IRIG-B Time Synchronizing to
GPS, 1ms. Resolution
8 High-speed status inputs
8 sockets Modbus TCP, 2
sockets DNP LAN/WAN
Optional
Communications
•
•
Dual RS485/Pulse Output
Ports
Additional 100BaseT
Ethernet Port –RJ45 or Fiber
Optic Card
Upgradeable I/O
•
Slots 3 and 4 provide up to
12 Form C Relay Outputs
for control or annunciation
80
External I/O Module Options
Analog Outputs
•
•
•
1mAON4 – 4 Channel 0-1mA Output
Card. Bidirectional and assignable to
any channel. 10Kohm Impedance
Max per channel
1mAON8 – 8 Channel 0-1mA Output
Card. Bidirectional and assignable to
any channel. 10Kohm Impedance
Max per channel
20mAON4 – 4 Channel 4-20mA
Output Card. Bidirectional and
assignable to any channel. 10Kohm
Impedance Max per channel
Analog Inputs
• 8AI1: 8 Analog Inputs,
0-1mA, bidirectional
• 8AI2: 8 Analog Inputs,
0-20mA
• 8AI3: 8 Analog Inputs,
0-5V DC
• 8AI4: 8 Analog Inputs,
0-10V DC
• Wiring: Common Mode
•
20mAON4 – 8 Channel 0-1mA
Output Card. Bidirectional and
assignable to any channel. 10Kohm
Impedance Max per channel
• Scaling: Programmable
81
Communication Options
Dual Ethernet Ports Provide Secured Com Over Two Separate Networks
Primary Ethernet Port
Provides 100 Base T
RJ45 Port
Secondary Ethernet
Can be used as
Redundant port or
limited access port on
different network
•Each Port has Separate Mac Address and IP Address
•Each Port Communicates Modbus and DNP 3.0 over Ethernet
•The Primary port can control the secondary port data access
•Multiple municipalities can securely share data from one meter through separate networks
•Perfect for redundant, high reliability applications
82
Total Web Solutions
Create Custom Web Site Screens
•
Allows a Simple Solution to put Readings on Web
•
Web Explorer – Meter Directly Hosts Web Pages
•
Download MV90 Data through Web
•
Web XML – Customize Web Sites to Meet for
your Application
•
Automatic Downloads of Stored Waveform Data.
•
Web Alarm – Email Alarm Conditions out to up to
10 users
•
WebReacher – Reach other Meters on Web
•
WebDNP – Gain Access to the Meter Speaking
Native DNP over Ethernet
•
10/100 Base T Ethernet
•
Works through browswer on Iphone, Android,
Ipad etc.!!
•
Works also with Firefox and other browsers
84
EPM 9900 Top Advantages
•
Very High Performance Recording Capability – Reason why the 9900 is the Best
Gigs of Memory to safely store data for years
•
Up to 10 MHZ Capture speed to capture every
anomaly. This meters doesn’t miss events.
•
Large Color Display – Easy navigation
•
Highly Versatile Communication Options – Up
to 6 com ports
•
Intrinsically Safe Mechanical Construction Best Current Inputs Connections
•
•
Upgradable I/O useful for every application
Easy to use configuration software
85
Order Codes
86