Complex Power
Download
Report
Transcript Complex Power
Complex Power
•
•
•
•
Designate as S
Magnitude of S = Apparent Power
Units are Volt-Amperes
The complex sum of Real Power (P) and
Reactive Power (Q)
S P jQ
S P Q
2
2
ECE 201 Circuit Theory I
1
Graphical Interpretation of S
Power Triangle
v i
S P jQ
S P Q
2
ECE 201 Circuit Theory I
2
2
v i
Q
tan
P
Vm I m
sin( v i )
Q
2
P Vm I m cos( )
v
i
2
Q
tan( v i )
P
ECE 201 Circuit Theory I
3
Summary
v i
S P jQ
Q
P
tan 1
S P2 Q2
S ApparentPower
ECE 201 Circuit Theory I
4
Summary -- 2
Apparent Power – the volt-amp capacity required to supply P
Q = Power exchanged between
source and load
P = Useful Output from the device being powered
(Watts)
ECE 201 Circuit Theory I
5
Summary -- 3
If the power factor angle is = 0,
Apparent Power = Average Power (and Reactive Power = 0).
ECE 201 Circuit Theory I
6
Example 10.4
Calculating Complex Power
• An electrical load operates at 240 V rms.
The load absorbs an average power of
8 kW at a lagging power factor of 0.8.
• Calculate the complex power of the load.
• Calculate the impedance of the load.
ECE 201 Circuit Theory I
7
The power factor is “Lagging”, so we have an
inductive load. The Reactive Power, Q, is
Positive.
P S cos
Q S sin
P S cos
Q S sin
ECE 201 Circuit Theory I
8
cos (0.8) 36.87
sin sin( 36.87) 0.6
1
P
8kW
S
10kVA
cos
0.8
Q S sin 10kVA(0.6) 6kVARS
S P jQ (8 j 6)kVA
ECE 201 Circuit Theory I
9
Vrms Veff
Z
I rms I eff
P Veff I eff cos( v i )
P (240) I eff (0.8) 8000W
I eff
8000W
41.67 A
(240)(0.8)
Z
Veff
I eff
240
5.76
41.67
Z cos 1 (0.8) 36.87
Z 5.7636.87 4.608 j 3.456
ECE 201 Circuit Theory I