Zelezna Ruda, 25.05.2010

Download Report

Transcript Zelezna Ruda, 25.05.2010

TECHNICAL UNIVERSITY OF KOŠICE FACULTY OF ELECTRIC ENGINEERING AND INFORMATICS Department of Electric Power Engineering

E T H N I C K Á U N I V E R Z

FE I

K O Š I C E A

Modeling of Reconnection of Decentralized Power Energy Sources Using EMTP ATP

Ing. Dušan MEDVEĎ, PhD.

Železná Ruda-Špičák, 25. May 2010

Contents

• Theoretical problems of reconnection of decentralized electric sources in power system • Choosing of suitable model of power system for reconnection of decentralized sources • Simulations of chosen electric sources in power system model in EMTP-ATP • Conclusion

Problems of Reconnection of Decentralized Power Energy Sources to Distribution Grid Problems of reconnections of wind power plant:

• convention sources must be „on“ and prepared, in the case of wind power plants outage; • dependence on actual meteorological situation; • relatively small power of wind power plants; • they are not possible to operate when the wind velocity is above 30 m/s or below 3 m/s.

Problems of reconnections of solar power plants:

• convention sources must be „on“ and prepared, in the case of solar power plants outage; • problems with the season variations of sunlight (in December is 7-times weaker than in July); • difference between night and day is very significant

Problems of reconnections of water power plants:

• they generate electric power only when the water flow is in allowable range;

Review of present possibilities of computer simulation of power system at our department

• MATLAB/SIMULINK • EUROSTAG • PSLF • EMTP-ATP • ...

EMTP ATP (Electromagnetic Transient Program)

• • • • • • • • Generally, there is possible to model the power system network of 250 nodes, 300 linear branches, 40 switchers, 50 sources, ...

Circuits can be assembled from various electric component of power system: Components with the lumped parameters R,L,C; Components with the mutual coupling (transformers, overhead lines, ...); Morephase transmission lines with lumped or distributed parameters, that can be frequency-dependent; Nonlinear components R, L, C; Switchers with variable switching conditions, that are determined for simulation of protection relays, spark gaps, diodes, thyristors and other changes of net connection; Voltage and current sources of various frequencies. Besides of standard mathematical functions, there is possible to define also sources as function of time;

EMTP ATP (Electromagnetic Transient Program)

• • • • • • • • Model of three-phase synchronous engine with rotor, exciting winding, damping winding; Models of universal motor for simulation of three-phase induction motor, one-phase alternating motor and direct current motor; Components of controlling system and sense points.

This program EMTP ATP is not only computational. Because of better representation of results and simplifying of inputting data, this program has spread with another sub programs as follows:

ATPDraw

– graphical preprocessor;

PCPLot , PlotXY, GTPPLot

– graphical exporting of ATP;

Programmer‘s File Editor (PFE)

– text editor for creating and editing of output files;

ATP Control Center

– program that concentrate all controlling sub-programs into one general controlling window.

Scheme of electric power network for simulations

Scheme of electric power network for simulations in EMTP-ATP

Parameters of power system

• Parameters setting of sources of power system

Parameters of power system

• Parameters setting of overhead lines of power system

Parameters of power system

• Parameters setting of transformers of power system

Sources reconnection

• There were reconnected various sources in different locations of power system • First source was connected from the beginning of simulation, the second one was connected in 0,5 s and the third one in 1 s • All parameters of components in power system were inserted as card data of given components • Consequently, there were changed voltages and powers of connected sources • The measured data (voltages, currents, ...) were recorded and evaluated in various nodes of network • The maximal possible connected power were calculated and tested with permitted difference of voltages (quality of voltages must agree with conditions of ± 2 % from nominal voltage in grid) • The result were evaluated for phase L1 (A), because the loads were almost symmetrical

Sources reconnection

Simulation of reconnection of two sources with the same values and the maximal voltage of 326 V

Sources reconnection

Voltage arising with sequential sources reconnecting

Sources reconnection

Simulation of reconnection of two sources with the same values and the maximal voltage of 400 V

Sources reconnection

Voltage deviation in the node, closest to third source

Sources reconnection

Voltage deviation in the node, closest to the third source (detail)

Sources reconnection

Simulation of reconnection of two sources with the same values and the maximal voltage of 385 V

Sources reconnection

Simulation of reconnection of two sources with the various parameters and the maximal voltage of 391 V (2nd source) and 333 V (3rd source)

Sources reconnection

Power of first source, when it operates alone (0-0,5 s), with the second one (0,5-1 s) and consequently with third one (1-2 s)

Sources reconnection

Power of second source, when it operates with first one (0-0,5 s), and with the third one (1-2 s)

Sources reconnection

Power of third source, when it operates with first and third one (1-2 s)

Sources reconnection

Maximal voltages, that are possible to reach with the respecting of ± 2 % voltage variation in every node: Source 1:

U

m1 Source 2:

U

m2 Source 3:

U

m3 = 89815 V = 391 V = 333 V Maximal immediate power measured in the closest distances from the sources: Power of source 1 (single) =

2,2643 MW

Power of sources 1 + 2 =

3,5280 MW

= 2,2541 MW + 1,2739 MW Power of sources 1 + 2 + 3 =

3,5653 MW

= 2,1458 MW + 1,2621 MW + 0,1574 MW

Simulations of transient phenomena

Complemented scheme for simulation of transient phenomena M1,M2,M3 – places of failure event; measuring places

U1

110kV BCT Y

V

TR0

22 kV I

00

M1

AAO

V

LCC

0 AA

LCC

AB

LCC

AC

LCC

TR2

Y BCT

V

2 AD

LCC 1.002 km

TR1

Y BCT

V

1 I AE

LCC

ADA

LCC

TR5

Y BCT

V

5 AEA

LCC

TR4

Y BCT

V

4

M2 V

01

I Y BCT

V

3 TR3

Simulated transient phenomena:

• short-circuits • load (branch) disconnection • phase interruption • atmospheric overvoltage

AF

LCC

AFA

LCC

AG

LCC

AGA

LCC

AFB

LCC

AH

LCC Y BCT

V

11 TR11

BCT

V

12

Y

TR12

Y BCT

V

13 TR13

Y BCT

V

15 AI

LCC

AJ

LCC Y BCT

V

14 AFC

LCC Y BCT

V

7 TR14 AFD

LCC Y BCT

V

10 TR10

BCT Y

TR8

Y BCT

V

8 TR9

V

9 TR15 AK

LCC

V

0k

M3

BCT

V

17

Y

TRnz TR16

Y BCT

V

16

Y BCT

V

6 TR7 TR6

Three-phase short circuit – overvoltage after short circuit elimination

Voltage characteristics before short-circuit creation in location M1, during short circuit and after short circuit, measured in location M1 22 -12 90 [kV] 56 -46 -80 0,040 0,062 (file 3fskrat_M1.pl4; x-var t) v:X0080A v:X0080B v:X0080C 0,084 0,106 0,128 [s] 0,150

Three-phase short circuit – measured results

Measured place Location M1 Mutual distances [km] M1 M2 M3 Measured place 0 4,110 8,121 Location M2 Mutual distances [km] M1 M2 M3 Measured place -4,110 0 4,011 Location M3 Mutual distances [km] M1 M2 M3 7,466 4,011 0 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Overvoltage after shot-ciruit interuption

U

[V] 88722 69337 71948 Overvoltage after shot-ciruit interuption

U

[V] 178560 182420 172670 Overvoltage after shot-ciruit interuption

U

[V] 45529 48449 57918 Peak current during short-circuit

i

p 6533,5 203,5 36,453 Peak current during short-circuit

i

p 3813,5 3840,9 36,373 Peak current during short-circuit

i

p [A] 2453,3 2432,2 2402,8

Two-phase short circuit – overvoltage after short circuit elimination

Voltage characteristics before short-circuit creation in location M1, during short circuit and after short circuit, measured in location M1 90 [kV] 60 30 0 -30 -60 -90 0,040 0,062 0,084 0,106 (f ile 2f skrat_M1.pl4; x-v ar t) v :X0080A v :X0080B v :X0080C 0,128 [s] 0,150

Two-phase short circuit – measured results

Measured place Location M1 Mutual distances [km] M1 M2 M3 Measured place 0 4,110 8,121 Location M2 Mutual distances [km] M1 M2 M3 Measured place -4,110 0 4,011 Location M3 Mutual distances [km] M1 M2 M3 7,466 4,011 0 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Overvoltage after shot-ciruit interuption

U

[V] 86268 71133 69032 Overvoltage after shot-ciruit interuption

U

[V] 167630 178690 163660 Overvoltage after shot-ciruit interuption

U

[V] 69409 67746 98249 Peak current during short-circuit

i

p 3122,3 197,08 36,822 Peak current during short-circuit

i

p 2536,6 2697,5 36,975 Peak current during short-circuit

i

p 1881,2 1854 1938

One-phase short circuit – overvoltage after short circuit elimination

Voltage characteristics before short-circuit creation in location M1, during short circuit and after short circuit, measured in location M1 80 [kV] 50 20 -10 -40 -70 0,040 0,062 0,084 0,106 (f ile 1f skrat_M1.pl4; x-v ar t) v :X0081A v :X0081B v :X0081C 0,128 [s] 0,150

One-phase short circuit – measured results

Measured place Location M1 Mutual distances [km] M1 M2 M3 Measured place 0 4,110 8,121 Location M2 Mutual distances [km] M1 M2 M3 Measured place -4,110 0 4,011 Location M3 Mutual distances [km] M1 M2 M3 7,466 4,011 0 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Steady state

U

[V] 17309 16969 16701 Overvoltage after shot-ciruit interuption

U

[V] 78221 47897 55168 Overvoltage after shot-ciruit interuption

U

[V] 129130 147370 144980 Overvoltage after shot-ciruit interuption

U

[V] 55513 59507 91992 Peak current during short-circuit

i

p 5100,5 157,81 36,45 Peak current during short-circuit

i

p 2607,7 2711,3 36,43 Peak current during short-circuit

i

p 1672,5 1641,2 1676,2

Phase interruption

Voltage characteristics during phase interruption in location M1, measured in location M2 20 [kV] 15 10 -5 -10 5 0 -15 -20 0,09 0,10 (file M1.pl4; x-var t) v:M2A v:M2B v:M2C 0,11 0,12 0,13 0,14 [s] 0,15

Phase interruption

Voltage characteristics during phase interruption in location M1, measured in location M3 20 [kV] 15 10 5 0 -5 -10 -15 -20 0,09 0,10 0,11 (f ile M1.pl4; x-v ar t) v :P17A v :P17B v :P17C 0,12 0,13 0,14 [s] 0,15

Load disconnection

Voltage characteristics after disconnection of branch AFA, measured in location M1 20 [kV] 15 10 5 0 -5 -10 -15 -20 0,09 0,10 0,11 (f ile AFA.pl4; x-v ar t) v :X0080A v :X0080B v :X0080C 0,12 0,13 [s] 0,14

Load disconnection

Current characteristics after disconnection of branch AFA, measured in location M1 200 [A] 150 100 50 0 -50 -100 -150 -200 0,09 0,10 0,11 0,12 (f ile AFA.pl4; x-v ar t) c:X0080A-M1A c:X0080B-M1B c:X0080C-M1C 0,13 [s] 0,14

Atmospheric overvoltage

During the direct lightning strike to overhead line pole (HV), it is considered line impedance

Z

0 =300-500 Ω and lightning current of

I

20 kA, then the theoretical peak voltage magnitude of overvoltage = wave is in the range 3-5 MV. H H

Atmospheric overvoltage

Simulation of direct lightning strike to bus bar 22kV in location M1 6 [MV] 4 2 0 -2 -4 -6 0,00 0,03 0,06 (f ile M1.pl4; x-v ar t) v :X0002A v :X0002B v :X0002C 0,09 0,12 [s] 0,15

Atmospheric overvoltage – measured results

Measured place M1 M2 M3 M1 M2 M3 M1 M2 M3 Location of failure M1 Mutual distances [km] 0 4,110 8,121 Location of failure M2 -4,110 0 4,011 Location of failure M3 7,466 4,011 0 Steady state

U

[V] 17309 16969 16701 17309 16969 16701 17309 16969 16701 Overvoltage

U

[MV] 5,304 4,96 2,83 2,65 4,01 4,28 5,28 6,23 10,43

Conclusion

using of EMTP-ATP it is possible to relatively quickly consider connectivity of new power source (voltage change, short-circuit ratio,

overvoltage, ...); there were confirmed theoretical assumptions that the most important points with the highest quantity change are the closest branches to connection node, i.e.: - the highest increasing of voltage magnitude is in the node of source connection, - the highest increasing of short-circuit current is in the node of source

connection, if there were connected 3 sources, the voltage in the power system was increased to permitted maximum voltage, and then it is possible to

connect another load to the grid without significant complications, the similar procedure can be used for various small power systems

Thank you for your attention