SEPAM Communications Troubleshooting
Download
Report
Transcript SEPAM Communications Troubleshooting
SEPAM Communications
Troubleshooting
Power
Communications module not
powered
Power
Communications module not
powered
Terminating Jumper
Protocol
Modbus Wiring
2-Wire RS-485
+ connects to + and – connects to -
4-Wire RS-485
+’s and –’s are swapped
TX+ > RX+, TX- > RX-, etc.
Modbus Configuration
Modbus Address, Parity, Baud Rate
Incorrect Sepam Port selection
Sepam 80 has dual comm and
remote module ports
ION Master Connections
To communicate to an ION meter
there are two communication port
settings that need to be made.
Comm port on the meter needs to be
set to Modbus Master
Modbus Master Options Module must
have the comm port assigned to
ModbusGate Connection
ION Master Connections (cont)
ION Master Connections (cont)
ION Master Connections (cont)
Common Wrench Errors
Wrench 1 (most common)
Wrench 2
MSA141 (Analog Module) is not available
DSM303 (Remote Display) is not available
Wrench 5
MET148-2 (Temp Module) module is not available
Wrench 4
Typically caused by faulty wiring between remote module
connection.
Wrench 3
Typically CCA63x (CT module) is absent
I/O module is absent
MCS025 (Sync-Check) is not available
Wrench 10
CPU overload (Sepam 80 only) typically caused by excessively
large Logipam program
Wrench 1 (Most Common)
Wrench 1
Normally caused by:
CT module not attached to relay
I/O card is configured in the software
but is not attached to relay
If you are unable to connect with
SFT2841 it could indicate a major fault
with the base unit
On Sepam 80 it could indicate a faulty
memory cartridge
Verifying Cause of Error