Transcript here

Conquest FireSpray
Fire Rated Ductwork
Warren Michigan
Manufacturing Capabilities
•
•
•
•
Two fabrication facilities (130,000 + sq. ft.)
History of large projects (Ohio State Univ.)
Full 3D modeling & project management staff
All styles of duct (spiral, flat oval, rectangular, welded)
Enclosure by Design:
• In the USA the predominate method
for fire protection is subdivided into
categories:
• Compartments
• Detection
• Alarm/Notification
• Evacuation
• Sprinklers
• Smoke Removal
Enclosure by Design:
• What about smoke removal?
• Are we engineering a smoke removal
system tested for that use?
• Or are we utilizing the existing
systems to perform a function they
are not tested to provide?
Enclosure by Design:
• According to SMACNA and the
corresponding British standard
ventilation and exhaust ductwork have
no tested fire resistive standard in
their respective designs.
• That means the SMACNA tables are
not designed to include a fire rating.
• HVAC systems with openings will
introduce hot gasses into the duct
that is not designed to handle.
What is Fire Rated
Ductwork
• Search of 2009 IBC and 2009 IMC
• No mention in the code of Fire
Resistive Ductwork
• How do we handle Fire Resistive
Ductwork?
Enclosure by Design:
• There is no USA (ASTM) test today
that recognizes fire rated duct
systems.
• There is however an International
Standard ISO 6944 (1985 and 2008) .
ISO 6944
• ISO 6944
• Test Fire Resistive performance of
ductwork.
• Test follows time temperature curve
in E119
• Developed in EU for Fire Duct and
Smoke Extraction Ductwork.
ISO 6944
• ISO 6944
• Tests Ductwork for 2 conditions
• Fire inside a duct Type B
• Fire outside a duct Type A
• Conditions of the Test
• Integrity
• Stability
• Insulation
Type A and Type B Duct
(Wrap is only rated for Type A)
THE DUCT IS THE ENCLOSURE
Alternate Systems
Drywall Enclosures
• Conventional Shaft Riser
with 2 hour Rated Gypsum
Enclosure (3 layers)
• Fire dampers must be in wall
Alt. Wrap Enclosures
Firewrap Insulated Duct
• Insulated Fire Wrap
• 1 and 2 hr protection
• Type A only (fire outside
the duct)
• Upgraded Duct
• Upgraded Supports
• Multiple Trades
Fire Rated Duct
Tested and Classified by UL &
ETL
Classified for up to 2 & 4 hours as a smoke and
fire duct (ISO-6944) and complies with NFPA 96
Fire Rated Ductwork
• US Codes are evolving to accept a
duct as an enclosure.
• ASTM E2816-11 Metallic Fire Resistive
Duct Enclosures.
• Passed Committee July 2011
• ICC Evaluation Services
• Acceptance Criteria November 2011
Fire Rated Ductwork
& Metalic Enclosure
• Test Procedure based on ISO 6944
(2008) standard
• Tests Ductwork for both conditions
• Horizontal Condition A, C
• Vertical Condition B, D
• Test for fire inside and outside the
duct. You cannot guarantee a fire
will remain outside the duct.
Fire Rated Ductwork
& Metalic Enclosure
• Test Procedure based on ISO 6944
(2008) standard
• Conditions of the Test
• Integrity
• Stability
• Insulation
• Test includes Hangers, Supports and
Firestop conditions.
• Inserts and structural connections
not inlcuded.
Grease Duct
• June 2012
• ICC ES issued Acceptance Criteria
AC101.2
• Recognized galvanized duct without
porcelain coating.
• Tested to conditions of UL1978
except for those related to coating.
• Field enclosure
Conquest FireSpray
[email protected]
586-576-7600