Tips & Insights for Sanitary Survey Preparation
Download
Report
Transcript Tips & Insights for Sanitary Survey Preparation
Tips & Insights to Prepare for
Sanitary Survey Inspections
(TIPSSI)
What to expect
What to have on hand
What to check
For Florida’s Water Sector
In coordination with FRWA and FDEP
Updated 1/11
1
Sanitary Survey
Form
Standard Info
~Current Facility ID
Capacity,
etc.,
~Well Construction
~Treatment Process
~Storage Data
~Distribution System
4/9/2015
2
Paper Work (part 1…)
Well Construction Information
Cross Connection Control Plan.
Bacteriological Sampling Plan
System Diagrams
Flow
Plans,
Schematics, etc.)
4/9/2015
MORs, Sampling Data Submittals
DEP Notices, Correspondence, etc.
3
Paper Work (part 2…)
Uni- Directional Flushing Program
Pump Specifications
Valve Maintenance / Exercising Plan
Tank Inspection Report
Signed,
Sealed by a P.E.
Within Last 5 Years
4/9/2015
Auxiliary Power Plan
Emergency Response Plan (ERP)
4
Annual Flow Data
Flows rates determine if appropriate
pumping capacity, storage capacity and
auxiliary power requirements are being met.
4/9/2015
5
O & M Log Books
Log books must be
maintained at the
treatment plant
and current to the
most recent visit.
4/9/2015
6
Wells
All wells should be
equipped with a well
casing vent. In cases
with no vent the
disinfection port may
be converted to act
as a vent.
4/9/2015
7
Flow Meters
Flow meters
must be
checked
periodically
for accuracy.
4/9/2015
8
•
All piping must be
screened (especially
dump lines, overflow
pipes, vents, etc.) and ,
labeled & color-coded
(ex.: reuse = purple).
4/9/2015
Piping
9
Lime Hoppers
Lime hoppers
should be covered.
The rooms should
be kept clean. A
ventilating fan is
recommended.
4/9/2015
10
Additives/Lubricants
Oil -lubed pumps must
utilize food grade oils.
NSF Standard 60
Approved (or
equivalent).
Hypo chlorination
systems must use NSF
60 approved chlorine.
4/9/2015
11
Maintenance
Clean, well- maintained
facilities let the inspector
know you share their
dedication to providing
safe drinking water.
4/9/2015
12
Safety
Be sure sources of
contamination are
not stored in close
proximity to wells.
4/9/2015
13
Safety
Open windows at a
well house encourage
unwanted visitors.
Prevent unauthorized
entry. Consider
fences, locked doors,
gates, alarms, etc.
4/9/2015
14
Safety
If fencing is not
an option,
other forms of
well protection
are available.
4/9/2015
15
Safety Devices
SCBA* is
required at all
Gas Chlorination
Facilities.
…MUST be inspected
often (according to
NIOSH guidelines).
4/9/2015
16
Chlorine Rooms
Chlorine rooms
must be
designed to meet
Ten State
Standards
4/9/2015
17
Chlorine Rooms
Open drains in
gas chlorine
rooms are not
acceptable (why
not?).
4/9/2015
18
Chlorine Rooms
4/9/2015
All gas cylinders
should be
properly secured
to a wall…
And kept out of
direct sunlight.
19
Chlorine Rooms
Hypochlorination
tanks must meet
with ANSI / NSF 60
standards.
All openings must
be protected and
the tank kept out of
direct sunlight.
4/9/2015
20
Chlorine Rooms
Exhaust vents
must not
discharge near
entrances.
Chlorine vents
must be low
…preferably as
far as possible
from entrances.
4/9/2015
21
Plants
Labeling of all
equipment and
piping gets extra
points from the
inspector.
Operating Pressures
and chemical feed
rates will be noted.
4/9/2015
22
Alarms
Chlorine alarms must be
fully operational at all
times;
Must be tested frequently
to insure proper working
condition.
4/9/2015
23
Elevated Storage Tanks
Overflows should
be brought down to
12” to 24” above
ground level
Discharge should
be to a splash plate
4/9/2015
24
Elevated Storage Tanks
4/9/2015
Storage tanks
with elevated
overflow outlets
must have both
a flapper valve
and a screen.
25
Elevated Storage Tanks
4/9/2015
Some systems
become creative
in meeting certain
requirements.
This may not
work as well as
intended.
26
Storage Tanks
All vents must be
properly screened
to help prevent
contamination.
Tanks should be
kept in good
condition w/a proper
pressure release
valve.
4/9/2015
27
Concerns noted on Report:
“DEFICIENCY 1: Storage tank
protection
Pipe inlet openings should be
sealed from rainwater.
RULE REFERENCE: 62-555.330(3)
RECOMMENDED ACTION: Refer to
Ten State Standards: finished water
structures shall have suitable watertight
roofs which exclude birds, animals,
insects, and excessive dust.
Please correct by August 31, 2011.”
4/9/2015
28
Site Review
Surrounding
areas are noted
for possible
sources of
contamination.
4/9/2015
29
Testing
Chlorine and pH
readings will be
conducted during
the survey. Proper
testing equipment
must be on-hand
and properly
maintained.
4/9/2015
30
Storage
Tanks
Some pictures need
no explanation.
31