Ivo Pinkiewicz, IENOT, POLAND TRANSFORMER POPULATION …

Download Report

Transcript Ivo Pinkiewicz, IENOT, POLAND TRANSFORMER POPULATION …

Ivo Pinkiewicz, IENOT, POLAND
DISTRIBUTION TRANSFORMER
POPULATION
and
EFFICIENCY LEVELS
IN POLAND
DISTRIBUTION OF



RATED POWER
YEAR OF MANUFACTURING
LOSSES
RATED POWER
DISTRIBUTION OF RATED POWER IN ONE OF UTILITIES IN POLAND
25
15
10
5
RATED POWER [kVA]
1090
865
730
700
550
520
400
347
330
273
250
200
160
100
63
40
25
0
10
RELATED NUMBER OF UNITS [%]
20
RATED POWER DISTRIBUTION
OF TRANSFORMERS IN SEVERAL UTILITIES IN POLAND
45
40
RELATIVE NUM B ER [%]
35
30
Z1
Z2
25
Z3
Z4
20
Z5
15
M EA N
10
5
0
20
25
30
40
50
63
100
160
R ATE D P O W E R [kVA]
250
400
630
1000
1600
MANUFACTURING YEAR DISTRIBUTION
OF 160 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
8
6
4
2
MANUFACTURING YEAR
1998
1995
1992
1989
1986
1983
1980
1977
1974
1971
1968
1965
1962
1959
0
1956
RELATIVE NUMBER [%]
10
1998
1996
1994
1992
1990
1988
1986
1984
1982
1980
1978
1976
1974
1972
1970
1968
1966
1964
1962
1960
1958
1956
1954
1952
RELATIVE NUMBER [%]
MANUFACTURING YEAR DISTRIBUTION
OF 400 kVA TRANSFORMERS IN ONE OF UTILITIES IN POLAND
10
9
8
7
6
5
4
3
2
1
0
Units with age above 25, 30 and 35 years in groups
of transformer rated 160, 250 and 400 kVA.
RELATIVE NUMBER PIECEC. [%]
30
25
20
>25 years
15
>30 years
>35 years
10
5
0
160 kVA
250 kVA
400 kVA
LOSSES DISTRIBUTION
RELATION OF LOSSES IN TRANSFORMERS RATED 160 kVA
IN ONE OF UTILITIES IN POLAND
900
800
N O LOAD LOSSES [W]
700
600
500
M e a n o f p o p u l a ti o n
A -A '
400
C -C '
300
1999
200
100
0
1500
2000
2500
3000
L O A D L O S S E S [W ]
3500
4000
LOSSES DISTRIBUTION
RELATION OF LOSSES IN TRANSFORMERS RATED 400 kVA
IN ONE OF UTILITIES IN POLAND
2000
1800
1600
NO LOAD LOS S ES [W]
1400
1200
1000
800
A -A '
M e a n o f p o p u l a ti o n
C -C '
600
1999
400
200
0
3000
3500
4000
4500
5000
5500
LO A D LO S S ES [W ]
6000
6500
7000
7500
8000
LOSSES DISTRIBUTION
5000
900
4500
800
4000
700
3500
600
3000
500
2500
400
2000
300
1500
200
1000
100
500
0
C-C'
1998
1996
1994
1992
1990
1988
1986
1984
1982
1980
1978
1976
1974
1972
1970
1968
1966
1964
1962
1960
1958
0
LOAD LOSSES [W]
1000
1956
NO LOAD LOSSES [W]
NO LOAD and LOAD LOSSES OF 160 kVA TRANSFORMERS
IN ONE OF UTILITIES IN POLAND
LOSSES DISTRIBUTION
10000
1800
9000
1600
8000
1400
7000
1200
6000
1000
5000
800
4000
600
3000
400
2000
200
1000
C-C'
1998
1996
1994
1992
1990
1988
1986
1984
1982
1980
1978
1976
1974
1972
1970
1968
1966
1964
1962
1960
1958
1956
0
1954
0
LOAD LOSSES [W]
2000
1952
NO LOAD LOSSES [W]
NO LOAD and LOAD LOSSES OF 400 kVA TRANSFORMERS
IN ONE OF UTILITIES IN POLAND
LOSSES
COMPARISON LEVELS OF LOSSES OVER THE YEARS
1955-60
1999
C -C'
NO LOAD LOSSES
LOAD LOSSES
2,26 ... 3,09
0,94 ... 0,81
1
1,70 ... 1,92
1,12 ... 1,18
1
EFFICIENCY LEVELS
DATA NECESSARY TO ESTIMATE EFFICIENCY LEVEL:
 Rated
value of no load and load losses
 Yearly Load profiles specified by:
– Yearly peak load
– Running time
– Loss time
EFFICIENCY
COMMON VALUES OF LOAD PROFILE COOFFICIENTS IN POLAND
Yearly peak load...............0,30....0,35
 Running time..................3500....4560 h
 Loss time........................2100....3100 h

EFFICIENCY
IMPROVEMENT EFFICIENCY THROUGH REPLACEMENT THE OLD
TRANSFORMER 100 kVA by C-C' TRANSFORMER
EFFICIENCY IMPROVEMENT [%]
8
7
6
Ts=1500h
5
Ts=2000h
4
Ts=3000h
Ts=4000h
3
Ts=5000h
2
1
0
0
0,2
0,4
0,6
0,8
YEARLY PEAK LOAD
1
1,2
EFFICIENCY
YEARLY ENERGY SAVING THROUGH REPLACEMENT THE OLD
TRANSFORMER 100 kVA by C-C' TRANSFORMER
3000
ENERGY SAVED [kWh]
2500
2000
Ts=1500h
Ts=2000h
Ts=3000h
Ts=4000h
Ts=5000h
1500
1000
500
0
0
0,2
0,4
0,6
0,8
YEARLY PEAK LOAD
1
1,2
EFFICIENCY
COMPARISON TYPICAL LOAD PROFILES AVERAGE LOADED
TRANSFORMER 100 kVA IN WEST EUROPE AND POLAND
WEST EUROPE*
A-A'
C-C'
40
40
Yearly peak load [%]
1500
1500
Running time [h]
6,5
6,5
Average load [%]
57
57
Yearly energy transmited [MWh]
3013
2017
Energy loss [kWh]
94,7
96,5
Efficiency [%]
Improvement of efficiency [%]
1,8
Savings of energy [kWh]
996
*) acc. to THERMIE B PROJECT No STR-1678-98-BE
POLAND
Av. Popul
C'C'
40
40
4250
4250
19,5
19,5
146
146
3604
2469
97,5
98,3
0,8
1135
Energy savings and efficiency improvement in
Polish Utilities
E N E R G Y S A V IN G
E F F IC IE N C Y IMP R O V .
33
31
29
27
25
E F F IC IE N C Y IMP R OVE ME N T [% ]
0 ,0
23
0
21
0 ,5
19
5
17
1 ,0
15
10
13
1 ,5
11
15
9
2 ,0
7
20
5
2 ,5
3
25
1
E N E R GY S AVIN G [GWh ]
when existing population is replaced by C-C’ Transformers