BRC1E61 – Energy Saving Function
Download
Report
Transcript BRC1E61 – Energy Saving Function
VRV3 – Thats the Daikin Difference
BRC1E61 – Energy Saving Function
• Two energy saving functions available
– Set Temperature Auto Reset
• This function will revert the set temperature back to the
programmed temperature after a certain time defined by the user
– Set Temperature Range Limit
• This function allows setting a temperature range per mode
VRV3 – Thats the Daikin Difference
BRC1E61 Operations Menu
VRV3 – Thats the Daikin Difference
Access to Energy Saving Function
Press the menu button for 5 seconds until the function
“Energy Saving Settings” is displayed
Select the function “Energy Saving Settings” and press Enter
VRV3 – Thats the Daikin Difference
Energy Saving Setting
In the Energy Saving Setting menu,
there are 2 options to choose from:
• Set Temperature Auto Reset
• Set Temperature Range Limit
Use the up/down key to select the
desired option and press Enter
VRV3 – Thats the Daikin Difference
Set Temperature Auto Reset
Highlight the “Set Temperature Auto Reset”
using the down arrow button and press
menu/enter button
The screen shown here will appear with 3
options
• Enable / Disable Setting (turns the
function on/off without deleting settings
• Condition Setting (Cool)
• Condition Setting (Heat)
Select the desired mode by pressing Enter
VRV3 – Thats the Daikin Difference
Set Temperature Auto Reset
To change the temperature to the desired
level, use the up/down buttons
The set temperature can be set in 1 Deg C
increments. Once selected, the time delay
can then be set using the ‘Right’ button
To change the time delay, use the up/down
buttons. It’s possible to programme a time
range between 30mins to 120mins
To confirm the settings, press Enter
You will then access the confirmation screen,
select Yes to confirm
VRV3 – Thats the Daikin Difference
2. Set Temperature Range Limit Function
In the Energy Saving Setting menu,
select the Set Temperature Range
Limit
To select use the up/down keys and
press Enter
VRV3 – Thats the Daikin Difference
2. Set Temperature Range Limit Function
You will then access the screen shown
here.
Select the ‘Condition Setting (Cool)’
and press Enter
The following screen will then be
displayed
VRV3 – Thats the Daikin Difference
2. Set Temperature Range Limit Function
To change the lower limit temperature,
use the up/down keys
To access the upper limit temperature,
use the ‘Right’ button
Once both lower and upper limits have
been set, press the Enter button. The
following confirmation screen will then
be displayed
Select Yes to confirm settings and
press Enter. Once completed, you will
return to the main menu
VRV3 – Thats the Daikin Difference
Functions and Applications
• Set temperature auto reset function
– Used to provide boost to cooling / heating for limited
periods.
– Useful for both domestic and commercial applications
• Set temperature range limit function
– Prevent extreme set points in commercial applications
including office, nursing homes, schools etc
– Useful for small VRV installations, excludes the need
for I Touch controller to enable this function
VRV3 – Thats the Daikin Difference
Thank You