Liebert ADAPT BX 6kVA
ADAPT BX 6kVA: Product Features
•
•
•
•
•
Reliability
– Double Conversion online
design
– DSP full-digital control
with high output precision
– Can withstand fluctuation
of input mains voltage
Flexibility
– Can be settable for
16/18/20 blocks battery
Energy Efficiency & Low TCO
Real time monitoring
Better battery life
PBX +
UPS Part Numbers
Sr.
No.
Partcode
Item Description
UPS
1
526600063000
Adapt BX , 6kVA UPS
2
326415000600
Parallel Assembly for ADAPT BX 6kVA
3
120031010001
PCA - SNMP Board, DP801 for Adapt BX UPS
4
120031010011
PCA - AS400 Board, for Adapt BX UPS
5
276316002300
PCA - MODBUS Board for Adapt BX UPS
ADAPT BX 6kVA: Technical Specs
Input Parameters
Adapt BX 6kVA
Nominal Input Voltage
230Vac
Permissible Input voltage range
161Vac (-30%) to 276Vac(+20%)
Low Line Transfer
176Vac +/-3% @100 Load
110Vac +/-3%@50 Load
Low Line Comeback
186Vac +/-3% @100 Load
120Vac +/-3%@50 Load
High Line Transfer
300VAc +/-3%
High Line Comeback
290Vac +/-3%
Nominal Input Frequency
50Hz
Permissible input frequency variation
4Hz (46 – 54 Hz)
Input Power Factor
>0.99 at 100%Load
Input Current Distortion: THDi
<10%
Generator rating (kVA)
1.5 times higher
ADAPT BX 6kVA: Technical Specs
Intermediate DC Ckt Parameters
ADAPT BX 6kVA
Types of batteries supported / Backup time
SMF
End of discharge battery bus voltage
SMF : 1.75V/cell ( 192 Vdc for 16 blocks/ 240 Vdc for
20 blocks)
Maximum battery charging Current
4.0Amp
Charging voltage
14.4Vdc +/-1%
Nominal DC Bus Voltage
273V
No. of batteries ( 12V)
16 / 18 / 20nos: SMF
Charging time (to reach 90% of AH)
3 hours recover to 90% capacity
Common Battery
Not available
ADAPT BX 6kVA: Technical Specs
Output Parameters
ADAPT BX 6kVA
Output Power
6kVA / 4.8kW (with 20 battery block)
6kVA / 3.8 kW (with 16 battery block)
Power Factor
0.8 lagging
Nominal O/P Vtg / Vtg Regulation
230Vac / +/-1%
O/P Vtg Distortion for 100% load
<=3% at linear load, <=6% for non-linear
Nominal Output Frequency
50Hz/ 60Hz
Output Frequency tolerance in free run mode
50Hz +/- 0.1Hz or 60Hz +/-0.1Hz
Output frequency synchronization range
46Hz ~54Hz@50Hz / 56Hz~64Hz@60Hz
Output crest factor
3:1 max
Overload Capacity
Ac mode : 100%~110%:10Min, 110%~130%:1Min,
>130% :1 sec.
Battery Mode:
100%~110%:30 sec, 110%~130%:10sec, >130% :1
sec.
Inverter to bypass load transfer time
< 10ms
AC –AC efficiency
89%
ADAPT BX 6kVA: Technical Specs
Possible Configuration
Standalone (Standard Model)
Hot Standby
1 +1 Paralleling
2+1 Paralleling
ADAPT BX 6kVA: Technical Specs
Mechanical Parameters
ADAPT BX
Protection Level
IP 20
Ventilation
Forced – Air Cooled( Air entry at front UPS)
Cable Entry
Back end
Color / Panel Finish
Dark structured grey
Sheet metal thickness
Normally 1.6mm, 2mm as required at stress point
Height
133mm / 3U
Depth
580
Width
438
Weight
17Kg
ADAPT BX 6kVA : Technical Specs
Environmental Parameters
ADAPT BX
Operating Temperature
00C to 400C ( the battery life will down when >25 Deg
C)
Storage Temperature
-250C to 400C ( recharge frequency : Every 3 months,
Charging duration : 1-2 duration) 400C - 450C 400C (
recharge frequency : Every 2 months, Charging
duration : 1-2 duration)
Relative Humidity
0 – 95% RH Non-condensing
Maximum Altitude with full rating
1000 meters
Acoustic noise with rated load at 1 meter
<=55 dBA
Adapt BX : Real Panel View
1. RS 232 Communication Port
2. USB Communication Port
3. Emergency Power Off function
connector (EPO connector)
4. Share current port (only available for
parallel model)
5. Parallel Port ( only available for parallel
model)
6. Intelligent slot
7. Power stage fan
8. Input circuit breaker
9. Input / Output terminal (Refer Dia. 2)
10. External maintenance bypass switch port)
11. Output terminal : connect to mission critical
loads)
12. External battery terminal
13. Utility battery terminal
14. Grounding terminal
ADAPT BX 6kVA: Technical Specs
Communication (Monitoring)
Monitoring using RS232 & USB
Remote Monitoring using SNMP Card /AS400 / MODBUS (optional)
Monitoring
ADAPT BX 6kVA
ADAPT BX : Monitoring
Contd…
Serial
Configuration
• ViewPower Pro Software
Serial
Configuration
• MIN GO (SNMP) Card
(Itemcode:120031010001)
Relay Contacts
Configuration
• AS 400 Card
Modbus
Configuration
• Modbus Communication Card
(CD Avilable with UPS)
(Itemcode : 120081010011)
(Itemcode : 276316002300)
ADAPT BX: 1. Serial Configuration
Requirement:
ViewPower Software CD
View Power Pro Software CD (UPS Management & Shutdown operation software)
Supported OS : x86 (64 bits)-Windows (7.98,2000, 2003,XP, VISTA, 2008,),
RedHat Linux 8 and above, RedHat Enterprise AS3 and above, Suse Linux 10 and
above, Ubuntu 6.10 and above, Fedora 5 and above, Macbox (10.3, 10.4,10.5),
Solaris 10.x64(32 bits)-Windows (7.98,2000, 2003,XP, VISTA, 2008,), Solaris 10.
RS232 Cable
Connectivity: Through RS232 cable.
Features:
Remote parameters monitoring:- Input,
output, bypass and battery
Monitoring of UPS status – On / Off, On Battery, On bypass.
Load (1 PC,Server) OS shutdown.
Event and data logging.
Note: * Optional – Supplied as per customer requirement.
ADAPT BX : 1. Serial Configuration
Features:

UPS On/Off

Scheduling different task; like Battery test, Load shutdown etc.

Alarm notification via Email. To maximum 20 mail users.

Alarm notification via SMS. To maximum 5 cell phone users.

Broadcast* alarms messages on LAN. Supported for ‘Windows’ platform (with Messenger Service)
Note: * To ‘Broadcast’ alarm messages on LAN, Viewpower software need not be installed on all the PCs
(Except to which UPS is directly connected using RS232 cable).
ADAPT BX: 2. SNMP Configuration
Requirement:
MIN GO Card
ViewPower Pro Software
Supported OS : Windows (98,2000, 2003,XP, VISTA, 2008, 7), RedHat Linux 8 and
above, RedHat Enterprise AS3 and above, Suse Linux 10 and above, Ubuntu 6.10
and above, Fedora 5 and above, Macbox (10.3, 10.4,10.5), Solaris 10.
Connectivity: Through Ethernet(LAN) cable.
Features:

Remote parameters monitoring:- Input, output, bypass
and battery parameters can be monitored.

Monitoring of UPS status - On / Off, On Battery, On
bypass. .

Load (200 PC) OS shutdown.

Alarm notification via Email. To maximum 4 mail users.

Event and data logging.
Note: USHA Card can’t be monitored through Winpower Software.
ADAPT BX : SNMP Manager
Intelligent Management Function
Requirement:
SNMP Card(MINGO Card)
Software Requirement :
ViewPower Pro Software
(Monitoring & Shutdown operation)
Features:
 Remote parameters monitoring:- Input, output, bypass and battery
 Data logging, Real time dynamic graphs of UPS Data, warning notification via
audible alarm, broadcast, mobile message, e-mail, & SNMP traps.
 Load OS shutdown.
 Optional Environmental Monitoring detector for temperature, humidity & Smoke
 Password security protection and remote access management
ADAPT BX: 3. Relay Contacts Configuration
Requirement:
AS400 Card
ViewPower Software CD
View Power Pro Software CD (UPS Management & Shutdown operation software)
Supported OS : x86 (64 bits)-Windows (7.98,2000, 2003,XP, VISTA, 2008,),
RedHat Linux 8 and above, RedHat Enterprise AS3 and above, Suse Linux 10 and
above, Ubuntu 6.10 and above, Fedora 5 and above, Macbox (10.3, 10.4,10.5),
Solaris
10.x64(32
bits)-Windows
(7.98,2000,
Solaris 10. Connectivity: DB9 interface is provided
2003,XP,
VISTA,
2008,),
Connectivity: DB9 interface is provided
Features:

Notification* about alarms: Utility failure, UPS failure,
UPS on bypass, Battery low.

Remote UPS shutdown
Note: * Notification means, for particular alarm respective pins of DB9 connector appear short
externally.
ADAPT BX: 4. MODBUS Configuration
Requirement:
Modbus communication Card
Communication Board
RS485
Connectivity:
RS232 standard connectivity
Features:

Parameter Monitoring:- Input, output, bypass
and battery parameters can be monitored.

UPS status can be monitored by BMS
application.
RS232
ADAPT BX: Standards
Competition Analysis
Attribute
Rating
Output Power Factor
Topology
Rectifier
Input Configuration
Input Voltage
Input P.F.
Frequency
THDi
Output Voltage
Emerson ADAPT BX 6Kva
6 kVA
0.9
Online Double
conversion'
IGBT
3/1Ph in & 1Ph out
6kVA
0.8
6kVA
0.8
6kVA
0.9
6VA
0.7
Online Double conversion'
IGBT
1Phase in 1 Phase out
Online Double conversion'
IGBT
1 Ph in 1 Ph out
230 / 415V
0.99
110V - 300V
0.99
230V ( 160V - 280V)
-
Online Double conversion'
IGBT
1 ph in / 1 Ph out
230V (120V - 280V), 415
(250V - 465V)
-
Online Double conversion'
IGBT
1 Ph in /1Ph out
220/230/240Vac ( 176V 276V)
>=99%
40 - 70Hz (auto sensing)
40 - 70Hz, <7%
230V
230V
<3%
90%
<2%
97%
46 - 54 Hz
<5%
230V (=/-1%)
<2% for linear, <5% for Nonlinear
>90%
1+1
SMF
1+1
SMF
105% ~ 130% for 10 min> 130
% for 1 sec
1+1
SMF, LATB
-
THDv
Efficiency
50Hz
45 - 55 Hz
5%
<10%
220V (+/-2%)
230V (+/-1%)
<3% for linear, <5% for <3% for Linear, <6% for Non linear
Non-linear
load
Up to 94%
89%
Overload
Parallel
battery
Ac mode : 100%~110%:10Min,
105%~125% for 5
110%~130%:1Min, >130% :1 sec.
mins,125%~150% 1 min Battery Mode: 100%~110%:30 sec,
200ms for over 150% 110%~130%:10sec, >130% :1 sec.
10& 20 kVA
3+1
2+1
SMF
SMF , LATB
No of Batteries
Battery charger
Operating Temp.
Height (mm)
Width (mm)
Depth (mm)
Weight (kg)
Comunication
APC, Smart UPS RC 6000VA Eaton MX (5 -20kVA) MX
(SRC 6000UXI..)
Frame
Liebert ITA
16block
4Amp
0-40 Deg.C
85 (2U)
435
640
17
16/18/20 blocks
4 Amp
0-40 Deg.C
133 (3U)
438
580
17
20blocks
0-40 Deg.C
440
89
678
15
0-40 Deg.C
690
444.5
735
-
USB, SNMP/AS400
USB/RS232, SNMP / AS400
DB-9 RS232, Smart slot
RS 232,SNMP
Numeric DHP E 11 60
20 blocks
4 Amp
0-40 Deg..C
710
260
555
92kg
RS232, SNMP / AS400 /HTTP
(optional)