Network Solutions www.mcscontrols.com Rev-H-02-12-15 Presentation Overview Network Hardware Types Network Protocols Network Adapters MCS-Magnum Communication MicroMag Communication Example Network Configurations Network Hardware Types Four network hardware types that are used in MCS products: RS485 RS232 Ethernet LonWorks (twisted pair) RS485 Hardware One twisted pair (two conductors) Shielded wire – wrapped foil with drain wire Minimum AWG 20 Max baud rate: 115,000 bit/s Multidrop – point to point Max 30 MCS Controllers wired together Total Network cable length < 4000’ (1219m) Can be lengthened with a repeater Supported Data Format Start bit: 1 bit Data bits: 8 bits Parity: None Stop bits: 1 bit RS232 Hardware One to one Three conductor 9 or 25 pin connecter Max total cable length < 50’ (15m) Can be lengthened with a repeater Supported Data Format Start bit: 1 bit Data bits: 8 bits Parity: None Stop bit: 1 bit Ethernet Hardware Star topography 4 twisted pairs (8 conductors) CAT5E Max baud rate: 10 Mbit/s Max cable length < 328’ (100m) Can be lengthened with a switch LonWorks Hardware One twisted pair (two conductors) Shielded wire Free topography Minimum AWG 20 Total Network cable length < 3280’ (1000m) Can be lengthened with a repeater Network Protocols Network protocols are formatting rules that specify how data is sent and received between devices. Protocols are necessary for devices to interact with each other Protocols MCS controllers support: Bacnet Modbus LonTalk Johnson N2 MCS Network Protocols The MCS Controllers support the following network protocols: Over Ethernet Over RS485 Over LonWorks MCS Network Adaptors MCS uses five different optional network adapters: Hardware Adapters MCS-485-Gateway (RS232 - RS485) MCS-Ethernet (Ethernet - RS232) MCS-USB-RS232 (USB - RS232) Hardware & Protocol Adapters MCS-BMS-Gateway (Bacnet MSTP, LonTalk, Johnson N2) MCS-Bacnet-Router2 (Bacnet IP) MCS-485-Gateway Converts between RS485 and RS232 Used with the MicroMag for a connection to: PC (MCS-Connect) MCS-Touch (MCSConnect) MCS-Ethernet Can be powered from MCS Controller Only hardware conversion, does not change protocol MCS-Ethernet Converts between Ethernet and RS232 Used with the MicroMag for Ethernet connection to: Internet Comes with 120V wall outlet power adapter Only hardware conversion, does not change protocol MCS-USB-RS232 Converts between USB and RS232 Used for PC (MCS-Connect) communication Powered through USB port Only hardware conversion, does not change protocol MCS-BMS-Gateway Converts Bacnet MSTP (RS485) to: LonTalk (LonWorks) Johnson N2 (RS485) Converts Bacnet IP (Ethernet) to: LonTalk (LonWorks) Johnson N2 (RS485) Bacnet MSTP (RS485) Only supports one MCS-Magnum or MicroMag Can be powered from MCS Controller MCS-Magnum MicroMag Ethernet Bacnet IP RS485 Bacnet MSTP MCS-BMS-Gateway MCS-BMS-Gateway Or RS485 • Johnson N2 • Bacnet MSTP LonWorks • LonTalk Or RS485 • Johnson N2 LonWorks • LonTalk MCS-Bacnet-Router2 Converts Bacnet MSTP (RS485) to Bacnet IP (Ethernet) Supports up to 30 MicroMag Can be powered from MicroMag MicroMag RS485 Bacnet MSTP MCS-Bacnet-Router2 Ethernet • Bacnet IP MCS-Pocket Router-2 The MCS-POCKET ROUTER-2 is the perfect travel companion for anyone who needs fast, easy wireless internet access on the go. Designed with a portable form factor that easily fits into a pocket, a laptop case, or the palm of your hand The MCS-POCKET ROUTER-2, 2.4GHz wireless technology allows 11n data transfer rates of up to 150Mbps while still remaining compatible with older 11b/g devices. Powered by USB for extreme portability The MCS-POCKET ROUTER-2 can be USBpowered to ensure convenient internet access anywhere Kit Components 110# power cord USB cable to MCS-POCKET ROUTER-2 Easy Setup MCS-POCKET ROUTER-2 ships with a different default SSID and encryption enabled by default. Check the bottom of the Pocket Router-2 for the security key used by your router, or change it to one of your own choosing. Advanced Security Features To provide the highest data security possible, the MCS-POCKET ROUTER-2 supports WEP, WPA, and WPA2 encryption. It also comes equipped with firewall features like NAT (Network Address Translation), VPN pass-through, and SPI (Stateful Packet Inspection) to prevent attacks from the internet. MCS-WIRELESS-3G Broadband Router with Integrated Verizon 3G Modem (Only for use in USA) The MCS-WIRELESS-3G is built for your network. It’s a highly-featured, compact router designed for critical industrial applications that require 24x7 connectivity. The router features a built-in high-speed Verizon 3G EVDO modem. Supplied with one year subscription to MCS Wireless Verizon Data Plan, 250MB per month. The MCS-WIRELESS-3G is a powerful tool that is especially useful in locations where there is no readily available internet connection. Combined with the data plan, the MCS-WIRELESS-3G may be used to wirelessly connect to the MCS-MAGNUM wherever a cellular signal is found. You will receive everything you need to setup communication with an MCS Controller, one year Verizon 250MB per month data plan and a crossover Ethernet cable to link the MCS-WIRELESS3G to the MCS Controller board. MCS also offers an MCS-WIRELESS-ROUTER-No Modem, for users who like the idea of wireless connection but want to supply their own Broadband Modem and Data Plan. NOTE: The MCS-WIRELESS-3G can be used to communicate with multiple MSC Controllers. Email: [email protected] for more information. MCS-Magnum Communication The MCS-Magnum comes with two hardware communication ports: RS485 Port Ethernet Port MCS-Magnum Communication The MCS-MAGNUM-DOOR-NEMA4 Keypad has been sealed in its own frame using a new Gasket (BISCO HT-800 Medium Cellular Silicone). The RS485 port has been added to the back of the Keypad. Moving the communicating port to the back, adding the new gasket, provides the unit with a NEMA4 rating. Operating Temperature -4°F to +158°F (-20°C to +70°C) Keypad showing New design, adding RS-485 connection New Gasket Provides the unit with a NEMA4 rating RS485 port on the MCS-Magnum MCS –USB-RS485 The MCS-USB-RS485 cable is a USB to RS485 levels serial that provides a fast, simple way to connect to MCS controllers, such as the and the MCS-MICROMAG. The MCS-USB-RS485 cable contains a small internal electronic circuit board, utilizing the FT232R, which is encapsulated into the USB connector end of the cable. Each cable supports the FTDIChip-ID™ and is equipped with a unique USB serial number programmed into the FT232R. MCS-USB-RS485 PC (MCS-Connect) MCS-MAGNUM MCS-Magnum RS485 Using the RS485, the MCS-Magnum can be connected to the BMS (Modbus RTU or MCS 485) Building Management System .. . RS485 The RS232 cannot be used with different protocols when the RS485 is used Wiring Multiple MCS Controllers Using the RS485, the network must be wired controller to controller Star configurations not allowed Up to 30 controllers can be wired together Correct Incorrect .. . MCS-Magnum Ethernet Using the Ethernet, the MCS-Magnum can be connected to: BMS (Bacnet IP or Modbus IP) MCS-Touch (MCS-Connect) PC (MCS-Connect) Internet access through router (which allows connection via MCS-Connect from anywhere) Or Or Or Ethernet MicroMag Communication The MicroMag comes standard with two independent ports: RS485 Port RS232 Port Ethernet access can be added with the MCS-Ethernet MicroMag RS232 The MicroMag RS232 serial port only supports MCS protocol. It can be used to connect to: MCS-Touch (MCS-Connect) PC (MCS-Connect) The PC may require USB to RS232 adapter, MCS Part # (MCS-USB-RS232) MCS-Touch MCS-PC9-MM cable MCS-USB-RS232 Or PC (MCS-Connect) MicroMag RS485 The MicroMag RS485 port can be used to connect: MCS-Touch (MCS-Connect) BMS (Bacnet MSTP or Modbus RTU or MCS 485) RS485 .. . Or Building Management System MCS-Touch MicroMag RS485 The MicroMag RS485 port can be used to connect: MCS-Touch (MCS-Connect) BMS (Bacnet MSTP or Modbus RTU or MCS 485) Internet Access using: MCS-485-GATEWAY and the MCS-Ethernet RS485 .. . Ethernet RS232 9pin 25pin MCS-485-GATEWAY Internet Router MCS-ETHERNET Example Network #1 Standalone MCS-Magnum MCS-Touch Ethernet Ethernet MCS-Touch Example Network #2 Standalone MCS-Magnum MCS-Touch BMS (Johnson N2 or LonTalk or Bacnet MSTP) Internet Access RS485 or LonWorks Building Management System MCS-BMS-Gateway Internet Router Ethernet MCS-Touch Example Network #3 Multiple MCS-Magnum Enclosures Internet Access BMS (Bacnet IP or Modbus IP) Rooftop/Chiller #1 Rooftop/Chiller #2 Ethernet Building Management System Internet Router Example Network #4 Standalone MicroMag MCS-Touch BMS (Modbus RTU or Bacnet MS/TP) MCS-PC9-MM cable RS485 MCS-485-Gateway MCS-Touch RS485 Building Management System Example Network #5 Multiple MicroMags BMS (Bacnet MSTP or Modbus RTU or MCS 485) MCS-Touch RS485 MCS-Touch RS485 Building Management System Advanced Example Network Multiple MCS-Magnum & Multiple MicroMag MCS-Touch BMS (Bacnet IP) MCS-Touch Building Management System MCS-ETHERNET-SWITCH MCS-Bacnet-Router2 For additional information please visit our website www.mcscontrols.com Or call MCS at 239-694-0089 5580 Enterprise Pkwy. Fort Myers, FL 33905 Office: 239-694-0089 Fax: 239-694-0031 www.mcscontrols.com