Slide 1
Ice Energy's Smart Grid
Infrastructure
Brian Parsonnet
VP Technology, CTO
Slide 2
OSIsoft () and Ice Energy (i e)
“You’re
Irrational!!”
i
e
“Get Real!!”
i
+1=0
Slide 3
Ice Bear: A Distributed Energy Resource
• The “Ideal Battery”
– Reduces ~6 kW of On-Peak demand
– Shifts 32 kWh (95%) of A/C energy to off-peak
• 5 MWH of Peak Shift Annually
– Reduces Carbon & NOx Emissions by ~50%
– Consumes the same amount of energy as a standard “DX” HVAC
system
• Provides cooling for 6 – 10 hours
– Nominal settings are from 12 noon to 6 pm (6 hours)
– Runs autonomously, or can be remotely dispatched
• SmartGrid Ready
– Aggregated to Multi-MW scale
– 100% on-line
Slide 4
Ice Bear: Typical Rooftop Installation
Slide 5
kW Demand over 24-Hour Cooling Cycle
Standard Cooling
(8 kW)
“Fan Only” during Ice
Melt (1.7 kW)
Ice Make
Ice Melt Cooling
(.3 kW)
Slide 6
Ice Energy is more than just the Ice Bear
• “The power grid is the largest machine ever made by
mankind”
– Millions of components working together, in true
synchrony, yet fault tolerant
Slide 7
Ice Energy is more than just the Ice Bear
• Utilities have their ways of integrating and
controlling this massive resource
– Secure, complex, tightly integrated control environment
– Historically, a “closed” architecture
• New technologies and drivers are forcing change
– Renewable Sources, Internet, Deregulation, Smart
Devices, Open Architectures…
– Industry response…the Smart Grid.
– How we facilitate integration is critical to large scale
deployment
Slide 8
Ice Energy is more than just the Ice Bear
• Integrating at the device level is difficult
– Burdened with communication, safety, control, and
security issues
• Smart Meter, PCT, RAS, Local Generation examples
• The Ice Bear has avoided these issues, as a device
behind the meter
– Influx of new players to address this problem
• We can anticipate 20 years of development, new
standards, changing industry structure
• Integrating within SCADA is comparatively easy
– Supervisory Control is common, and easily integrated
– Data Historians are a ubiquitous tool for Data Access
Slide 9
Utility Requirements
• “Can we control it?”
– The prospect of controlling 20,000 separate Ice Bears is
daunting
• “Can we rely on it?”
– Availability is critical. And can you really manage 20,000
units?
• “Can you prove it?”
– Information / Data Reporting
• “Does it work with what I have?”
– Regulated and “closed” architecture
• “Will it work with SmartGrid?”
– This is a moving target, with lots of players. How do we fit?
Slide 10
The Utility’s Perspective: SCADA
Slide 11
Ice Energy Utility Solution
• Integrate simply with utility SCADA Systems
(Supervisory Control And Data Acquisition)
– Supervisory Control
• Phase 1: Utility defines standard Ice Bear Operation
• Phase 2: Utility modifies control strategy monthly,
weekly, daily, or hourly
– Provide an interface as per each utility’s needs
– Data Acquisition
• Provide PI connectivity to the utility to serve results
• Connects securely, seamlessly to our server
• Utility middleware is bypassed
– Reducing risk, constraints, complexity, and time
Slide 12
Ice Energy Software Infrastructure
Presentation Layer
Web Portal
Business Logic
Database
Field Data Access
CoolData Controller
Field Assets
User Interface (Computer, hand-held, phone)
Utilities, Users, Field Service, Vendors, Builders…
Visualization, Presentation Logic
Security, Personality
Integration (Utilities, Service, Market Data)
M&V, Diagnostics, Analytics, DER Optimization
Business Automation (Billing, Reporting…)
Data Historian, Customer Configuration & Rules,
Service Records, Tariffs, ETL, …
Data Upload, Control, Programming, Configuration
Ice Bear & 3rd Party Asset Control, Data Logging
HVAC & FMS Integration, Field Network Integ.
Ice Bear & 3rd Party Assets
Slide 13
Ice Energy Software Technologies
Presentation Layer
Web Portal
Business Logic
Database
Microsoft, Apple
LogiFusion, .NET 3.5
Analytica, Ultimus, Microsoft
OSISoft PI, Sharepoint, SQL, Solomon
Field Data Access
SQL Server, Custom Drivers
CoolData Controller
NI Lab View, Lua, C, C++, …
Field Assets
Ice Bear & Customer Assets
Slide 14
Works™ Studio
Designer Tools
• Design
•Model
•Deploy
Works™ Solutions
Application Portal
Works™ Manage
Application Management
Tool
•Manage
•Monitor
LogiWorks™ Application Server
Monitoring Services
Application
Framework
Services
User
Interaction
Services
Information
Services
Works
Portal™
Works
Modules™
Works
Services™
Works
Process™
Works
Integration™
Business
Application
Services
Business
Presentation
Services
Business
Information
Services
Business
Process
Services
Business
Integration
Points
Process
Services
Community
Services
Works™ Messaging
Application Access
Services
Data Central Services
Operational Systems
Works™Office Integration
Works™DataPortal
Works™ System Integration
Enterprise applications
Enterprise data
Device data
Slide 15
CoolData® SmartGrid Controller
•
•
•
•
•
•
•
•
“SmartGrid” ready
Network communications
Local scheduling and remote dispatch
Direct load control for demand
response of other building assets
Real-time status, sub-metering, and
data monitoring of customer
equipment
Performance analysis and automated
diagnostics
Configuration management
Physical & Cyber security
The CoolData Controller is part of the
CoolData Network
•1-Wire Dallas Sensor Network
•NI LabVIEW Application Layer
•Web Server
•OSIsoft, PI Enterprise Layer
Slide 16
OSIsoft’s PI system
• Power Generation, Transmission & Distribution
– 100% of US ISOs
– 50% of the mid and large sized power producers
– Over 200 GW of total 350 GW average power generated &
transmitted in US daily is monitored by PI software
– Over 50% of ITOs
– Heavily involved in SmartGrid
• PI Features
– Can process 20,000,000 continuous data streams
– Stores 250,000 events per second
– Serves 8,000,000 points per second to clients and other applications
• Architecture
– Uptime 99.995% (100% with 3-server collective)
– Shadow Servers for auto-replication at remote locations
Slide 17
OSIsoft PI at Ice Energy
• Ice Energy PI Infrastructure: Reliable, Scalable
–
–
–
–
Heart of Ice Energy’s CoolData Architecture
Supports 30,000 On-line Users
Supports 100 GW of Ice Bear distributed resource
Supports on-site shadow servers at utilities for local data access
• Strategic Relationship
– Ice Energy and OSIsoft entered into an Enterprise Licensing
Agreement Dec ’07
– Unlimited use of OSIsoft technologies
– Proactive monitoring of the PI infrastructure by OSIsoft
– Access to OSIsoft’s Center of Excellence
Slide 18
PI is at the heart of the CoolData system
Portal
Marketing
Data Viewer
Workflow
Monitoring
& Diags
OSIsoft PI
Customer /
Site DB
Service
CoolData
Server
Scheduler,
Optimizer
CoolData
Controller
FMS
Slide 19
Monitoring & Diagnostics
Raw & Cleansed
Data (PI)
Absolute Sensor
Limits (ACE)
Op Mode (ACE)
Modal Sensor
Limits (ACE)
PI Notifications
Application Data
(AF)
KPI’s (ACE)
Auto Fault
Diagnostics
Slide 20
Monitoring
Upper
Bound
Signal
Lower
Bound
Slide 21
Our Infrastructure is SCADA compatible
Presentation Layer
Corporate Apps
PN
Web Portal
Business Logic
Utility
Soltn
Database
PI
Field Data Access
CoolData Controller
Field Assets
Supervisory
Control, M&V
IE Lan
PI
Comm Server
DER Optimizer
Internet, Wireless, BPL
Field Controller
LT
Non-IED
Field Networks
IEDs
Slide 22
Diagnostic Migration
Presentation Layer
Web Portal
Business Logic
Database
Phase 1
• Remote engineer
creates off-line tool
• Results daily / weekly
Phase 2
• Algorithm moves to the
server, applied to all
units
• Results are hourly
Field Data Access
CoolData Controller
Field Assets
Phase 3
• Algorithm moves to the
CoolData Controller
• Results are immediate
Slide 23
DER Control: Phase 1 – Autonomous
Presentation Layer
Web Portal
Business Logic
Database
1) Utility defines operating
schedule
5) Utility dashboard
2) CoolData infrastructure
distributes configurations
4) CoolData M&V
Field Data Access
CoolData Controller
Field Assets
3) Units control themselves,
as per daily schedule
Slide 24
DER Control: Phase 2 – SCADA
Utility issues Presentation
loading order: Layer
• For immediate or scheduled deployment
• Shed or add load
Web
Portal other…
• Scoped by region,
transmission,
• Temporary or permanent changes
Business Logic
DER Optimizer understands:
Database
• GIS and T&D locations
• Maintenance / operational status
• Customer imposed restrictions
Field Data/Access
• Historical performance
expectation
• Communication limitations
• Additional DR assets
6) Utility creates special
loading orders, as needed
10) Utility reporting
7) DER Optimizer
determines method, and
acknowledges orders
9) CoolData M&V
CoolData Controller
Field Assets
8) Units override default
behavior as per request
Slide 25
Large Scale Utility Requirements
•
“Can we control it?”
– Phase 1: Utility provides nothing more than a standard operating schedule
– Phase 2: We provide a Supervisory Control interface to the utility, designed to
meet their specific needs
•
“Can we rely on it?”
– OSIsoft is a proven reliable backbone, already vetted and accepted by the utility
industry.
– Ice Bear reliability has been proven in Utility-sponsored pilots and customer
installations
•
“Can you prove it?”
– You have all your data via a dedicated PI Server at your site.
•
“Does it work with what I have?”
– Our solution integrates PI-to-PI, and does not require integration to SCADA
middleware. In fact, we enable a faster, easier path for connectivity to
additional DSM resources.
•
“Will it work with SmartGrid?”
– Yes. We don’t impose ourselves on the architecture, rather, we are designed to
fill in the gaps and dovetail with what exists.
Slide 26
Thank You
Questions?
Ice Energy's Smart Grid
Infrastructure
Brian Parsonnet
VP Technology, CTO
Slide 2
OSIsoft () and Ice Energy (i e)
“You’re
Irrational!!”
i
e
“Get Real!!”
i
+1=0
Slide 3
Ice Bear: A Distributed Energy Resource
• The “Ideal Battery”
– Reduces ~6 kW of On-Peak demand
– Shifts 32 kWh (95%) of A/C energy to off-peak
• 5 MWH of Peak Shift Annually
– Reduces Carbon & NOx Emissions by ~50%
– Consumes the same amount of energy as a standard “DX” HVAC
system
• Provides cooling for 6 – 10 hours
– Nominal settings are from 12 noon to 6 pm (6 hours)
– Runs autonomously, or can be remotely dispatched
• SmartGrid Ready
– Aggregated to Multi-MW scale
– 100% on-line
Slide 4
Ice Bear: Typical Rooftop Installation
Slide 5
kW Demand over 24-Hour Cooling Cycle
Standard Cooling
(8 kW)
“Fan Only” during Ice
Melt (1.7 kW)
Ice Make
Ice Melt Cooling
(.3 kW)
Slide 6
Ice Energy is more than just the Ice Bear
• “The power grid is the largest machine ever made by
mankind”
– Millions of components working together, in true
synchrony, yet fault tolerant
Slide 7
Ice Energy is more than just the Ice Bear
• Utilities have their ways of integrating and
controlling this massive resource
– Secure, complex, tightly integrated control environment
– Historically, a “closed” architecture
• New technologies and drivers are forcing change
– Renewable Sources, Internet, Deregulation, Smart
Devices, Open Architectures…
– Industry response…the Smart Grid.
– How we facilitate integration is critical to large scale
deployment
Slide 8
Ice Energy is more than just the Ice Bear
• Integrating at the device level is difficult
– Burdened with communication, safety, control, and
security issues
• Smart Meter, PCT, RAS, Local Generation examples
• The Ice Bear has avoided these issues, as a device
behind the meter
– Influx of new players to address this problem
• We can anticipate 20 years of development, new
standards, changing industry structure
• Integrating within SCADA is comparatively easy
– Supervisory Control is common, and easily integrated
– Data Historians are a ubiquitous tool for Data Access
Slide 9
Utility Requirements
• “Can we control it?”
– The prospect of controlling 20,000 separate Ice Bears is
daunting
• “Can we rely on it?”
– Availability is critical. And can you really manage 20,000
units?
• “Can you prove it?”
– Information / Data Reporting
• “Does it work with what I have?”
– Regulated and “closed” architecture
• “Will it work with SmartGrid?”
– This is a moving target, with lots of players. How do we fit?
Slide 10
The Utility’s Perspective: SCADA
Slide 11
Ice Energy Utility Solution
• Integrate simply with utility SCADA Systems
(Supervisory Control And Data Acquisition)
– Supervisory Control
• Phase 1: Utility defines standard Ice Bear Operation
• Phase 2: Utility modifies control strategy monthly,
weekly, daily, or hourly
– Provide an interface as per each utility’s needs
– Data Acquisition
• Provide PI connectivity to the utility to serve results
• Connects securely, seamlessly to our server
• Utility middleware is bypassed
– Reducing risk, constraints, complexity, and time
Slide 12
Ice Energy Software Infrastructure
Presentation Layer
Web Portal
Business Logic
Database
Field Data Access
CoolData Controller
Field Assets
User Interface (Computer, hand-held, phone)
Utilities, Users, Field Service, Vendors, Builders…
Visualization, Presentation Logic
Security, Personality
Integration (Utilities, Service, Market Data)
M&V, Diagnostics, Analytics, DER Optimization
Business Automation (Billing, Reporting…)
Data Historian, Customer Configuration & Rules,
Service Records, Tariffs, ETL, …
Data Upload, Control, Programming, Configuration
Ice Bear & 3rd Party Asset Control, Data Logging
HVAC & FMS Integration, Field Network Integ.
Ice Bear & 3rd Party Assets
Slide 13
Ice Energy Software Technologies
Presentation Layer
Web Portal
Business Logic
Database
Microsoft, Apple
LogiFusion, .NET 3.5
Analytica, Ultimus, Microsoft
OSISoft PI, Sharepoint, SQL, Solomon
Field Data Access
SQL Server, Custom Drivers
CoolData Controller
NI Lab View, Lua, C, C++, …
Field Assets
Ice Bear & Customer Assets
Slide 14
Works™ Studio
Designer Tools
• Design
•Model
•Deploy
Works™ Solutions
Application Portal
Works™ Manage
Application Management
Tool
•Manage
•Monitor
LogiWorks™ Application Server
Monitoring Services
Application
Framework
Services
User
Interaction
Services
Information
Services
Works
Portal™
Works
Modules™
Works
Services™
Works
Process™
Works
Integration™
Business
Application
Services
Business
Presentation
Services
Business
Information
Services
Business
Process
Services
Business
Integration
Points
Process
Services
Community
Services
Works™ Messaging
Application Access
Services
Data Central Services
Operational Systems
Works™Office Integration
Works™DataPortal
Works™ System Integration
Enterprise applications
Enterprise data
Device data
Slide 15
CoolData® SmartGrid Controller
•
•
•
•
•
•
•
•
“SmartGrid” ready
Network communications
Local scheduling and remote dispatch
Direct load control for demand
response of other building assets
Real-time status, sub-metering, and
data monitoring of customer
equipment
Performance analysis and automated
diagnostics
Configuration management
Physical & Cyber security
The CoolData Controller is part of the
CoolData Network
•1-Wire Dallas Sensor Network
•NI LabVIEW Application Layer
•Web Server
•OSIsoft, PI Enterprise Layer
Slide 16
OSIsoft’s PI system
• Power Generation, Transmission & Distribution
– 100% of US ISOs
– 50% of the mid and large sized power producers
– Over 200 GW of total 350 GW average power generated &
transmitted in US daily is monitored by PI software
– Over 50% of ITOs
– Heavily involved in SmartGrid
• PI Features
– Can process 20,000,000 continuous data streams
– Stores 250,000 events per second
– Serves 8,000,000 points per second to clients and other applications
• Architecture
– Uptime 99.995% (100% with 3-server collective)
– Shadow Servers for auto-replication at remote locations
Slide 17
OSIsoft PI at Ice Energy
• Ice Energy PI Infrastructure: Reliable, Scalable
–
–
–
–
Heart of Ice Energy’s CoolData Architecture
Supports 30,000 On-line Users
Supports 100 GW of Ice Bear distributed resource
Supports on-site shadow servers at utilities for local data access
• Strategic Relationship
– Ice Energy and OSIsoft entered into an Enterprise Licensing
Agreement Dec ’07
– Unlimited use of OSIsoft technologies
– Proactive monitoring of the PI infrastructure by OSIsoft
– Access to OSIsoft’s Center of Excellence
Slide 18
PI is at the heart of the CoolData system
Portal
Marketing
Data Viewer
Workflow
Monitoring
& Diags
OSIsoft PI
Customer /
Site DB
Service
CoolData
Server
Scheduler,
Optimizer
CoolData
Controller
FMS
Slide 19
Monitoring & Diagnostics
Raw & Cleansed
Data (PI)
Absolute Sensor
Limits (ACE)
Op Mode (ACE)
Modal Sensor
Limits (ACE)
PI Notifications
Application Data
(AF)
KPI’s (ACE)
Auto Fault
Diagnostics
Slide 20
Monitoring
Upper
Bound
Signal
Lower
Bound
Slide 21
Our Infrastructure is SCADA compatible
Presentation Layer
Corporate Apps
PN
Web Portal
Business Logic
Utility
Soltn
Database
PI
Field Data Access
CoolData Controller
Field Assets
Supervisory
Control, M&V
IE Lan
PI
Comm Server
DER Optimizer
Internet, Wireless, BPL
Field Controller
LT
Non-IED
Field Networks
IEDs
Slide 22
Diagnostic Migration
Presentation Layer
Web Portal
Business Logic
Database
Phase 1
• Remote engineer
creates off-line tool
• Results daily / weekly
Phase 2
• Algorithm moves to the
server, applied to all
units
• Results are hourly
Field Data Access
CoolData Controller
Field Assets
Phase 3
• Algorithm moves to the
CoolData Controller
• Results are immediate
Slide 23
DER Control: Phase 1 – Autonomous
Presentation Layer
Web Portal
Business Logic
Database
1) Utility defines operating
schedule
5) Utility dashboard
2) CoolData infrastructure
distributes configurations
4) CoolData M&V
Field Data Access
CoolData Controller
Field Assets
3) Units control themselves,
as per daily schedule
Slide 24
DER Control: Phase 2 – SCADA
Utility issues Presentation
loading order: Layer
• For immediate or scheduled deployment
• Shed or add load
Web
Portal other…
• Scoped by region,
transmission,
• Temporary or permanent changes
Business Logic
DER Optimizer understands:
Database
• GIS and T&D locations
• Maintenance / operational status
• Customer imposed restrictions
Field Data/Access
• Historical performance
expectation
• Communication limitations
• Additional DR assets
6) Utility creates special
loading orders, as needed
10) Utility reporting
7) DER Optimizer
determines method, and
acknowledges orders
9) CoolData M&V
CoolData Controller
Field Assets
8) Units override default
behavior as per request
Slide 25
Large Scale Utility Requirements
•
“Can we control it?”
– Phase 1: Utility provides nothing more than a standard operating schedule
– Phase 2: We provide a Supervisory Control interface to the utility, designed to
meet their specific needs
•
“Can we rely on it?”
– OSIsoft is a proven reliable backbone, already vetted and accepted by the utility
industry.
– Ice Bear reliability has been proven in Utility-sponsored pilots and customer
installations
•
“Can you prove it?”
– You have all your data via a dedicated PI Server at your site.
•
“Does it work with what I have?”
– Our solution integrates PI-to-PI, and does not require integration to SCADA
middleware. In fact, we enable a faster, easier path for connectivity to
additional DSM resources.
•
“Will it work with SmartGrid?”
– Yes. We don’t impose ourselves on the architecture, rather, we are designed to
fill in the gaps and dovetail with what exists.