SIPROTEC 4
7SA522
Distance Protection
for Transmission Lines
Productmanager Distance Protection
Michael Claus
EV S V 13 Nürnberg H
Phone: +49 911 433 8261
Fax: +49 911 433 8301
Email: [email protected]
7SA522
Distance Protection for Transmission Lines
Distance protection
Info - 3
EV S V13/ Claus/ 21.08.00
SIPROTEC 7SA522
Front design
Navigation Keys
convenient menu
operation
4-line back-lit display
Measured values
Fault data
4 freely assignable
function keys with slot
for legend text
Turning ON/OFF of
functions
Control of switchgear
(plant)
14 LED´s for user
assignment and slot
to insert legend text
9-pole
service interface
standard cable
DIGSI 4
Distance protection
Proven numeric keypad
secure entry of numbers
easy password entry
Width of housing
1/2 of 19" or 1full 19“ rack
Info - 4
EV S V13/ Claus/ 21.08.00
SIPROTEC 7SA522
Terminals and Communication Interfaces
Width of housing
1/2 of 19" or full 19"
Binary inputs 8 (16*, 24*)
Output contacts 16 (24*,32*)
(*in full 19“ rack housing)
Open to new techniques
(methods)
electric or fibre optic (FO)
process or 2nd remote relay
interface
Remote relay interface (plan)
electric or fibre optic (FO)
for protection signalling
System interface
electric or fibre optic
IEC60870-5-103 or Profibus
4 Current Transformers (CT)
FMS (approx. 12/00)
option with
in future DNP3.0, MODBUS
Ienormal or Iesensitive
and Profibus DP
Service interface
Time synchronization
electrical or fibre optic (FO) GPS
DIGSI 4 via Modem
with IRIG-B and DCF-77
4 Voltage Transformers (VT)
Distance protection
Info - 5
EV S V13/ Claus/ 21.08.00
7SA522
Connection Diagram: Basic Version
Optional
Sensitivity:
• normal
• high (5mA)
Connection:
• Ven
• Vsync
• Vx
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
R15
R16
R17
IL1
IL2
IL3
I4
VL1
VL2
R18
VL3
R13
R14
V4
K5
K6
K7
K8
K9
K10
K11
K12
K13
K14
K15
K16
Fast BO1
Fast BO2
Fast BO3
Fast BO4
Fast BO5
Fast BO6
Fast BO7
BO8
BO9
BO10
BO11
R1
R2
R3
R4
R5
R6
R7
R8
R9
R10
R11
R12
BO12
K17
K18
J1
J2
J3
BO 14
BI 1
BI 2
BI 3
J4
J5
J6
BI 4
J7
J8
J9
J10
J11
J12
BI 6
Distance protection
BO 13
BO 15
Live status contact
NC or NO with Jumper
K3
K4
BI 5
=
=
(~)
BI 7
BI 8
Serial
Interfaces
+
-
K1
K2
Remote Relay
Interface #2
E
Remote Relay
Interface #1
D
Service Port
DIGSI, Modem
C
System/Scada
B
Front Port
IRIG-B
Version
Width
A
No. of No. of
Binary Output
Inputs Relays
Basic
½ x 19“
8
16
Medium 1/1 x 19“
16
24
Maximum 1/1 x 19“
24
32
Info - 6
EV S V13/ Claus/ 21.08.00
7SA522
Single Line Diagram
D i r e c t i o n a l Over- STUB
G ro u n d
current O/C
Gnd
Fault
Distance Locator O / C
52
21
21N
FL
50N
51N
50 50N-2
51 51N-2
67N
50STUB
L
o
c
a
l/T
e
leC
tr
l.
C
o
m
m
a
n
d
s
C
B
In
d
ic
a
tio
n
s
TripCircuit
supervision
74TC
86
Lockout
68
68T
Power
Swing
85-21
27WI
8 5 -6 7 N
Pilot Weak
Dist. infeed
Teleprotection schemes
can use one channel or
two redundant channels to
the remote end
Distance protection
P ilo t
Gnd
50HS
50BF
59
2
5
S
y
n
c
h
ro
Switch Bkr. O v e r h
e
c
k
onto- fail. v o l t a g e c
Flt. O/C
Operat.
values
Supervision
7
9
A
u
to
re
c
lo
s
u
re
CFC Logic
Serial Communication
Interfaces
Info - 7
EV S V13/ Claus/ 21.08.00
!
SIPROTEC 7SA522
Scope of functions (1)
ANSI-No.
Distance Protection
21, 21N
quadrilateral and/or MHO characteristic
full scheme measurement with sophisticated loop selection
three phase and single phase tripping
five independent zones and one controlled overreach zone
all zones can be set forward/reverse/non-directional
with/without parallel line compensation
special filtering for CVT transients
special algorithm for detection and compensation of CT
saturation
Fault Locator with/without parallel line compensation
FL
Universal teleprotection interface
(PUTT, POTT, Blocking, Unblocking, DTT...)
85-21
Distance protection
Info - 8
EV S V13/ Claus/ 21.08.00
17.10.97
en513all7
SIPROTEC 7SA522
Scope of functions (2)
High resistance earth fault protection
for earthed systems
ANSI-No.
50N, 51N,
67N
directional and/or non-directional
4 stages
definite-time and/or inverse-time characteristic
high sensitivity (3 mA secondary)
backup protection running in parallel to the distance
protection
Teleprotection interface for earth fault protection
(Directional comparison, Blocking, Unblocking)
85-67N
Weak infeed protection
(Echo and Trip)
WI
Power swing blocking/out-of-step tripping
68
Distance protection
Info - 9
EV S V13/ Claus/ 21.08.00
17.10.97
en513all8
SIPROTEC 7SA522
Scope of functions (3)
ANSI-No.
Overcurrent protection DMTL/IDMTL as parallel or
emergency function
50, 51
50N-2, 51N-2
Overvoltage protection
59
Fast tripping with switch-onto-fault condition
50HS
STUB Bus Overcurrent protection
50-STUB
Single and three pole multishot automatic reclosure
79
Synchro-check
25
Circuit-breaker failure protection
50BF
Distance protection
Info - 10
EV S V13/ Claus/ 21.08.00
SIPROTEC 7SA522
Scope of functions (4)
ANSI-No.
Trip Circuit Supervision
74TC
Lock Out
86
Oscillographic Fault Recording
FR
Voltage Phase Sequence
47
Interfaces
Time synchronization (IRIG-B, DCF77)
User interface#1 (on the front for DIGSI 4)
User-(Service-)interface #2 (on the rear, DIGSI 4/Modem)
System interface (IEC60870-5-103/Profibus FMS*/others)
Remote relay interfaces #1 (planned for teleprotection)
Remote relay interfaces #2 (planned for teleprotection)
* available in Version 4.2 approx. 1. Q/01
Distance protection
Info - 11
EV S V13/ Claus/ 21.08.00
SIPROTEC 7SA522
Quadrilateral Zone Characteristic
rd
wa
for
X
s
Line
Z5
Z4
Z2
Z1B
rev
e
Z1
rse
Load
Load
R
forw
ard
s
Z3
rev
ers
e
Distance protection
Info - 12
EV S V13/ Claus/ 21.08.00
SIPROTEC 7SA522
MHO Zone Characteristic
X
Line
Z5
Z4
Z1B
Z2
Z1
Load
Load
R
Z3 (if revers)
Distance protection
Info - 13
EV S V13/ Claus/ 21.08.00
MHO characteristic
Effect of polarization
Im( V )
Example: 2 phase fault B-C
delta V = Z R x (I B - I C) - V BC
a > 90° and b < 90°
--> internal fault
Z R x ( I B - I C)
b
a
kpol x (V BC, memory - V BC)
V BC
Without memory
polarization
With memory
polarization
V Pol
Re( V )
Distance protection
Symbols:
ZR
V BC
I B, I C
k pol
zone setting
measured fault voltage
measured fault currents
polarization factor (0.15%)
Info - 14
EV S V13/ Claus/ 21.08.00
7SA522 - Trip time curves at SIR = 1
SIR=1 (A-G)
50
45
40
tripping time (ms)
35
30
EPAC 3000 Doku
SEL321 Doku
25
7SA522 gemessen
EPAC31/35
20
15
10
5
0
0
5
10
15
20
25
30
35
40
45
50
55
60
65
70
75
80
85
90
95
100
% of zone setting
Distance protection
Info - 15
EV S V13/ Claus/ 21.08.00
7SA522 - Parallel-line compensation: connection and setting
L1 (A)
L2 (B)
L3 (C)
Busbar
Q1
Q2
Q3
Q4
Q5
Q6
Q7
Q8
52
Line
Distance protection
Circuit
breaker
IL1(A)
IL2(B)
IL3(C)
I4
52
Circuit
breaker
Parallel line
Info - 16
EV S V13/ Claus/ 21.08.00
7SA522 - Fault locator
Distance protection
Info - 17
EV S V13/ Claus/ 21.08.00
7SA522 - Teleprotection Schemes
Configuration
Distance protection
Info - 18
EV S V13/ Claus/ 21.08.00
7SA522 - Phase segregated Teleprotection
2
2
L2-E
Z1
Z1B
A
1
L1-E
Z1
1
B
Z1B
A1 trips single-phase in L1 with a phase-segregated L1-receive-signal
Maximum of Selectivity
Note: 3 binary channels for both directions are requested or (in preparation) one serial link
Distance protection
Info - 19
EV S V13/ Claus/ 21.08.00
7SA522 - Teleprotection with three-terminal lines
Software provides
teleprotection of threeterminal lines without
additional logic
Distance protection
Info - 20
EV S V13/ Claus/ 21.08.00
7SA522 - Echo and Tripping in case of no-infeed or weak-infeed
Configuration
Settings
Matrix
The receive signal is derived from :
and
*Three-terminal schemes are supported as well
Phase segregated weak-infeed tripping
Note: The echo signal must be marshalled
in addition to the send signal on the
transmission signal contact
Distance protection
!
Info - 21
EV S V13/ Claus/ 21.08.00
17.10.97
en513ase2
7SA522
High Resistance Earth Fault Protection (1)
Earth (zero sequence) current protection, 4 stages
3 definite-time stages
1 inverse-time stage: IEC, logarithmic inverse or ANSI characteristic
this stage can also be used as a 4th definite-time stage
Directional determination with 3V0 and/or Ipol of an earthed power
transformer
Directional determination with V2 and I2 (negative sequence)
Sensitive 3I0-measurement with a dynamic from 0.005 A to 100 x In
Elimination of higher harmonics with special digital filters
Inrush-stabilisation with I0/100Hz
Teleprotection: Directional comparison, Blocking or Unblocking
Operation with weak infeed trip and echo
Instantaneous trip after switch-onto-fault
Distance protection
Info - 22
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (2)
T
Definite-time characteristic
T3I0>
T3I0>>
T3I0>>>
3I0>
Distance protection
3I0>>
3I0>>>
3I0
Info - 23
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (3)
T
Inverse-time characteristic: IEC
Tp =1
Pickup: a = 1.1 x 3I0/IP
Reset: b = 1.045 x 3I0/IP
0 ba
Distance protection
20
3I0/Ip
Info - 24
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (4)
IEC-characteristic:
normal inverse: t s
extremly inverse: t s
0.14
0.02
I
Ip
80
I
Ip
ANSI-characteristic:
A
t s
B
* D
N
I
1
Ip
very inverse: t s
* Tp
1
long time inverse: t s I
120
* Tp
2
13.5
* Tp
I
1
Ip
1
Ip
Inverse
short inverse
long inverse
moderately inverse
* Tp
1
very inverse
extremly inverse
definite inverse
Logarithmic-inverse characteristic:
t s T 3I 0P max T 3I 0P * ln
Distance protection
3I 0
for t>T3I0Pmin, otherwise: t[s]=T3I0Pmin
3I 0P
Info - 25
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (5)
Earth fault
direction
Inrushstabilisation
EF IE> Echo
EF Fault Det.
SOTF
Teleprotection
>EF Trip rel.
P
Direc. 3I0>>>
P
3I0>>>
=
&
EF>>> Trip
T
&
3I0>>> Def. Time Stage
>EF>>> block
3I0>> Def. Time Stage
3I0> Def. Time Stage
P Direc. 3I0p
P 3I0p
&
=
&
EFp Trip
P3146 AddTdelay
T(3I0/IN)
T
Inverse Time Stage
>EFp block
= Input signal
(binary input)
Distance protection
P
= Parameter
= Output Signal
(alarm, command)
Info - 26
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (6)
Tripping characteristic Logarithmic Inverse
t
10
T3I0pmax (P3145)
9
8
T3I0p (P3144)
7
3I0p(P3140)
6
Example: t = 5.8 - 1.35 ln(3I0 / 3I0p)
5
4
3
2
T3I0min
(P3141) 1
0
0
5
10
3I0p Startpoint(P3154)
Distance protection
15
20
25
30
35
3I0 / 3I0p
Info - 27
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (6)
Filter characteristic for stages 3I0>>> and 3I0>>
dB
10
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
-110
-120
-130
-140
-150
-160
0
1
2
3
4
5
6
7
8
9
10
11
f/fn
Distance protection
Info - 28
EV S V13/ Claus/ 21.08.00
7SA522
High Resistance Earth Fault Protection (7)
Filter characteristic for stages 3I0> and Inverse time stage
dB
10
0
-10
-20
-30
-40
-50
-60
-70
-80
-90
-100
-110
-120
-130
-140
-150
-160
-170
0
1
2
3
4
5
6
7
8
9
10
11
f/fn
Distance protection
Info - 29
EV S V13/ Claus/ 21.08.00
7SA522 - STUB protection for 11/2-circuit breaker arrangement
Busbar A
CB
(A)
Ik = IA+ IB
line isolator 1
feeder 1
IA
stub fault
CB
(C)
IB
feeder 2
line isolator 2
CB
(B)
Release of STUB-stage with open line isolator:
Busbar B
Distance protection
Info - 30
EV S V13/ Claus/ 21.08.00
7SA522 - Monitoring
Operating system monitoring
Plausibility monitoring
Auxiliary voltage failure
Current sum
Measured value detection
Buffer battery
Current symmetry
Hardware–Watchdog
Software–Watchdog
Working memory
1- / 2-pole failures
Program memory
3-pole failures
Parameter memory
Voltage sum
Sampling frequency
Voltage symmetry
1/5 A–setting
Voltage phase rotation
Calibration data
Earth current
transformer
sensitive/normal
Modules (I/O Boards)
Distance protection
Open conductor
Fuse Failure
Info - 31