Application Guidelines for FMC
Download
Report
Transcript Application Guidelines for FMC
75 years of excellence
NEMA RV 3
Application & Installation Guidelines For Flexible & Liquid Tight Flexible Metal Conduits
www.nema.org
75 years of excellence
Application Guidelines for FMC
Construction of FMC
Grounding and Bonding
Uses Permitted and Not Permitted
www.nema.org
75 years of excellence
Construction for FMC
Constructed in accordance with NEC
Complies with safety requirements of UL1
Interlocked corrosion resistant steel or Aluminum
strip
www.nema.org
75 years of excellence
Picture Example for FMC
www.nema.org
75 years of excellence
Diagram Example for FMC
Cross-section view illustrating interlocking construction
www.nema.org
75 years of excellence
Grounding and Bonding for FMC
Permitted for bonding
When installed with listed fittings and;
Flexibility is not required after installation and;
When installed according to NEC Articles 348 and 250 and;
Protected by overcurrent device rated 20 Amperes or less.
Limited to 6’ lengths when used for bonding (see NEC
250.118 (5))
Grounding conductor required if FMC
installed for flexible equipment or
when used in lengths greater than 6’.
Grounding and bonding continued in slide 7…
www.nema.org
75 years of excellence
Product Marking for FMC
Manufacturer’s designation
UL Logo
Conduit type
Reduced wall (RW)
Extra reduced wall (XRW)
Material type
Aluminum (AL)
Steel (No Mark Required)
www.nema.org
75 years of excellence
FMC Marking Example
www.nema.org
75 years of excellence
Uses Permitted for FMC
Exposed and concealed locations – NEC 348.10
Dry locations only
Branch circuits and feeders
Ducts or plenums for environmental air
300.22(B) limits to 4’ length
300.22(C) no length limit
Under raised floors for computer rooms
Lighting whips and motor leads
These uses are not all inclusive, but serve as guidelines
www.nema.org
75 years of excellence
Uses Not Permitted for FMC
NEC 348.12
Wet locations
2008 NEC removed exceptions
Hoistways except as permitted in 620.21(A)(1)
Storage battery rooms
www.nema.org
75 years of excellence
Uses Not Permitted – cont. for FMC
Hazardous locations except 501.10(B) and 504.20
Where conductors are exposed to deteriorating material
Underground or in concrete
Where subject to physical damage
www.nema.org
75 years of excellence
Reference Articles
Reference UL 1 and NEC
NEMA RV 3 1.4.1 – National Electric Code
NEMA RV 3 1.4.2 – Related NEC Articles
NEMA RV 3 1.4.3 – UL Standards
Guide information page: http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/index.htm
White book “Guide Information for Electrical Equipment”
www.nema.org
75 years of excellence
Application Guidelines for LFMC
Construction of LFMC
Grounding and Bonding
Marking
Uses Permitted and Not Permitted
www.nema.org
75 years of excellence
Construction for LFMC
In accordance with NEC
Complies with safety requirements of UL360
Interlocked zinc-coated corrosion resistant steel
Trades sizes are 3/8” through 4”
Sizes 3/8” – 1 ¼” have bonding strip enclosed by
convolution
www.nema.org
75 years of excellence
Construction – cont. for LFMC
Jacket material is liquid-tight, non metallic
Jacket specifications governed by UL 360
Fittings for LFMC are constructed to UL 514B
www.nema.org
75 years of excellence
Picture example for LFMC
Cut-away view of Liquidtight Flexible Metal Conduit to illustrate construction
www.nema.org
75 years of excellence
Diagram Example for LFMC
Cross-section view illustrating interlocking construction
www.nema.org
75 years of excellence
Grounding and Bonding for LFMC
LFMC trade sizes 3/8” – 1 ¼” permitted for
equipment bonding:
When installed with listed fittings and;
Flexibility is not required after installation and;
When installed according to NEC Articles 350 and 250
and;
Only in 6’ lengths or less
Sizes 3/8” – 4” may be installed in unlimited
lengths provided:
A separate grounding conductor is installed
And installed according to NEC Articles 350 and 250
www.nema.org
75 years of excellence
Surface Print for LFMC
Manufacturer’s name or location
Trade size
Temperature rating
Burial rating (when applicable)
Flame rating (when applicable)
Current rating (for equipment bonding according to NEC
article 250)
www.nema.org
75 years of excellence
Uses Permitted for LFMC
Exposed and concealed locations as follows:
When flexibility or protection from liquids, vapors or
solids are required
As permitted by 501.10(B), 502.10, 503.1 and 504.20
Other hazardous classified locations per 553.7(B)
Direct burial where listed & marked for that purpose
If LFMC is marked direct burial it is also suitable for use
in concrete or in poured concrete
The following are references throughout the NEC code:
www.nema.org
75 years of excellence
Uses Permitted –cont. for LFMC
Outside branch circuits and feeders
Under raised floors for computer rooms
Lighting whips and motor leads
These uses are not all inclusive, but serve as
guidelines
References throughout the NEC Code:
www.nema.org
75 years of excellence
Uses Not Permitted for LFMC
Where subject to physical damage
Where operating conditions cause temperatures to
exceed material ratings
See NEC 350.12 for prohibited uses
www.nema.org
75 years of excellence
Reference Articles for LFMC
NEMA RV 3 2.4.1 – National Electric Code
NEMA RV 3 2.4.2 – Related NEC Articles
NEMA RV 3 2.4.3 – UL Standards
Guide information page:
http://database.ul.com/cgibin/XYV/template/LISEXT/1FRAME/index.htm
White book “Guide Information for Electrical
Equipment”
www.nema.org
75 years of excellence
Installation Guidelines
Installation Considerations
Securing & Supporting FMC & LFMC
Terminating FMC
www.nema.org
75 years of excellence
Installation Considerations for FMC & LFMC
Minimum centerline bend radius
Table 2 chapter 9 NEC
“Other bends” column
Maximum # of bends between pull points
Not to exceed (4) - 90 degree bends
Or a total of 360 degrees (any direction)
www.nema.org
75 years of excellence
Lateral Offsets
•Use tables for length
•Lateral offset
•Example below
Offset Table 2
3/4" Trade Size
0.75
Overall Length of Conduit for Given Offset and Lateral Distance
"B" (in.)
Lateral Dist.
"R" Offset Distance (in.)
1.0
1.5
2
2.5
3.0
4.0
5.0
6.0
8.0
10.0
7
7.6
8
8.3
8.7
9
9.2
9.5
9.8
10
10.2
10.4
10.6
11.0
11
11.1
11.3
11.5
11.8
12
12.1
12.2
12.4
12.7
13.0
13
13.1
13.2
13.4
13.6
13.8
14.4
14
14.1
14.2
14.3
14.5
14.7
15.3
15
15.1
15.2
15.3
15.5
15.6
16.1
16.7
20
20.0
20.1
20.2
20.3
20.4
20.7
21.2
21.7
22.9
24.4
25
25.0
25.1
25.1
25.2
25.3
25.6
25.9
26.2
27.2
28.3
30
30.0
30.1
30.1
30.2
30.2
30.4
30.7
31.0
31.7
32.7
www.nema.org
75 years of excellence
Vertical Loop
–Vertical loop w/offset
–L=(8xTS)+(1.57xA) +T/2+F
•L = Overall length
•TS = Trade size
•A = Horizontal dist between fittings
•T = Travel distance
•F = Offset
–This accounts for suggested tangent
length
www.nema.org
75 years of excellence
Installation Considerations – cont. for
FMC & LFMC
Fittings should be tightened properly
Section 3.3, tables 1 and 2 of NEMA guidelines for
proper torquing values
Closely follow manufacturer's instructions
www.nema.org
75 years of excellence
Securing & Supporting FMC & LFMC
According to NEC 348.30 & 350.30
Both must be supported and secured every 4.5’ or less
Must be secured within 12” of each termination
These support requirements are waived if needed
for flexibility or for luminaries
www.nema.org
75 years of excellence
Securing & Supporting – cont. for FMC & LFMC
Both may be unsupported when:
Conduit is fished between access points through concealed
spaces in finished buildings or structures and supporting is
impractical
Flexibility is required
• 3’ maximum for LFMC
• 3’ maximum for FMC ½” through 1¼”
• 4’ maximum for FMC 1½” through 2”
• 5’ maximum for FMC 2½” and larger
Used on luminaries; 6’ maximum
Run through non-vertical framing members with distances
not exceeding 4½’
www.nema.org
75 years of excellence
Terminating FMC
Fitting Selection requires knowing:
Trade size or metric designator
Type of FMC, (standard, reduced or extra-reduced
wall)
Type of metal (steel or aluminum)
www.nema.org
75 years of excellence
Conduit Preparation for FMC & LFMC
Square the cut end of the metal conduit
Insert conduit flush with fitting end stop
Ensure seating of clamp on conduit before torquing
Be careful torquing the securement screw
Always follow the manufacturer's instructions
Follow recommendations from NEMA FB 2.20, “Selection and
Installation guidelines for Fittings for use with Flexible
Conduit and Cable”
www.nema.org
75 years of excellence
Cutting Conduit for FMC
Rotary armor cutters
Hacksaw
Cut one convolution at a 60 degree angle
Diagonal wire cutters
Brake the conduit or twist open
Then cut with the cutters
www.nema.org
75 years of excellence
Cutting Conduit for LFMC
Hacksaw
Blade should have 32 teeth per inch
Band saw with ½” X .025 Blade with 24 teeth per
inch at 350 ft/min
www.nema.org
75 years of excellence
Fitting Attachment for FMC
Always make sure the conduit is inserted
completely to the smooth end stop
When using a clamp type fitting, be sure the
fitting seats between the convolutions
Hand tighten the fitting screws and slightly rotate
the conduit in the fitting
If there are two screws, tighten alternately to
provide even pressure.
Table 1 in NEMA RV 3 shows standard torque
values for FMC fittings
www.nema.org
75 years of excellence
Terminating for LFMC
Fitting Selection requires knowing:
Trade size or metric designator
The environment of installation
Conduit preparation
Square the end of the conduit
Fully insert conduit to end stop
Ensure jacketing is not cut or ripped
Always follow the manufacturers instructions
Follow recommendations from NEMA FB 2.20, “Selection and
Installation guidelines for Fittings for use with Flexible
Conduit and Cable”
www.nema.org
75 years of excellence
Fitting Attachment for LFMC
Squared end must be fully inserted into ferrule
Assembly methods vary for LFMC fittings, follow
manufacturer's instructions
Table 2 in NEMA RV 3 show standard torque
values for LFMC fittings
www.nema.org
75 years of excellence
Unthreaded Entries
Hand tighten the threaded portion of fitting to
secured box using a locknut
Assemble nut, gland and ferrule onto conduit
After securely tightening the gland nut to the
threaded body, finish tightening the locknut ¼
turn
www.nema.org
75 years of excellence
Fitting Example
www.nema.org
75 years of excellence
Verification of Installation
• Conduit shall be properly terminated at boxes
• Conduit shall be properly secured and supported
• Conduit shall not show evidence of damage or physical
abuse
www.nema.org