INSTRUCTIONS
 Click on the slide show ICON in the lower left hand corner of this screen to start the slide
show.
 A question will appear and stay on the screen for 2 minutes. The
question will then be replaced with the correct answer and code
reference. This process will repeat until you reach a slide with a
stop sign. You can then click on the slides and the questions and
answers will be repeated without the timer so you can look up the
answers or take notes.
 Do not worry about writing down the answers until after the timed
portion of the program.
 Concentrate on finding the answer and improving your speed
using the NEC. This drill is focused on changes to the 2011 NEC.
(C) COPYRIGHT 2008 TED "SMITTY" SMITH
2
1. Conductors for small motors shall not be smaller than _________ AWG unless
otherwise permitted.
Answer 1.
14 AWG
430.22(G)
2. The conductors of PV output circuits and inverter input and output circuits shall be
identified at all points of __________.
2. Answer
Termination, connection and splices
690.4(B)(2)
3. Conductors in Type PLTC cables used for Class 2 thermocouple circuits shall be
permitted to be any of the materials used for _____________________.
3. Answer
Thermocouple extension wire
725.154(I)
4. Cable trays containing conductors rated over 600 volts shall have a permanent,
legible warning notice carrying the wording
“_________________________________” placed in a readily visible position on all
cable trays with spacing of warning notices to exceed 3 m (10 ft).
4. Answer
“ DANGER---------HIGH VOLTAGE---------KEEP AWAY”
392.18(H)
5. Bonding jumpers at the service shall be used around __________________, such
as reducing washers or oversized, concentric or eccentric knockouts.
5. Answer
Impaired connections
250.92(B)
6. What is the ampacity of a 10 AWG THHN copper conductor installed in a raceway
with a total of 7 current carrying conductors? The raceway is EMT and it is
installed across a rooftop that is subject to direct sunlight. The ambient
temperature of the area is 89.7 degrees F. The conduit is installed 9 “ above the
rooftop.
6. Answer
40*.70*.82= 22.96 amperes
7. If a 1 ½” x 4” octagon box contains a stud and a cable clamp, the number of wires
must be reduced to ______________ if using 14 AWG conductors.
 A. four
 B. five
 C. six
 D. seven
7. Answer
B. Five 310.16(B)
8. A pull box containing a U- pull that has two 3” schedule 80 PVC conduits entering
from the bottom will have a vertical measurement of at least
__________________.
 A. 21
 B. 24
 C. 26
 D. 30
8. Answer
A 21”
314.28
3 x 6= 18 + 3= 21”
9. A box containing two 12 THHN grounding conductors and two 12 THW conductors
will have a required volume of _________ cubic inches?
 A. 4.5
 B. 5
 C. 6.75
 D. 9
9. Answer
C. 6.75 cubic inches
314.16(B)
10. A standard sized metal device box that contains two switches, one receptacle,
and three 14/2 NM cables with grounds is required to be
______________________.
 A. 3”x2” x2 ¼”
 B. 3” x 2” x 2 ¾”
 C. 3” x 2” x 2”
 D. 4” x 2 1/8” x 2 1/8”
10. Answer
C 3” x 2” x 2”
314.16(B)
11. For feeders operating in excess of 600V several tests must be performed before
energization and a test report must be delivered to ____________________ prior
to energization.
11. Answer
The authority having jurisdiction
225.56(B)
12. Incidental metal parts on central vacuum outlet assemblies such as screws or
rivets installed into or on insulating material ______________________ be
considered likely to become energized.
 A. Shall
 B. Shall not
12. Answer
B. Shall Not
422.15 (C)
13. Truck space branch circuit supplied loads shall be considered to be
________________.




A. Non- continuous
B. Non simultaneous
C. Continuous
D. Non coincidental
13. Answer
C. Continuous
626.21(D)
14. Ground fault protection of equipment shall be provided for fixed outdoor electric
deicing and snow melting equipment.
 A. True
 B. False
14. Answer
A. True
426.28
15. Receptacle face plated mounted inside a box having a recess mounted
receptacle shall effectively _____________the opening and seat against the
mounting surface.
15. Answer
Close
406.6
16. A battery powered lighting unit in an anesthetizing location shall be permitted to
be wired to the ____________ in the area and connected ahead of any local
switches.
 A. Equipment branch circuits
 B. Critical lighting circuits
 C. Life Safety circuits
 D. None of the above
16. Answer
B. critical lighting circuits
517.63(A)
17. If the source of a separately derived system and the first disconnecting means are
located in separate enclosures, a supply side bonding jumper shall be installed
with the _____________________ from the source enclosure to the first
disconnecting means.
17. Answer
Circuit conductors
250.30(A)(2)
18. A 24 VDC control wiring circuit is installed using THHN conductors. It is installed in
an EMT along with a 120 VAC power circuit and a 480 VAC, three phase,
equipment circuit. All of the conductors for the 120 VAC and 480 VAC circuits are
THWN. Is this an acceptable installation?
18. Answer
Yes
300.3(C)(1)
19. All switchboards and panelboards supplied by feeders in other than one or two
family dwellings shall be marked to indicate the device or equipment
___________________________.
19. Answer
Where the power supply originates
408.4(B)
20. A listed ______________________ fitting or other approved means shall be used
where a raceway crosses a structural joint intended for expansion, contraction or
deflection, used in buildings, bridges, parking garages, or other structures.
20 Answer
Expansion/deflection fitting
300.4(H)
CLICK THE MOUSE BUTTON TO CONTINUE TO
THE UNTIMED REVIEW. YOU WILL NEED TO
CLICK EACH SLIDE TO ADVANCE TO THE NEXT
SLIDE.
1. Conductors for small motors shall not be smaller than _________ AWG unless
otherwise permitted.
Answer 1.
14 AWG
430.22(G)
2. The conductors of PV output circuits and inverter input and output circuits shall be
identified at all points of __________.
2. Answer
Termination, connection and splices
690.4(B)(2)
3. Conductors in Type PLTC cables used for Class 2 thermocouple circuits shall be
permitted to be any of the materials used for _____________________.
3. Answer
Thermocouple extension wire
725.154(I)
4. Cable trays containing conductors rated over 600 volts shall have a permanent,
legible warning notice carrying the wording
“_________________________________” placed in a readily visible position on all
cable trays with spacing of warning notices to exceed 3 m (10 ft).
4. Answer
“ DANGER---------HIGH VOLTAGE---------KEEP AWAY”
392.18(H)
5. Bonding jumpers at the service shall be used around __________________, such
as reducing washers or oversized, concentric or eccentric knockouts.
5. Answer
Impaired connections
250.92(B)
6. What is the ampacity of a 10 AWG THHN copper conductor installed in a raceway
with a total of 7 current carrying conductors? The raceway is EMT and it is
installed across a rooftop that is subject to direct sunlight. The ambient
temperature of the area is 89.7 degrees F. The conduit is installed 9 “ above the
rooftop.
6. Answer
40*.70*.82= 22.96 amperes
7. If a 1 ½” x 4” octagon box contains a stud and a cable clamp, the number of wires
must be reduced to ______________ if using 14 AWG conductors.
 A. four
 B. five
 C. six
 D. seven
7. Answer
B. Five 310.16(B)
8. A pull box containing a U- pull that has two 3” schedule 80 PVC conduits entering
from the bottom will have a vertical measurement of at least
__________________.
 A. 21
 B. 24
 C. 26
 D. 30
8. Answer
A 21”
314.28
3 x 6= 18 + 3= 21”
9. A box containing two 12 THHN grounding conductors and two 12 THW conductors
will have a required volume of _________ cubic inches?
 A. 4.5
 B. 5
 C. 6.75
 D. 9
9. Answer
C. 6.75 cubic inches
314.16(B)
10. A standard sized metal device box that contains two switches, one receptacle,
and three 14/2 NM cables with grounds is required to be
______________________.
 A. 3”x2” x2 ¼”
 B. 3” x 2” x 2 ¾”
 C. 3” x 2” x 2”
 D. 4” x 2 1/8” x 2 1/8”
10. Answer
C 3” x 2” x 2”
314.16(B)
11. For feeders operating in excess of 600V several tests must be performed before
energization and a test report must be delivered to ____________________ prior
to energization.
11. Answer
The authority having jurisdiction
225.56(B)
12. Incidental metal parts on central vacuum outlet assemblies such as screws or
rivets installed into or on insulating material ______________________ be
considered likely to become energized.
 A. Shall
 B. Shall not
12. Answer
B. Shall Not
422.15 (C)
13. Truck space branch circuit supplied loads shall be considered to be
________________.




A. Non- continuous
B. Non simultaneous
C. Continuous
D. Non coincidental
13. Answer
C. Continuous
626.21(D)
14. Ground fault protection of equipment shall be provided for fixed outdoor electric
deicing and snow melting equipment.
 A. True
 B. False
14. Answer
A. True
426.28
15. Receptacle face plated mounted inside a box having a recess mounted
receptacle shall effectively _____________the opening and seat against the
mounting surface.
15. Answer
Close
406.6
16. A battery powered lighting unit in an anesthetizing location shall be permitted to
be wired to the ____________ in the area and connected ahead of any local
switches.
 A. Equipment branch circuits
 B. Critical lighting circuits
 C. Life Safety circuits
 D. None of the above
16. Answer
B. critical lighting circuits
517.63(A)
17. If the source of a separately derived system and the first disconnecting means are
located in separate enclosures, a supply side bonding jumper shall be installed
with the _____________________ from the source enclosure to the first
disconnecting means.
17. Answer
Circuit conductors
250.30(A)(2)
18. A 24 VDC control wiring circuit is installed using THHN conductors. It is installed in
an EMT along with a 120 VAC power circuit and a 480 VAC, three phase,
equipment circuit. All of the conductors for the 120 VAC and 480 VAC circuits are
THWN. Is this an acceptable installation?
18. Answer
Yes
300.3(C)(1)
19. All switchboards and panelboards supplied by feeders in other than one or two
family dwellings shall be marked to indicate the device or equipment
___________________________.
19. Answer
Where the power supply originates
408.4(B)
20. A listed ______________________ fitting or other approved means shall be used
where a raceway crosses a structural joint intended for expansion, contraction or
deflection, used in buildings, bridges, parking garages, or other structures.
20 Answer
Expansion/deflection fitting
300.4(H)