Transcript 2102
System and its components Matej Kroselj
A brief history
Industrial PLC
SYSTEM Industrial & Building Automation
CAN field bus Ethernet communication Not yet intelligent…
Generally
High level network
SYSTEM Industrial & Building Automation
CyBro controller Low level network Accessories
Controller SYSTEM
Cybro controller is the core building block of automation system. Cybro controller is always equipped with CAN interface to connect IEX modules. In addition to this Cybro controller may have local inputs, outputs and communication interfaces, with Ethernet being most important among them. Through Ethernet or serial connection, controller can be programmed, monitored, remotely updated and managed over any kind of physical media including Internet.
Behavior of CyBro controller is specify by program running in it.
CyPro is a development environment used for programming Cybro controllers. Application generators and extensive libraries may reduce the need for programming, so most of the standard systems can be simply configured. On the other hand full system power is available to skilled programmers.
SYSTEM High level network
RS485 technical specifications: - bus length: max. 1000m - number of devices: max. 32 - baudrate: 19.2kbps
A-bus is proprietary high level network protocol. This compact and highly reliable protocol can be used with Ethernet TCP/IP or serial RS485 network standard. A-bus is perfect low cost choice for connecting CyBro controllers, touch screen panels and PC with SCADA tool. A-bus protocol is open protocol, so it can be used also in products from other vendors.
Ethernet technical specifications: - UTP cable length: max. 100m - cable autodetect: patch/crossover - number of devices: max. 255 - baudrate: 10/100Mbps - TCP/IP protocols: UDP, DHCP, IPv4 ModBus protocol is used to establish master-slave communication between intelligent devices. It is standard, truly open and the most widely used network protocol in the industrial manufacturing environment. ModBus protocol can be established on Ethernet or serial RS485 network.
SYSTEM Low level network
IEX technical specifications: - bus length: max. 300m - number of devices: max. 31 - baudrate: 20, 50,100 (default), 200, 500kbps - software selectable - topology: free IEX is proprietary low level network based on CAN (Controller Area Network) bus protocol. IEX protocol uses all advantages (reliability, speed) of CAN bus to connect different expansion module to CyBro-2 controller. Expansion modules have unique network addresses and when they are connected, modules are detected automatically - so there is no need for DIP-switch addressing.
Modules: Wide range of IEX modules are available, covering every possible IO unit (digital, analog, RTD, temperature, moisture, illumination, presence), communication protocols (infrared, RS232, RS485, Ethernet, DSI, DALI, GSM, GPRS), operator panels (keypads, semi-graphics, touch screens, IR remote controller), dedicated high function modules (access control, inverter unit, RGB controller, fan-coil controller, hotel room controller, light controller, switch unit, park sensor module).
CYBRO-2
SPECIFICATIONS:
CPU 24MHz, flash, RAM, EEPROM RTC, HSC 2 x RS232, Ethernet, IEX comm.
10 x digital input 8 x relay output (5A/230V AC) 4 x analog input 0..20mA or 0..10V
1 x analog output 0..10V
MECHANIC:
mounting: DIN rail (35mm) width: 6M
TYPES:
CYBRO-2-230 CYBRO-2-230-E CYBRO-2-24 CYBRO-2-24-E
CONTROLLER
RC
SPECIFICATIONS:
CPU 24MHz, flash, RAM, EEPROM RTC 2 x RS232, Ethernet, IEX comm.
power supply 24V DC
MECHANIC:
mounting: DIN rail (35mm) width: 6M
TYPES:
RC RC-E
CONTROLLER
OPERATOR PANEL Touch screen panels
High-quality color displays with superior clarify and wide viewing angels from 4.3’’ to 15’’. Resistive touch detection technology.
Freeware developing environment for creating graphical human-machine interfaces.
RS232/485, Ethernet ports for communication between panels and CyBro controllers.
Mounting in panel on electrical cabinet door or with mounting kit on wall.
Power supply 24V DC.
TYPES:
4.3’’, 480x272, wide screen, 65k colors, serial port - OP-MT6050I 5.6’’, 320x234, 65K colors, serial and *Ethernet ports - OP-MT6056I, *OP-MT8056T 7“, 800x480, 65k colors, wide screen, serial and *Ethernet ports - OP-MT6070IH, *OP-MT8070IH 10’’, 800x480, 65K colors, wide screen, serial and *Ethernet ports - OP-MT6100I, *OP-MT8100I 10.4’’, 800x600, 65K colors, serial and Ethernet ports - OP-MT8104XH 12.1’’, 800x600, 65K colors , serial and Ethernet ports - OP-MT8121X 15’’, 1024x768, 65K colors , serial and Ethernet ports - OP-MT8150X
OP-1
SPECIFICATIONS:
IEX expansion module LCD 2x16 characters 5 x key temperature measurement IR receiver buzzer 24V DC power supply consumption: 50mA
CUSTOMIZATION:
custom designed front foils
MECHANIC:
mounting: into wall flush box 120x58mm (4 x switch)
TYPE:
OP-1-IW
OPERATOR PANEL
OP-2
SPECIFICATIONS:
IEX expansion module LCD 2x16 characters 5 x key 24V DC power supply consumption: 40mA
MECHANIC:
mounting: on electrical cabinet door enclosure IP54 with rubber seal
TYPE:
OP-2-CT
OPERATOR PANEL
OP-3
SPECIFICATIONS:
IEX expansion module LCD 2x20 characters, 4 x LED 5 x key temperature measurement humidity measurement IR receiver buzzer 24V DC power supply consumption: 50mA
CUSTOMIZATION:
custom designed front foils
MECHANIC:
mounting: on wall flush box Ø60 needed
TYPES:
OP-3-T-OW OP-3-TH-OW
OPERATOR PANEL
OP-4
SPECIFICATIONS:
IEX expansion module LCD 2x20 characters rotary encoder key light measurement IR receiver buzzer 24V DC power supply consumption: 50mA
MECHANIC:
mounting: on wall
TYPE:
OP-4-OW
OPERATOR PANEL
OP-5
SPECIFICATIONS:
IEX expansion module LCD 2x20 characters 5 x key temperature measurement humidity measurement IR receiver buzzer 24V DC power supply consumption: 50mA
CUSTOMIZATION:
custom designed front panel
MECHANIC:
mounting: on wall flush box 3M needed
TYPES:
OP-5-T-IW OP-5-TH-IW
OPERATOR PANEL
GSM-1
GSM/GPRS module
SPECIFICATIONS:
GSM/GPRS 850/900/1800/1900 MHz 4 x analog/digital input 2 x relay output 24V DC power supply consumption stand by: 50mA active: 500mA
MECHANIC:
mounting: DIN rail (35mm) width: 2M
TYPE:
GSM-1
IEX MODULE
CR-W2
Access control module SPECIFICATIONS:
2 x input for RFID card readers with Wiegand protocol 4 x analog/digital input 2 x relay output 24V DC power supply consumption stand by: 50mA active: 500mA
MECHANIC:
mounting: DIN rail (35mm) width: 3M
TYPE:
CR-W2
IEX MODULE
AIC-12, AIR-12, AIV-12
analog precision measurement
SPECIFICATIONS:
- AIC-12: 12 x 0..20mA
- AIR-12: 12 x Pt100/1000,Ni100/1000,R - AIV-12: 12 x 0..10V
24V DC power supply consumption: 50mA
MECHANIC:
mounting: DIN rail (35mm) width: 3M
TYPES:
AIC-12 AIR-12 AIV-12
IEX MODULE
AOV-12
analog voltage outputs
SPECIFICATIONS:
12 x 0..10V
24V DC power supply consumption: 150mA
MECHANIC:
mounting: DIN rail (35mm) width: 3M
TYPE:
AOV-12
IEX MODULE
BIO-24
digital I/O
SPECIFICATIONS:
12 x digital input - BIO-24R: 12 x relay output - BIO-24T: 12 x transistor output 24V DC power supply consumption - BIO-24R:160mA - BIO-24T: 90mA
MECHANIC:
mounting: DIN rail (35mm) width: 6M
TYPES:
BIO-24R BIO-24T
IEX MODULE
BIO-24R MANAGING LIGHTS WITH BIO-24R MODULE
BIO-8R4
power digital I/O for switching lights (L) for driving blinds (B24) for general purpose (N)
SPECIFICATIONS:
4 x mains power digital input 8 x power relay output (16A) 24V DC power supply consumption: 150mA
MECHANIC:
mounting: DIN rail (35mm) width: 6M
TYPES:
BIO-8R4-L BIO-8R4-B24 BIO-8R4-N
IEX MODULE
BIO-8R4 CONNECTING BLINDS TO BIO-8R4 MODULE
BIO-8R4 CONNECTING LIGHTS TO BIO-8R4 MODULE
8C
digital I/O
SPECIFICATIONS:
4 x digital input 4 x relay output 24V DC power supply consumption: 100mA
MECHANIC:
field mountable
TYPE:
8C-FB
IEX MODULE
FC
fan coil module
SPECIFICATIONS:
1 x digital input 5 x relay output 2 x input temperature measurement 24V DC power supply consumption: 110mA
MECHANIC:
field mountable
TYPE:
FC-FB
IEX MODULE
FC CONNECTING FAN COIL AND WINDOW SWITCH TO FC MODULE
HR
hotel room module
SPECIFICATIONS:
12 x digital input 10 x relay output 2 x input temperature measurement 24V DC power supply consumption: 200mA
MECHANIC:
mounting: DIN rail (35mm) width: 6M
TYPE:
HR
IEX MODULE
LC-S
analog dimming light control
SPECIFICATIONS:
4 x 0..10V output 3 x potentiometer input 2 x digital input multisensor input (motion, light, IR receiver) 24V DC power supply consumption: 100mA
MECHANIC:
field mountable
TYPE:
LC-S-FB
IEX MODULE
LC-D
digital dimming light control
SPECIFICATIONS:
4 x DSI output DALI output 3 x potentiometer input 2 x digital input multisensor input (motion, light, IR receiver) 24V DC power supply consumption: 160mA
MECHANIC:
field mountable
TYPE:
LC-D-FB
IEX MODULE
LC-DC
digital dimming light control
SPECIFICATIONS:
DALI output 2 x digital input multisensor input (motion, light, IR receiver) 24V DC power supply consumption: 100mA
MECHANIC:
mounting: DIN rail (35mm) width: 2M
TYPE:
LC-DC
IEX MODULE
O2
switching lights
SPECIFICATIONS:
2 x relay output 24V DC power supply consumption: 85mA
MECHANIC:
mounting: flush box (80 mm)
TYPE:
O2-L-IW
IEX MODULE
TS, TS-H
temperature sensor
SPECIFICATIONS:
temperature measurement humidity 24V DC power supply consumption: 15mA
MECHANIC:
mounting: on wall
TYPE:
TS-OW-WHITE TS-H-OW-WHITE TS-OW-IVORY TS-H-OW-IWORY TS-OW-CUSTOM
IEX MODULE
SW-L
switch module
SPECIFICATIONS:
8 x switch input 4 x LED 24V DC power supply consumption: 70mA
CUSTOMIZATION:
different LED colors
MECHANIC:
mounting: flush box
TYPE:
SW-L-EM SW-L-EM-CUSTOM SW-L-EM-KIT
IEX MODULE
SW-W
digital dimming light control
SPECIFICATIONS:
8 x switch input 2 x switch / potentiometer input 2 x LED output 24V DC power supply consumption: 50mA
MECHANIC:
mounting: flush box
TYPE:
SW-W-EM SW-W-EM-CUSTOM
IEX MODULE
SW-W CONNECTING KEYS AND MOTION SENSORS TO SW-W MODULE
SW-W2
switch module
SPECIFICATIONS:
4 x switch / potentiometer input 4 x LED output 24V DC power supply consumption: 70mA
CUSTOMIZATION:
different LED colors
MECHANIC:
mounting: flush box
TYPE:
SW-W2-IW
IEX MODULE
SW-W2 CONNECTING KEYS AND POTENTIOMETERS TO SW-W2 MODULE
COM-ABUS, COM-PRN
Serial 232/485 port
SPECIFICATIONS:
RS232 port RS485 port
MECHANIC:
mounting: DIN rail (35mm) width: 2M
TYPE:
COM-ABUS COM-PRN
IEX MODULE
CAD-232-A2
A-bus converter
SPECIFICATIONS:
RS232 to RS485 converter
MECHANIC:
mounting: DIN rail (35mm) width: 2M
TYPE:
CAD-232-A2
ACCESSORIES
ES, ES-W
external temperature sensor
SPECIFICATIONS:
temperature measurement (connects to TS, FC etc.)
MECHANIC:
mounting: on wall (ES) on wire (ES-W)
TYPE:
ES ES-W-OW-WHITE ES-W-OW-IVORY ES-W-OW-CUSTOM ES-1M-IW
SENSOR
MS-I, MS-O
multisensor
SPECIFICATIONS:
light measurement IR receiver 12..24V DC power supply
MECHANIC:
mounting: flush box in ceiling
TYPE:
MS-O-IW MS-I-IW
SENSOR
LRI8134
multisensor
SPECIFICATIONS:
light measurement motion detector IR receiver 12..24V DC power supply
MECHANIC:
mounting: flush box in ceiling
TYPE:
LRI8134-IW
SENSOR
LRM8114 / 15 / 16 / 17
motion sensor
SPECIFICATIONS:
motion detector 12..24V DC power supply
MECHANIC:
mounting: on wall
TYPE:
LRM8114-IW LRM8115-OW LRM8116-OW LRM8117-OW
SENSORS
RE
remote control
SPECIFICATIONS:
Philips RC-5 code system 11 x keys IR range 5m
MECHANIC:
mounting: on wall
TYPE:
RE
ACCESSORIES
Cables and accessories
IEX bus cables, Ethernet and serial cables, bus splitters, bus adapters,…
ACCESSORIES
PS-30
switching power supply
SPECIFICATIONS:
output voltage 24V DC ±3%, max 1.4A
12V DC ±3%, max 2.4A
5V DC ±3%, max 3.8A
MECHANIC:
mounting: DIN rail (35mm) width: 3M
TYPE:
PS-30 PS-30-V12 PS-30-V05
POWER SUPPLY UNIT
PS-50
switching power supply
SPECIFICATIONS:
output voltage 24V DC ±3%, max 2.75A
MECHANIC:
mounting: DIN rail (35mm) width: 5M
TYPE:
PS-50
POWER SUPPLY UNIT
PS-80
switching power supply
SPECIFICATIONS:
output voltage 24V DC ±3%, max 5A
MECHANIC:
mounting: DIN rail (35mm) width: 8M
TYPE:
PS-80
POWER SUPPLY UNITS
SOFTWARE CyPro
HARDWARE REQUIREMENTS:
Pentium 500MHz with 128MB RAM 4MB of hard drive space RS232 or Ethernet port for connection to controller
Available at:
www.cybrotech.co.uk
CyPro is a software package for programming CyBro-2 controllers. It runs on Microsoft Windows 95/98/ME/NT4/2k/XP/Vista. CyPro is a fully featured IDE (integrated development environment) that comprising an editor, a compiler, and an on-line monitor.
CyPro development tool is based on the IEC 1131-3 standard. It employs instruction lists and structured text programming, extended with several useful visual tools.
SOFTWARE CyBro OPC Server
HARDWARE REQUIREMENTS:
Pentium 500MHz with 128MB RAM 2.5MB of hard drive space RS232 or Ethernet port for connection to controller
Evaluation licence available at:
www.cybrotech.co.uk
A CyBro OPC Data Access Server enables OPC clients (such as SCADA) to connect to the CyBro-2 system, using A-bus protocol. OPC includes open connectivity via open standards. An OPC server uses Microsoft's OLE technology (also known as the Component Object Model, or COM) to communicate with clients. COM technology permits a standard for real-time information exchange between software applications and process hardware.