SOFTING Industrial Automation GmbH Demonstration Version of PB-DIAG Suite Dale Fittes Technical Specialist HITEX UK July 2010

Download Report

Transcript SOFTING Industrial Automation GmbH Demonstration Version of PB-DIAG Suite Dale Fittes Technical Specialist HITEX UK July 2010

SOFTING Industrial Automation GmbH
Demonstration Version of PB-DIAG Suite
Dale Fittes
Technical Specialist
HITEX UK
July 2010
2
1. Overview of the PB DIAG Software demonstration
2. Download the PB-DIAG Suite Software
3. Installation
4. Opening the Demo Project
5. The Overview Window
6. The Signal Quality Window
7. The Topology Window
8. The Protocol Window
9. The Project Window
10. The Trend Window
11. The Oscilloscope Window
12. The Frame Window
13. Automatic Report Generation
14. Key Features
15. Further Resources
© Softing Industrial Automation GmbH 2010
Contents:
3
 Softing launched the new Profibus Diag Suite and BC-600-PB
worldwide on 01 July 2010.
 A stand-alone demonstration version of Profibus Diag Suite can be
downloaded for free from Softing´s website. This software includes demo
record files, which can be used to show the features of the tool
• You do not need a Profibus network for the presentation
• You can simulate the analysis of typical network failures, without
using a physical network
 This document will help you to install and run the demo software.
© Softing Industrial Automation GmbH 2010
1. Intention of this Document
4
 Uninstall all versions of BC400/450 and PB-T3 before installing
PB-DIAG Suite !
 Use following link to download latest version of PB-DIAG Suite Software:
http://www.softing.com/home/en/industrial-automation/downloads/updates/profibus-dp.php?navanchor=3010238
Note:
If you still want to read PB-T3 record files please
install the PB-T3-Viewer from following link after
deinstallation of PB-T3 software:
ftp://ftp.softing.com/pub/outgoing/jp/PBT3_Viewer_English.msi
Click here for download
© Softing Industrial Automation GmbH 2010
2. Download the PB-DIAG Suite Software
5
Download software
For Setup open file V202_Update.zip or any newer version
Open „Setup_EN.exe“
Follow the instructions of the installation menu:
• Accept terms of license agreement
• Setup type: select „complete“
© Softing Industrial Automation GmbH 2010
3. Installation of PB-DIAG Suite Software
6
 Open Profibus Diagnostic Suite Software with following icon:
 Click on „Show demo project“
© Softing Industrial Automation GmbH 2010
4. Open Demo Project
7
 Select the requested demo file by clicking on the respective bookmarks
 Wait until all 4 windows have opened:
1-Netzstatus, 2-Trend, 3-Oscillogram, 4-Telegramme_Frames
 Now you can start your presentation to the customer.
You do not need a Profibus network for this!
© Softing Industrial Automation GmbH 2010
4. Open Demo Project (contd.)
8
click on „1-Netzstatus_Networkstatus .npb“
First overview with one mouse click. Potential problems are clearly
indicated and distinguished by bus communication or bus physics.
+
Select „Busanfang“ as
test location
4 windows for easy
operation:
• Overview
• Protocol,
• Bus Physics
• Topology
First indication:
or
Green light indicates:
All values are okay
=> Traffic light is green
„Communication is okay“
Green light indicates:
„bus physics are okay“
Result: Everything looks good if measured from the master !
All quality levels above
limit
=> Traffic light is green
© Softing Industrial Automation GmbH 2010
5. Profibus-DIAG Suite
The Overview Window
9
Now select „Busende 15“ as test location
First indication:
There is a problem !
Green light indicates:
All values are okay
=> Traffic light is green
© Softing Industrial Automation GmbH 2010
5. Profibus-DIAG Suite
The Overview Window (contd.)
„Communication is okay“
yellow light indicates:
„bus physics are critical
while bus is running“
All critical values are
marked by red ink:
In this case 5 out of 7
Stations show bad quality
=> Traffic light is yellow
Result: Measurement from other end indicates bad signal quality.
Check Signal Quality for further details !
10
Click on „Signal Quality“
Click on „Signal Analysis
Settings“ for sorting bar graph
Click on „Stations“ and select
„Auto sort by distance“
Result: bars will be sorted acc. to the correct topology for easy interpretation!
This is a unique feature !
© Softing Industrial Automation GmbH 2010
6. Profibus-DIAG Suite
The Signal Quality Window
11
Make Reflections visible:
Select „Busende 15“
A Double Click on bar #2 opens
the oscilloscope view
Select „Busanfang 2“
Result:
Reflections on the bus
Worst situation at „Busende 15“
strong refections
smaller refections
© Softing Industrial Automation GmbH 2010
6. Profibus-DIAG Suite
The Signal Quality Window (contd.)
12
© Softing Industrial Automation GmbH 2010
6. Profibus-DIAG Suite
The Signal Quality Window (contd.)
Localize the failure with
the Oscilloscope:
Select „Busende 15“
Click on bar #2
increase zoom to 62,5 ns
Place cursor 1 to rising flank
Place cursor 2 to distortion
=> Now you can read the distance
from measuring point „Busende
15“ to the point where the
reflection is caused: 22,8 m
Distance 22,8 m
13
Now you can compare the
distances between the
failure and the different
stations:
Click on bar #2
Place cursors
Now distance is 22,8 m
Click on bar #12
Place cursors
Now distance is only 12,5 m
Click on bar #15 (Busend)
Now distance is 0 m and no
distortion
Result: the reflections are caused
at end of bus at #15 (missing terminator).
Consequently no reflections can be seen there.
© Softing Industrial Automation GmbH 2010
6. Profibus-DIAG Suite
The Signal Quality Window (contd.)
14
Click on „Topology“
The topology view gives you:
- the correct sequence of the Profibus nodes
- the distance between the nodes
- the complete cable length
© Softing Industrial Automation GmbH 2010
7. Profibus-DIAG Suite
The Topology Window
15
Click on „Protocol“
Click on Segment View
Life List
Green = data exchange okay
Yellow = slave reports diagnose
Orange = config or param failure
Red = no answer, node is dead
Blue = node not configured in
Master
Bus cycle time
Number of Retries, Diagnose, Restarts
indicate early problems in the network
Log for starting up communication
between master and slaves
=> For further info: Manual PB-DIAG Suite page 27
© Softing Industrial Automation GmbH 2010
8. Profibus-DIAG Suite
The Protocol Window
16
By clicking on the slaves you get
specific info on each device.
Click through the slaves to show
different diagnose messages of
different slaves in clear text (not only
hex strings)
Check GSD-file configuration:
Expected GSD = real GSD ?
If not => configuration failure
Configuration can be seen under
configuration bookmark
Large variation of Station Delay Times
indicates a problem of the slave
Log file of the selected slave
If you prefer the matrix overview,
you may use this as well:
- Click on segment
- Select „Station Statistics“
- You can display all events or select
„retries“, „diagnose“, „set parameters“
for each node
© Softing Industrial Automation GmbH 2010
8. Profibus-DIAG Suite
The Protocol Window (contd.)
17
The „Project Window“ offers an easy
filing of your records
You will find further record files for
demonstration in the „Project View“
- Place the cursor on „projects“ tag:
=>The project view opens
- you may lock the window to avoid
automatic closing
- open „Projects“-filer
- Select e.g. „Diagnose-Repeater.rpb“
with some nice examples of diagnose
messages
© Softing Industrial Automation GmbH 2010
9. Profibus-DIAG Suite
The Project Window
18
click on „2-Trend.qlg“:
Select node
see longtime trend of
quality level of this node
with time stamps
see longtime trend of
critical communication
events with time stamps
© Softing Industrial Automation GmbH 2010
10. Profibus-DIAG Suite
The Trend Window
19
© Softing Industrial Automation GmbH 2010
11. Profibus-DIAG Suite
The Oscilloscope Window
20
click on
„4-Telegramme_Frames“:
This is the Expert Mode !
Here you can trigger and filter
down to the single bit !
You may toggle between
„Frames“ or „Diagnose Mode“
You may define individual
color coding for each type of
frame
By clicking on a frame you get
the decoded contents
© Softing Industrial Automation GmbH 2010
12. Profibus-DIAG Suite
The Frame Window
21
click on:
Test / Create Report
click on „continue“ to create the
report
© Softing Industrial Automation GmbH 2010
13. Profibus-DIAG Suite
The automatically generated Report
22
Toggle between protocol and
signal quality report by
selecting pages
Protocol Report:
- life list and status of nodes
- retries, diagnose, set parameter
for each node
Signal Quality Report:
- min, max, avrg value per node
- bar graphs from all test locations
- oscilloscope charts
© Softing Industrial Automation GmbH 2010
13. Profibus-DIAG Suite
The automatically generated Report (contd)
23
 Quick and simple overview on the network status (includes both
communication and signal quality) with just one mouse click.
PB-DIAG Suite + BC-600-PB are also made for service personel, and not
just for „experts“.
No other tool offers such an easy approach to Profibus Analysis.
 The Diagnose Mode for Protocol Analysis:
-> complete decoding of relevant parameters and diagnose messages
instead of Hex strings.
 Physical Analysis:
-> signal quality bar graphs sorted by real topology BC-600-PB
offers a simple and unique way of analysis without relying on
oscilloscopes.
 -> Unique stand-alone-mode (without PC), enables monitoring of the
network to determine whether detailed diagnose is required.
© Softing Industrial Automation GmbH 2010
14. Profibus-DIAG Suite
Key Features:
24