**************************)*******3
Download
Report
Transcript **************************)*******3
Chapter 8
Feedback Controllers
Chapter 8
Error Signal
e t R t B t
where
R t = set point (3-15 psig; 4-20mA; 1-5V)
B t = measured value of controlled variable
(or equivalent signal from transmitter)
(3-15 psig; 4-20mA; 1-5V)
Define
e t e t 0; R t R t R ; B t B t B
0 R B e t R t B t
Take Laplace Transform
E s R s B s
Proportional Control
p (t ) p K c e(t ) p K c R (t ) B (t )
where
p (t ) controller output
p = bias value (adjustable)
K c controller gain (dimensionless, adjustable)
e(t ) error signal
Transfer Function
p t p t p
P s
Kc
Gc s
e t e t 0
E s
Chapter 8
Reverse or Direct Acting
Controller
• Direct-Acting (Kc < 0): “output increases
as input increases"
• Reverse-Acting (Kc > 0): “output increases
as input decreases"
Chapter 8
Proportional Band (PB)
PB is the error (% of the range of controlled
variable) required to move the output from
its lowest to its highest value.
100%
PB
Kc
Chapter 8
• Example 2: Flow Control Loop
Assume FT is direct-acting.
1.) Air-to-open (fail close) valve ==> ?
2.) Air-to-close (fail open) valve ==> ?
• Consequences of wrong controller action??
Chapter 9
Chapter 8
Example 3: Liquid Level Control
• Control valves are air-to-open
• Level transmitters are direct acting
Question:
Type of controller action?
p 10 psig
in order to make qo 170 gpm
p 9 psig
qi qo at steady state
p t p Kce t
Kce 1
where K c 0
e R B 0
INTEGRAL CONTROL ACTION
Chapter 8
p (t ) p
1
I
t
e( )d
0
P( s )
1
E ( s ) I s
I : reset time (or integral time) - adjustable
(1) If e(t ) 0, then p(t ) varies continuously with time.
(2) If e(t ) 0 for t t*, then
p t ps p
1
I
t*
e( )d constant
0
Proportional-Integral (PI)
Controller
t
1
p (t ) p K c e(t ) e(t ) dt
I 0
where p is not adjustable
Transfer Function
P( s )
1
K c 1
E ( s)
Is
Reset Time
Reset time is the time that the integral mode repeats the
action of proportional mode.
t I
t
t*
Example:
Heat Exchanger Control Loop
Reset Windup
e t 0
t
1
p(t ) p K c e(t ) e(t )dt
I 0
vp t vp K v p t p
p t
t
0
to
ts
Reset Windup
e t 0
e t 0
t
1
p(t ) p K c e(t ) e(t )dt
I 0
vp t vp K v p t p
p t
t
t
t
Anticipatory or Derivative Control
Action
de
p (t ) p D
dt
Used to improve dynamic response of the
controlled variable
Proportional-Integral-Derivative
(PID) Control
Now we consider the combination of the
proportional, integral, and derivative control
modes as a PID controller.
• Many variations of PID control are used in
practice (see Table 8.1, page 194)
• Next, we consider the three most common
forms.
Parallel Form of PID Control
The parallel form of the PID control algorithm
(without a derivative filter) is given by
1
p t p K c e t
τI
de t
0 e t * dt * τ D dt
t
Transfer Function
P s
1
K c 1
τDs
E s
τI s
Effects of Anticipatory
(Derivative) Control Action
Drawbacks of Anticipatory
(Derivative) Control Action
Chapter 8
Parallel-Form PID Controller with
Derivative Filter
P s
τDs
1
K c 1
E s
τ I s τ D s 1
where
0.05 0.2 (usually 0.1)
Derivative and Proportional Kicks
One disadvantage of the previous PID
controllers is that a sudden change in set
point (and hence the error, e) will cause the
derivative term momentarily to become
very large and thus provide a derivative kick
to the final control element.
R t
p t
Elimination of Derivative and
Proportional Kicks in ParallelForm Controllers
1
p t p K c e t
I
or
dB
0 e t * dt * D dt
1
p t p Kc B t
I
t
dB
0 e t * dt * D dt
t
Series Form of PID Control
Historically, it was convenient to construct early analog controllers
(both electronic and pneumatic) so that a PI element and a PD element
operated in series. Commercial versions of the series-form controller
have a derivative filter that is applied to either the derivative term,
as in Eq. 8-12, or to the PD term, as in Eq. 8-15:
P s
τ I s 1 τ D s 1
Kc
E s
τ
s
ατ
s
1
I D
Elimination of Derivative Kick in
Series-Form Controllers
R s
B s
B s
s 1
R s D s 1 B s K c I
P s
s
I
versus
s 1
R s B s K c D s 1 I
P s
Is
Expanded (Non-interacting) Form
of PID Control
In addition to the well-known series and parallel forms,
the expanded form of PID control in Eq. 8-16 is sometimes
used:
t
de t
0
dt
p t p K c e t K I e t * dt * K D
Chapter 8
Chapter 8
Typical Response of Feedback Control Systems
Consider response of a controlled system after a
sustained disturbance occurs (e.g., step change in
disturbance variable)
Chapter 8
Chapter 8
Automatic and Manual Control Modes
Chapter 8
•
Automatic Mode
Controller output, p(t), depends on e(t), controller
constants, and type of controller used.
( PI vs. PID etc.)
Manual Mode
Controller output, p(t), is adjusted manually.
Manual Mode is very useful when unusual
conditions exist:
plant start-up
plant shut-down
emergencies
• Percentage of controllers "on manual” ??
(30% in 2001, Honeywell survey)
Digital PID Controller
t n 1
D
p n p K c e n e k e n e n 1
I k 1
t
Chapter 8
where,
t = the sampling period (the time between
successive samples of the controlled variable)
p n = controller output at the nth sampling
instant, n=1,2,…
en = error at the nth sampling unit
velocity form - see Equation (8-19)
(pd)- incremental change
Chapter 8
Controller Comparison
P
-Simplest controller to tune (Kc).
-Offset with sustained disturbance or set point
change.
PI
-More complicated to tune (Kc, I) .
-Better performance than P
-No offset
-Most popular FB controller
PID
-Most complicated to tune (Kc, I, D) .
-Better performance than PI
-No offset
-Derivative action may be affected by noise
Chapter 8
Summary of the Characteristics of the Most
Commonly Used Controller Modes
1. Two Position:
Inexpensive.
Extremely simple.
2. Proportional:
Simple.
Inherently stable when properly tuned.
Easy to tune.
Experiences offset at steady state.
3. Proportional plus integral:
No offset.
Better dynamic response than reset alone.
Possibilities exist for instability due to lag
introduced.
Chapter 8
4. Proportional plus derivative:
Stable.
Less offset than proportional alone (use of
higher gain possible).
Reduces lags, i.e., more rapid response.
5. Proportional plus reset plus rate:
Most complex
Rapid response
No offset.
Difficult to tune.
Best control if properly tuned.
Chapter 8
On-off Controllers
•
•
•
•
Simple
Cheap
Used In residential heating and domestic refrigerators
Limited use in process control due to continuous
cycling of controlled variable excessive wear
on control valve.
Example 1: Temperature control of jacketed vessel.
On-Off Controllers
Chapter 8
Synonyms:
“two-position” or “bang-bang” controllers.
Controller output has two possible values.
Chapter 8
Practical case (dead band)