Legionella In Light of Recent Events

Drew Industrial Ashland Canada Corp

®

Legionella Bacteria

Source of Legionella

Pervasive organism

Conditions for growth

68

- 122

F (20

- 50

C)

pH 6-8

Stagnant waters

A nutrient source

 Biofilms, organics  Sediments, deposits

Factors Determining the Risk of Contracting the Disease

A source of Legionella

Favorable growth conditions

Aqueous aerosol

Sufficient organisms to cause infection

Susceptible individual

®

Systems Promoting Growth

Cooling towers

Evaporative condensers

Hot and cold water systems

Taps and showerheads

Humidifiers and air washers

Spa and whirlpool baths

Decorative fountains

®

We know that…

In order to minimize Legionella growth:

Chemical treatment alone is not effective

Minimization is dependent upon design, maintenance, contaminants, awareness and consistent implementation

Effective Legionella management requires a

“best practices”

approach: A system that is properly treated, serviced and supervised

®

Total System Approach: Five Areas of Activity and Performance

Comprehensive system assessment

Intensive microbiological treatment program

  

Sterilization and cleaning Monitoring and control Documentation

®

®

System Assessment

System survey

In-depth survey of system mechanical layout and operating conditions

Utilizes established protocol, ex BSRIA Building Services Research Institute Assoc. (UK)

Identify, evaluate and rank specific factors associated with potential for microbiological growth and Legionella

Mechanical and chemical

Determine risk minimization action plans

®

“Ideal System”

      

Water flow is continuous No dead legs or stagnant conditions Basin and deck protected from sun No evidence of sludge, debris, algae Drift eliminators installed, functioning No evidence of aerosols, drift System not near health care, aged, residential facility

     

Low number of people potentially exposed Halogen used Biodispersant/bio dispersing biocide used Comprehensive water treatment program Automated biocide and chemical dosing Continuous automated monitoring, control

®

Susceptibility to Legionnaires’ Disease

       

Age – The very young and +40 year olds Gender – Males are twice as likely to contract the disease than females Heavy Smoker Heavy Drinker Individuals with weakened immune systems – Cancer, AIDS, HIV positive Chronic Medical Problems – respiratory, diabetes, asthma, renal dialysis Certain Drug Therapies – corticosteroids or other immunosuppressive therapies Organ Transplants

®

Legionella Risk Management in Cooling Waters

Outbreak Potential is typically the cumulative effect of many high risk variables

– – – –

Population of those whom are susceptible Type of facility Susceptibility of the cooling system Microbiological control capability

– –

Monitoring and inspection frequency Documentation provides a management and control feedback loop

®

High Risk Facilities

    

Hospitals Retirement Homes Long-term and chronic care facilities Public facilities

Offices

– –

Malls Hotels Process cooling systems that have the potential for:

Aerosol spray cooling – automotive

Process contamination

CPI/HPI Food/Beverages ®

Cooling System Susceptibility

High airborne dirt load potential (utilization of side-stream filtration)

– –

Nearby construction Lack of ground coverings with aggregate materials or vegetation

High nutrient load potential

– –

Process side inleakage Tower near chemical, food or vehicle exhaust

®

Cooling System Susceptibility

Cooling tower air discharge near proximity to fresh air intakes or open windows of building, and/or outdoor population (i.e. ground level).

®

Cooling System Susceptibility

No operation or intermittent operation of equipment while wet:

– –

Drain if stagnant > 1 month Idle - rotate weekly or install 5 – 10% slip stream flow

Dead legs or seasonal cross-over lines

Remove them or

– –

Loop them with 5 – 10% slip stream flow Close shut-off valves at flowing supply and drain the remainder of the branch system and equipment

®

Effects of Cooling System Dynamics – cfu/ml Same Day Comparative Samples (Example System Treated with Continuous Oxidant and Slug Feed of Glutaraldehyde Once Per Week)

Flowing Bulk Water Basin Chip Scale Aerobic Bacteria <10 1600 Fungi <10 10 Anaerobic Bacteria <10 1,000,000 Higher Life Forms No Yes Basin Sludge Dead Head (off) Plate/Frame XER Slip Stream By-pass (10%) Plate/Frame

®

3,500,000 400 <10 20 <10 <10 1,000,000 10,000 <10 Yes Yes No

Microbiological Control Capability

  

Efficacious biocides selection Biodispersant supplement for biofilm Effective application for required concentration and contact time

– – –

System dynamics (ART, T ½ ) and volume Dedicated automated feed of microbiocides Feedback control Loop (ORP, self verifying feed pumps)

Pre-conditioning/sterilization

Preseason start-up

– – –

Idle restarts Sterilization/hyper chlorination at the summer peak End of season shutdown

®

Microbiological Control Additives of Choice

  

Oxidation

– – – –

Bleach (CSW 20) Sodium Bromide/Bleach (Drewbrom) BCDMH (Biosperse 261T) Chlorine Dioxide Non Oxidants

Glutaraldehyde 1 º (Biosperse 254/255)

Isothiazolin 2º (Biosperse 250) Biodispersants

Nonionic Surfactants (Drewsperse 739)

Protein cross linking/cationic surfactant blend (Performax 405)

Anionic surfactants (Drewsperse 7211)

®

Legionella Control with Non-Oxidizing Biocides

Chemical Compound Glutaraldehyde Isothiazolin 2 Bromo-2-Nitro Propane-1,3, diol (BNPD) Active Concentration mg/ ℓ 25 - 54 2.25 - 2.6

25 400 Contact Time 1 Hour 6 Hours 24 Hours 60 Minutes Dithiocarbamates Di-bromo-nitrilo-propionamide (DBNPA) 40.0 - 60.0

4 - 8 6 Hours 2 Hours Note: System potential contaminants and operational pH must be checked for compatibility with the non-oxidizing biocide

®

Continuous Oxidant Feed Protocol

Continuous feed for chlorine, bromine, BCDMH or stabilized bromine

Dosage:

Recommended 0.2 - 0.4 FAH and/or equivalent mV ORP with a minimum requirement of a measurable residual FAH

For higher risk systems increase FAH residual as needed to control CFU level and biofilm

Feed a supplemental organic biocide *

Recommend biocide be glutaraldehyde or an alternate biocide fed with biodispersant

Feed once per week or as needed to control biofilm

® *

Alternative choices of non-oxidizing biocide should be based on Relative Population Density (RPD) lab results

Intermittent Oxidant Feed Protocol

Intermittent Oxidant Feed

– –

Chlorine, bromine, BCDMH or stabilized bromine Minimum dosage: Hold 0.5 - 1.0 FAH and/or equivalent mV ORP for a minimum of 2 hours each day

Feed alternating supplemental organic biocides *

Recommend one biocide be glutaraldehyde or an alternate biocide fed with biodispersant

– –

Feed an additional compatible organic biocide* Alternate feed once per week

*

Alternative choices of non-oxidizing biocide should be based on RPD results

®

®

Chlorine Dioxide A Selective Oxidant

Oxidation potential not affected by pH

Selective oxidant

No dissociation; does not react with water

Does not react with amines, nitrogen compounds

Highly effective against biofilm

Continuous Chlorine Dioxide Feed Protocol

Continuous chlorine dioxide feed

Minimum dosage: 0.1 ppm residual ClO 2 equivalent mV ORP or

Feed a supplemental organic biocide as needed based on biofilm control

Recommend biocide is glutaraldehyde or an alternate biocide fed with biodispersant *

Feed once per week or as needed to control biofilm

*

Alternative choices of non-oxidizing biocide should be based on RPD results

®

Intermittent Chlorine Dioxide Feed Protocol

Intermittent chlorine dioxide feed

Minimum dosage: 0.5 ppm residual ClO 2 and/or equivalent mV ORP for a minimum of 2 hours per day

Feed alternating supplemental organic biocides *

Recommend one biocide be glutaraldehyde or an alternate biocide fed with biodispersant

– –

Feed an additional compatible organic biocide Alternate feed once per week *

Chlorine dioxide is also an effective supplemental biocide for process cooling systems where contaminants that increase bacterial growth are present.

® *

Alternative choices of non-oxidizing biocide should be based on RPD results

Dual Non-Oxidizer Feed Protocol

Slug feed of non-oxidizer

– –

Alternately twice per week, evenly spaced Timer/Pump (self verifying optional) automated feed is preferred over manual

Oxidant feed once per week

Minimum dosage to hold 1 – 2 ppm FAH for 2 hours. Based upon system demand this may require the feed of 5 to 10 ppm active oxidant

Dosing a day prior to a nonoxidizer addition is the preferred method.

®

Preconditioning and Sterilization

Frequency

Minimum once per year for season equipment operation

• End of season preferred –

Minimum twice per year for year round system operation

• During turn around on process systems and 6 months later • Beginning and end of cooling season –

Confirmed Out Break

®

Preconditioning and Sterilization

Procedure

Ensure all air intakes and windows within at least 100 feet of the tower are closed

• •

Open all cross over lines Ensure complete recirculation of the total system and all equipment

• •

Turn fans off and activate stand-by pump Blowdown flush all strainers, risers, water boxes and dead legs.

®

Preconditioning and Sterilization

Procedure Cont’d

Add biodispersant (200 ppm) and non-oxidizer recirculate for 24 hours (120 – 360 ppm)

• •

Blowdown/flush etc.

Add oxidant to produce 5 ppm FAH (due to system demand, dosage may be 15 to 25 ppm – 1.5 to 2.5 lbs. 10% bleach/1,000 gal) test verify 5 ppm at end of 6 hours

Drain system blowdown/flush etc.

®

Preconditioning and Sterilization

Procedure Cont’d

• •

Water Wash/Hose out Tower

-

Upper deck Drift eliminators Fill Sumps and companion indoor sumps and storage tanks through to pump strainer If high pressure water jetting is employed then ensure suitable respiratory protective equipment is worn.

®

Preconditioning and Sterilization

Procedure – Cont’d

• •

Leave drained for seasonal outage If wet storage is employed, refill with inline blend of protecsol and 300 – 400 ppm of 1.5 % Isothiazolin non-oxidizer.

Immediate placement into service

Refill Start pumps Slug feed corrosion and deposit control compounds and non-oxidizer (i.e. prime the system volume) ®

Sterilization Only

Frequency

During restart of idle/stagnant towers, condensers, heat exchangers

Seasonal restart of HVAC system, which was preconditioned and sterilized the end of the previous season

Peak of summer cooling demand

– – (i.e. beginning of August).

Known outbreaks in the area Biological dip slide counts exceed 10 5 – 10 6 CFU/ml. Visible slime (i.e. biofilm) present.

®

Sterilization Only

Procedure

Deconcentrate via bleed-off and blowdown of dead legs, risers, water boxes, and strainers to achieve 2 cycles of concentration. Close bleed

• •

Fans off Add oxidant to produce 5 ppm FAH (Due to system demand, dosage may be 15 to 25 ppm – 1.5 to 2.5 lbs/10% bleach/1,000 gal). Test hourly to verify 5 ppm held for 6 hours

• • •

Blowdown dead legs, risers water boxes and strainers Resume treatment program cycles of concentration Add Non-oxidizing Biocide

®

®

Monitoring and Inspection

Inspection for visible slime or sludge's

Decks

Mist eliminators

Fill

Sumps

Corrosion or biofilm coupons

Monitoring and Inspection

Testing

Bulk water dip slides

• Prior to non-oxidizing biocide addition Minimum once per week Target ≤ 10 4 CFU/ml

Coupon surfaces - if available

Prior to non-oxidizer and/or biodispersant addition Every 30 to 60 days, but be consistent Target ≤10 5 CFU/cm 2 ®

Direct Testing of Legionella

Frequency Consideration

Prior to peak summer sterilization (i.e. beginning/mid August) for seasonally operated HVAC or after a sterilization.

After cleaning of a confirmed cooling tower sourced outbreak

If a confirmed outbreak has occurred in the area ( ≤3 km minimum)

Three times per year of 24/7 Industrial process cooling systems of higher risk noted earlier

®

Legionella Testing – Pathcon/Biosans

Ship via air direct

7 days to culture

If positive, species and type is determined, requiring additional time

E-mail results within 2 days after the 10 th day after receipt by lab

®

OSHA/Wisconsin Protocol

Confirmed Cooling Tower Source of Outbreak 1.

2.

3.

4.

5.

6.

Turn off tower fans Shock dose chlorine donor to 50 ppm FAC Add Biodispersant Hold 10 ppm FAC for 24 hours Drain cooling system and repeat steps 2 - 4 Inspect for biofilms. If present, drain and mechanically clean.

®

OHSA/Wisconsin Protocol

7.

8.

9.

Refill system and operate for 1 hour at 10 ppm FAC Flush system Recharge system with water treatment additives for deposit, corrosion and biological control and return to service Note test monthly:

 Legionella ≤10 CFU/ml  HPC ≤105 CFU/ml ®

Field Study on Biofilm Growth

Phase Colonization Growth Detection Biofilm Formation (Exopolymer/ Minimum Biofouling) Maximum Biofilm Growth (8 – 10 Cells Thick) Fully Mature Biofilm Matrix Time 15 Minutes 2 Days 5 Days 14 Days 31 – 40 Days

®

Documentation

Why Document?

When a pneumonia outbreak occurs in a facility it allows for:

Speed in identifying the source for eradication purposes, removing a potential and continual threat. After all it may not be cooling system derived.

Clinical micro biologists and physicians to select appropriate antibiotics, dosages and monitor the progress without the presence of further stressors.

®

Documentation

To name a few:

Simplified line drawing of the cooling system and all equipment, dead legs cross over lines, chemical feed points/lines/control, system volume, recirculation make up and blowdown rates

Key water test results/date

Chlorides or conductivity for cycles of concentration assessment Make-up, blowdown water meter readings FAH and/or ORP for Halogen concentration Biological Tests – CFU/ml; CFU/cm2 Start, end and expiry dates of dip slide lots for bio testing ®

Documentation

To name a few:

• • •

Chemical pump and timer settings Biocide usage Start-up/shutdown and other application logs of preconditioning/sterilization and sterilization only

Inspection/observations for slimes, muds, algae in cooling tower and on coupons and what was done to improve

Contingency plans procedures, and results/check offs when performed.

®

Use of Proper Monitoring & Control Equipment is Critical!

Microbiological Residuals, Corrosion, Scale & Biofouling On-line

®

Action Levels

Immediate response to positive test results

On-line treatment requires a minimum of 14 days to produce results

Unrealistic a system could be totally Legionella free

®

Preventive Actions

Legionella is as Common as “Dirt”

Keep Systems Mechanically and Microbially Clean

Minimize or Rotate Idle Equipment

Employ Filtration and Keep Filter Media Clean

Mist Eliminators Clean and Functioning Properly

®

Preventive Actions

Inspect and Test

– – – – –

Domestic Waters Fountains Spas Air Handling Units Humidifying/Dehumidifying Equipment/Coils

®

Biofilms

 

Biofilms Don’t Just Harbour Legionella, They:

– – – – –

Restrict Air Flow Restrict Water Flow Reduce Heat Transfer Reduce Heat Rejection Induce Localized Corrosion Biological Control

– – –

Higher Life Forms – None Bacteria CFU/ml <10 4 , > 10 5 Do something Bacteria CFU/cm 2 <10 5 , >10 6 Do something

®

Preventive Action

Use your Biocides in a Prudent Manner And Remember

Sterility Does Not Exist Except in Higher Life Forms

®

Additional Information Upon Request

    

Legionella: Minimizing Risks, August 2000, Water Engineering and Management Environmental Aspects of Legionnaires’ Disease, February 1988, Journal AWWA Legionella Treatment Strategies: First Response and Minimization Action Plan, 2002 International Water Conference Paper 02-12 Who Should Be Responsible for Legionella, ASHRAE Journal May 1999, Volume 41, No. 5, 62-68, ref. ISSN-0001 2491 Why Evaporative Coolers Have Not Caused Legionnaires’ Disease, ASHRAE Journal, January 1995, page 29-33

®

Additional Information Upon Request

Legionellosis, Guideline: Best Practices for Control of Legionella, February 2000, Cooling Technology Institute

Minimizing Risk of Legionellosis Associated with Building Water Systems, February 2000, ASHRAE Standard 12-2000 (ISSN 1041-2336)

®

®

What Can You Anticipate

Expert group review of design and maintenance of cooling towers in long term care homes, hospitals and other facilities housing people with complex health needs.

What Can You Anticipate

Review of other existing HVAC/Legionella standards and development/adoption of a standard for use;

ASHRAE Guideline 12-2000 “Minimizing the risk of Legionellosis associated with building water systems”

Cooling technology institute February 2000 Guidelines – “Legionellosis guideline: “Best Practices for control of Legionella”

Health and Safety Commission, U.K., approved code of practice and guidance – L8, “Legionnaires” disease, the control of Legionella bacteria in water systems”

The chartered institution of Building Services Engineers, U.K. TM 13 2000, “Minimizing the risk of Legionnaires’ disease”

®

Walker Report

http://www.health.gov.on.ca/english/public/pub /ministry_reports/walker_legion/rep_intro ...

Report of the expert panel on the Legionnaires” disease outbreak in the city of Toronto – September/October 2005, December 2005.

®

Industrial Hygienists

Employ Certified Industrial Hygienists

Employ HVAC Engineers

Can fully evaluate potable cold and hot Domestic Water systems

Can calculate cooling tower plume relationships and re-entrainment of plume into air intakes or windows

Can assess air handling systems

®

Industrial Hygienists

A firm such as:

– –

Stantec Consulting Resource Environmental Associates

Complete air quality, risk assessments on all aspects of exposure to Legionella and other environmental conditions such as molds and asbestos

Firms may also have a division that does complete sterilizations of systems – hot and cold domestic, air handling, etc.

®

Ashland

Ashland is capable of a cursory review of cooling systems to assist a customer in targeting certain areas, as related to:

System Cleanliness

Microbiocide addition – whether oxidizing or non oxidizing biocide.

Capable of applying chemicals to meet the protocols – continuous chlorination, shock feeding

Mechanical/operational conditions that can lead to high risk

– –

Assist in providing documentation tools Can provide routine microbiological testing and has a sample protocol and a lab arrangement to test for Legionella

®

Thank You

®