S4000C Intelligent Sensor

Download Report

Transcript S4000C Intelligent Sensor

S4000C Intelligent Sensors..
… for Combustible Gas Detection
Model S4000C
Features:
Benefits:

Three Digit Display

Displays gas concentrations in %LEL,
fault codes for troubleshooting and
calibration prompts

4-20mA Output

Industry standard output for remote
alarm and fault indication

Dual Redundant MODBUS
Communications

Provides complete diagnostic status

Warning, Alarm & Fault Relays

Provides local alarm capability

Calibration, Gas Check, Setup Modes

Simplifies operation and maintenance

Remaining Sensor Life Indication

Reduces downtime by providing headsup on sensor life

Sensor can be remote mounted up to
7,600ft. (2,316M)

Increased installation flexibility
S4000C Key Features / Benefits

Remaining Sensor Life
The technician is able to determine when it is time to replace the
sensor before it fails. The (%) remaining sensor life is displayed
upon initiation of calibration.

Surface Mount Electronics
Allows for higher MTBF and reduces cost of purchase.

Target Gas Calibration
Allows you to set the gas detector to the specific (target) gas you
want detected, but uses only one type of calibration gas.

Easily upgrade your installed GMI Smart Sensors
Backwards compatible with our Smart Sensors (Models
S104/S106A) – no need to re-wire.
S4000C Key Features / Benefits

Magnet
A magnet is used for calibration prompts and to configure the
relays and Modbus actions. This eliminates the cost of an
expensive hand held device.

Remote Mounting & Remote Calibration
This allows for easy and fast remote calibration.

Optional Outputs
Standard 4-20 mA.
3- eight amp relays for Fault, Warn and Alarm.
Dual Modbus for redundant digital communication and reduction
of field wiring cost.
Model S4000C Intelligent Sensors

Ease of Calibration
– Single Point by One Person
– Display Prompts User
– No Adjustments, Tools or De-classification

Approvals
– CSA Certified
– FMRC Tested and Approved

Two Year Warranty
– Sensor & Electronics are covered against defects in materials and
workmanship

Fault Diagnostics
– 6 Parameters Monitored During Operation
– +3 Parameters Monitored During Calibration
– Display Codes, Relays & Analog Signal are Output
Model S4000C Intelligent Sensors
Outputs

Digital Display Codes
– 8 User Prompts
– 9 Fault Codes
– 3 User Selectable Relay Options

Analog Signal Output
–
–
–
–
–

0mA
1.5mA
1.5mA
4 to 20mA
20 to 22mA
Malfunction (optional calibration signal)
Calibration, Test Gas Mode
Relay Options Selection
0 to 100% of full scale (proportional)
Over Range (not proportional)
SPDT Relay Outputs
– Alarm, Warn & Malfunction Indications
– 8A @ 250 VAC, 8A @ 30 VDC, resistive max.
Display Units for S4000C

Model DC110
– 8 Channel Readout/Relay
Display Module with Peak
Channel Indication
– Provides Common & Discrete
Outputs for Malfunction, Warn
and Alarm
– Features:
• DIP Switch Selectable Options
• Relay Contacts for all Common
Outputs
• Open Collectors for all Discrete
Outputs
• Optional Voting for Common
Alarm Output
Display Units for S4000C

Model DC120
– Dual Channel Explosion-proof
Display Module with Dual Digital
Displays
– Provides Common Relay contacts
for Malfunction, Warn and Alarm

Model DC130
– Dual Channel Readout/Relay
Display Module with Dual Digital
Displays
– Provides Common Relay contacts
for Malfunction, Warn and Alarm
– DIP Switch Selectable Options
Accessories

Mounting Hardware
– Duct Mounting Plate (10041)
– Wall and Panel Mounted Chassis
– 2 inch, 4 inch and 19 inch
Chassis

Splash Guard
– 10395-1

Dust Guard & Dust Guard Kits
– 1800822, 10110-1 & 10044-1

Test Gas Applicator
– 10460-2 & 10535-1

Aluminum Sensor Block (for
sample draw)
– 10066

Calibration & Test Gas Equipment
– Portable Purge Calibrator
• Methane (1400150-M)
• Hydrogen (1400150-H)
• Other Gases are available
1400150-x
– 3 Liter Chamber for
calibrating to volatile liquid
vapors (1400200)