FLUSARC 24kV
24 kV GIS Switchgear
for Secondary Distribution
Main Data
12 - 24kV SF6 insulated switchgear
Compact, extensible or modular
Indoor or Outdoor
With either fuse combination or circuit breaker for
transformer protection
Electric data:
Rated Voltage
12 - 24 kV
Rated Current
630 A
Short Time Current 1s
Making Capacity
Internal Arc
CB Breaking Capacity
2
> 2 , FLUSARC 24kV Sept. 2008
12,5-25 kA
62,5 kA
21 kA 1 sec
16 kA
Main Features Installation
Easy installation
 Can reach installation site already pre-assembled
 No need for specialized civil works
 Fast cable connection due to standardized bushing +
coupling MV cable terminals
 Reduced dimensions
 (CCT1, 2 disconnecting switch & 1 disconnecting
switch+fuses)

Width 1065mm

Height 1665mm

Depth 825mm
 Also available in 1290mm height
3

SF6 compartment is the same

Smaller footprint and cable compartment
> 3 , FLUSARC 24kV Sept. 2008
Main Features
Maintenance
Cable testing
 Easy cable testing thanks to standardized bushings
 Cable testing can be done
without interruption
of service
Terminal
cover
Capacitive
insulator
Adapter
terminal
4
> 4 , FLUSARC 24kV Sept. 2008
Test
kit rod
Main Features
Maintenance
Maintenance-free SF6 compartment
Sealed for life
 No adjustement or filling with gas during the whole life
SF6 pressure gauge
+ warning and alarm
contacts available
5
> 5 , FLUSARC 24kV Sept. 2008
Main Features
Operation
Several versions available:
 Indoor or outdoor
 Modular, extensible or compact
 Regular or reduced height
Suitable for very harsh
& polluted environments
Operates in severe conditions:
 Several installations already in Saudi Arabia
 Several installations already in Finland
Flusarc 24 outdoor version
6
> 6 , FLUSARC 24kV Sept. 2008
Main Features
Operation
Reliable working of the operating devices
 Field-proven experience with thousand of
installations over 15 years
All the operations are carried out from
the front
 Mechanical signals show the position of
the various switching components
Correct sequence instructions is showed
on switchgear front
7
> 7 , FLUSARC 24kV Sept. 2008
Main Features
Operation
Also Type tested under water
 Proved to be highly reliable
Maximum service continuity
Remote operation possible
8
> 8 , FLUSARC 24kV Sept. 2008
Main Features
Maximum service continuity
Insulation of all the live parts with SF6 gas
Simple and reliable system thanks to the low
pressure gas ensuring maintenance-free operation
for 30 years
Suitable for applications in polluted or high
humidity areas
 Flusarc not affected by external ambient conditions
 Flusarc can operate completely immersed in the
water for a defined period (24 h)
9
> 9 , FLUSARC 24kV Sept. 2008
Main features
Personnel safety
 Direct earthing of the whole switchgear structure
 Total segregation of live parts located in a completely
sealed SF6 stainless steel metal housing
 Access to fuses without any danger with earthing at both
sides
 Mechanical interlocks ensure correct sequence of
operations
 Security and simplicity of locking devices
 Internal arc proof in the tank
 On request also in cable compartment
 CESI type tests certification
10
> 10 , FLUSARC 24kV Sept. 2008
Main features
Personnel safety
 SF6 prevents fires from spreading
 Overpressure valves are placed under the switchgear:
 allows the hot exhaust gas escape into cable conduit
 eliminates any risk for the operator
Overpressure
valves
11
> 11 , FLUSARC 24kV Sept. 2008
Applications
Compact secondary substations
Light industries
Hotels,
shopping centres,
office buildings,
business centres etc.
Airports, hospitals,
tunnels, light mining applications
and railways
Utilities (e.g. Iberdrola, ENEL, Endesa, EDP, Fortum, SEC)
12
> 12 , FLUSARC 24kV Sept. 2008
Circuit Breaker Function
Characteristics:
 24kV 630A
 Short-time current: 16kA 1s
Option of two different relay
types for CB (Self powered and
Auxiliary powered)
Manual and motorized versions
Several versions available
 Outdoor
 Extensible
 Reduced height
13
> 13 , FLUSARC 24kV Sept. 2008
Circuit Breaker Function
Vacuum CB with 3 positions disconnector in series
Connected
14
> 14 , FLUSARC 24kV Sept. 2008
Disconnected
Earthed
Circuit Breaker Function
Vacuum interruption technology guarantees high
performance and reliability
 30 years without maintenance
Circuit breaker placed inside SF6 compartment
 Reduced dimension
Disconnecting switch placed
inside SF6 compartment
 Reduced dimension
 High reliability, same
mechanism for
disconnecting switch
and earthing switch
15
> 15 , FLUSARC 24kV Sept. 2008
Flusarc 24 configurations,
Block version I
C
CC
CCC
CCCC
CCCC
NB: Also versions with reduced basement height 400 mm are available
16
> 16 , FLUSARC 24kV Sept. 2008
Flusarc 24 configurations,
Block version II
T1CC
17
T1CC
> 17 , FLUSARC 24kV Sept. 2008
T1CCC
T1CCCC
Flusarc 24 configurations,
Block version III
T1T1CC
18
> 18 , FLUSARC 24kV Sept. 2008
T1T1CCC
CBCC
CBCCC
Flusarc CB 24
CBC
CBCCCC
19
> 19 , FLUSARC 24kV Sept. 2008
CBCBCC
CBCBCCC
Flusarc 24 Modular Version
20
> 20 , FLUSARC 24kV Sept. 2008
Inner View
21
> 21 , FLUSARC 24kV Sept. 2008
Type test
GPS-A0-004583
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
AT-A1-021622
AT-A1-025914
MP-A1-027149
A3-034915
A3-034916
A3-034917
A3-040945
GPS-A1-029405
B126-01-AX-EE-01E
Description
Arcing due to internal fault
Short-time withstand and peak withstand current test
Mainly active load current switching tests
Cable and line-charging current switching tests
Cable-charging breaking current tests under earth fault conditions
Earth fault breaking current tests
Short-circuit making current tests
Breaking tests at the rated transfer current
Dielectric perfomance
Dielectric perfomance
Temperature rise test. Measurement of the resistance of the main
circuit.
Temperature rise
Dielectric perfomance
Switching and Short-Circuit perfomance (16kA 1 sec.)
Switching and Short-Circuit perfomance (20kA 3 sec.)
Short-time withstand and peak withstand current test
Mainly active load current switching tests
Short-circuit making current tests
Type test:
Mechanical operation tests
Degree of protection
Measurement of leakage current
Dielectric tests on auxilairy circuits
Dielectric test with DC voltage
Immersion test
Strength of the gas-filled compartment
Anticorrosive protection
Date
21/12/1999
05/05/2001
05/05/2001
05/05/2001
05/05/2001
05/05/2001
05/05/2001
05/05/2001
10/07/2001
10/07/2001
Stds
Laboratory
IEC 60298
CESI
CESI
CESI
CESI
CESI
CESI
CESI
CESI
CESI
CESI
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265 - IEC 60420 - IEC 60129
IEC 60265-1 - IEC 60298
IEC 60265-1 - IEC 60299
12/07/2001 IEC 60265-1 - IEC 60298 - UNESA 6407B
CESI
16/07/2001
16/07/2001
16/07/2001
23/07/2001
IEC 60265-1 - IEC 60129
CESI
CESI
CESI
CESI
23/07/2001
IEC 60265-1 - IEC 60129
CESI
01/10/2001
IEC 60298 - RU 6407 B:96
LABEIN
EN 60137
LABEIN
IEC 32271-102
IEC 60268 - Techincal spec. PEHLA n° 4
3/1995
IEC 60268 - Techincal spec. PEHLA n° 4
LABEIN
IEC 60265-1
IEC 60265-1
IEC 60265-1 - IEC 60129
Type test:
B126-02-BB-EE-01E
Power-frequency voltage withstand test
Measurement of partial discharges
Cantilever load withstand test
Temperature rise test
Dry lightning impulse voltage withstand test
Verification of thermal short-time current withstand
FLUSARC 24 is fully type tested
01/05/2002
B126-02-BF-EE-01E
Mechanical endurance tests
01/05/2002
RP LS 03-137-A
Internal arc (21kA 1 sec.)
09/06/2003
22
> 22 , FLUSARC 24kV Sept. 2008
SVEPPI
B126-01-AX-EE-01E
Type test
GPS-A0-004583
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
B126-02-BB-EE-01E
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
GPS-A1-012579
B126-02-BF-EE-01E
AT-A1-021622
RP
LS 03-137-A
AT-A1-025914
RP LS 03-137-B
MP-A1-027149
A6-004394
A3-034915
E10053
A3-034916
E10056
A3-034917
A3-040945
E10054
GPS-A1-029405
E10057
E10063
E10064
E10065
E10066
B126-01-AX-EE-01E
E10067
E10068
E10069
Degree of protection
Measurement of leakage current
Dielectric tests on auxilairy circuits
Dielectric test with DC voltage
Immersion test
Strength of the gas-filled compartment
Description
Anticorrosive protection
Arcingtest:
due to internal fault
Type
Short-time withstand
and
peak withstand
current test
Power-frequency
voltage
withstand
test
Mainly active of
load
current
switching tests
Measurement
partial
discharges
Cable andload
line-charging
current switching tests
Cantilever
withstand test
Cable-charging
current tests under earth fault conditions
Temperature
rise breaking
test
Earth
fault breaking
currentwithstand
tests
Dry
lightning
impulse voltage
test
Short-circuit
tests
Verification
of making
thermal current
short-time
current withstand
01/10/2001
IEC 60298 - RU 6407 B:96
LABEIN
Date
Stds
Laboratory
IEC 60298
21/12/1999
IEC 60265 - IEC 60420 - IEC 60129
05/05/2001
IEC 60265 - IEC 60420 - IEC 60129
05/05/2001
IEC 60265 - IEC
60420 - IEC 60129
EN 60137
05/05/2001
01/05/2002
IEC 60265 - IEC 60420 - IEC 60129
05/05/2001
IEC 60265 - IEC 60420 - IEC 60129
05/05/2001
IEC 60265 - IEC 60420 - IEC 60129
05/05/2001
IEC 60265IEC
- IEC
60420 - IEC 60129
05/05/2001
32271-102
01/05/2002
IEC 60268
Techincal
spec.
PEHLA n° 4
IEC- 60265-1
- IEC
60298
10/07/2001
09/06/2003
3/1995
IEC
60265-1
IEC
60299
10/07/2001
IEC 60268 - Techincal spec. PEHLA n° 4
09/06/2003 IEC 60265-1 - IEC3/1995
60298 - UNESA 6407B
12/07/2001
IEC 60265-1
23/02/2006
IEC 60265-1
16/07/2001
IEC 62271-200
04/12/2007
IEC 60265-1
16/07/2001
IEC 62271-200
05/12/2007
IEC 60265-1 - IEC 60129
16/07/2001
IEC 60265-1 - IEC 60129
23/07/2001
IEC 60265-1
05/12/2007
Breaking tests
at the rated
Mechanical
endurance
teststransfer current
Dielectric
perfomance
Internal arc (21kA 1 sec.)
Dielectric perfomance
Temperature
rise test.
Measurement of the resistance of the main
Internal
arc (21kA
1 sec.)
circuit.
Temperature rise. Measurement of the resistance of the main circuit
Temperature rise
Short-time withstand and peak withstand current test
Dielectric perfomance
Temperature rise test
Switching and Short-Circuit perfomance (16kA 1 sec.)
Short-circuit
making
current perfomance
test on Load(20kA
Break3Switch.
Switching and
Short-Circuit
sec.) Short-circuit
making
current
on
Earthing
Switch
inside
Load
Break
Short-time withstand and peak withstand current test Switch.
23/07/2001
Mainly active rise
loadtest
current switching tests
Temperature
06/12/2007
Short-circuit
making
current
tests
Basic short-circuit test duties: T10, T30, T60, T100s and T100a. Single06/12/2007
Type test:
phase
and double-earth fault test
Mechanical operation
tests
Temperature
rise test
Degree
of
protection
Short-time withstand and peak withstand current test
Measurement of leakage current
Making
breaking
tests
in test duties TDisc, TDiwmax, TDitrasfer
Dielectricand
tests
on auxilairy
circuits
Dielectricarc
test(20kA
with DC
voltage
Internal
1 sec.)
Immersion
Internal
arctest
(20kA 1 sec.)
Strength arc
of the
gas-filled
compartment
Internal
(20kA
1 sec.)
Anticorrosive protection
CESI
CESI
CESI
CESI
LABEIN
CESI
CESI
CESI
CESI
LABEIN
CESI
SVEPPI
CESI
SVEPPI
CESI
CESI
CESI
ICMET
CESI
ICMET
CESI
CESI
ICMET
IEC 60265-1
- IEC 60129
IEC 62271-200
CESI
ICMET
IEC 62271-100
ICMET
07/12/2007
10/12/2007
IEC 62271-200
ICMET
ICMET
11/12/2007
01/10/2001
12/12/2007
12/12/2007
13/12/2007
IEC 62271-105
IEC 60298
- RU 6407 B:96
IEC 62271-200
IEC 62271-200
ICMET
LABEIN
ICMET
ICMET
ICMET
EN 60137
LABEIN
IEC 32271-102
IEC 60268 - Techincal spec. PEHLA n° 4
LABEIN
IEC 62271-200
IEC 62271-200
Type test:
B126-02-BB-EE-01E
B126-02-BF-EE-01E
23
RP LS 03-137-A
Power-frequency voltage withstand test
Measurement of partial discharges
Cantilever load withstand test
Temperature rise test
Dry lightning impulse voltage withstand test
Verification of thermal short-time current withstand
FLUSARC 24 is fully type tested
01/05/2002
Mechanical endurance tests
01/05/2002
> 23 , FLUSARC 24kV Sept. 2008
09/06/2003
Internal arc (21kA 1 sec.)
SVEPPI
CUSTOMER
COUNTRY
ENEL
ACEA
AEM
SELMA / ENDESA
FASYMON / IBERDROLA
ELCONTROL
TECHNICAL UNIVERSITY-SOFIA
BEIJING POWER UTILITY
ZHUHDI POWER UTILITY
ELKAMO
NOAVARAN BARQARIA
TENAGA NATIONAL BERHAD
Power Utility
LME (EDP Power Utility)
TIEPCO (SEC Power Utility)
ARKO S.R.O.
INTERSWITCH PTY LTD
CRYSTAL CONSULTING & ENG.
STATIONENBAU AG
GIRISIM ELEKTRIC D.S.
(Tedas Power Utility)
BINH SON ELECTRIC CO.LTD
ONE CO.LTD
MAIN REFERENCES
ITALY
ITALY
ITALY
SPAIN
SPAIN
BULGARIA
BULGARIA
CHINA
CHINA
FINLAND
IRAN
MALAYSIA
PORTUGAL
SAUDI ARABIA
SLOVENSKA
SOUTH AFRICA
SWITZERLAND
SWITZERLAND
TURKEY
VIETNAM
VIETNAM