Fan Peformance April 2008

Download Report

Transcript Fan Peformance April 2008

Fan Performance
Mark Stevens
Director of Laboratory Services
AMCA International
The International Authority on Air System Components
Fan Testing for Air Performance
The International Authority on Air System Components
AMCA Standard 210
Piezometer Ring
Fan Static Pressure
Nozzles
Fan Airflow
Test Fan
Auxiliary Fan
The International Authority on Air System Components
AMCA 210 Test Results
800
2.5
700
2
500
1.5
400
1
300
200
0.5
100
0
0
0
2
4
6
8
Air Flow, Q
The International Authority on Air System Components
10
12
Power, H
Pressure, P
600
Fan Laws for Speed Change
QC =
( )
( )
( )
NC
N
Q
Q, Fan Airflow Rate
P
P, Fan Pressure
H
H, Fan Power
2
PC =
NC
N
3
HC =
NC
N
The International Authority on Air System Components
10% Speed Change
800
2.5
700
2
600
500
1.5
400
1
300
200
0.5
10% More Q
100
0
0
0
2
4
6
8
Air Flow, Q
The International Authority on Air System Components
10
12
14
Power, H
Pressure, P
33% More H
AMCA Standards 500-D & -L
Test Damper
Piezometer Ring
Damper Pressure Drop
Nozzles
Damper Airflow
Auxiliary
Fan
The International Authority on Air System Components
AMCA
Test Point
Results
Fan500-D
Operating
700
600
500
Pressure, P
Operating Point
400
300
200
100
0
0
2
4
6
8
Air Flow, Q
The International Authority on Air System Components
10
12
Speed Change
800
700
600
New Operating Point
Pressure, P
500
New speed
Operating Point
400
300
200
100
0
0
2
4
6
Air Flow, Q
8
The International Authority on Air System Components
10
12
14
Damper Opening
700
600
Pressure, P
500
Operating Point
400
New Operating Point
300
New System
200
100
0
0
2
4
6
8
Air Flow, Q
The International Authority on Air System Components
10
12
System Effect
• Installed duct configuration does not
match tested duct configuration
• Detrimental effect on fan air performance
due to adverse flow conditions at the inlet
or outlet of a fan
The International Authority on Air System Components
Installation Type D
Ducted Inlet / Ducted Outlet
Piezometer Ring
Fan Static Pressure
Nozzles
Fan Airflow
Test Fan
Auxiliary Fan
Plenum
Plenum
Installed Fan
The International Authority on Air System Components
AMCA Catalog Ratings
• “Performance certified is for
installation type:
◦
◦
◦
◦
A: Free inlet, Free outlet”
B: Free inlet, Ducted outlet”
C: Ducted inlet, Free outlet”
D: Ducted inlet, Ducted outlet”
The International Authority on Air System Components
System Effect
• Even when the tested duct
configuration matches the installed duct
configuration, improper duct design can
introduce adverse flow conditions
The International Authority on Air System Components
Elbow Example
The International Authority on Air System Components
Detailed Plenum Example
Plenum
The International Authority on Air System Components
Detailed Plenum Example
• Centrifugal Fan
• Airflow Rate
Cutoff
◦ 14.4 m3/s
Blast Area
Outlet Area
• Blast Area/Outlet Area
◦ 0.6
• Velocity
◦ 14.4 m/s
The International Authority on Air System Components
Detailed Plenum Example
E-F
duct friction at 5000CMH (Q)
E
contraction loss-plenum to duct
E
PS energy required to create velocity at E
D
PV loss (also PT loss) at D as result of air velocity decrease
747 Pa (duct design)
50 Pa (part of duct system)
125 Pa (part of duct system)
0 Pa
PS does not change from duct to plenum at D
C-D outlet duct on fan as tested
0 Pa
--------------------
REQUIRED Fan PS
922 Pa
The International Authority on Air System Components
Detailed Plenum Example
D-E duct friction at 5000CMH (Q)
D
contraction loss-plenum to duct
D
PS energy required to create velocity at D
B-C SEF
747 Pa (duct design)
50 Pa (part of duct system)
125 Pa (part of duct system)
149 Pa
B-C PV loss (also PT loss) at C as result of air velocity decrease
0 Pa
PS does not change from duct to plenum at C
------------------
REQUIRED Fan PS
1071 Pa
The International Authority on Air System Components
Detailed Plenum Example
Calculation of SEF of 149 Pa
From AMCA Publication 210
No
Duct
From Figure 8.3
12%
Effective
Duct
25%
Effective
Duct
50%
Effective
Duc t
100%
Effective
Duct
Outlet Duct
Blast Ar ea
Sys tem E ffe ct C urve
O utle t Area
100% Effective Duct Length
0 .4
P
R -S
U
W
--
0 .5
P
R -S
U
W
--
0 .6
R -S
S -T
U- V
W- X
--
0 .7
S
U
W -X
--
--
0 .8
T-U
VW
X
--
--
0 .9
W -W
W -X
--
--
--
1 .0
--
--
--
--
--
The International Authority on Air System Components
Using line R from Figure 7.1
14.4 m/s
The International Authority on Air System Components
Plenum Example from AMCA 201
Assuming:
• Use of the same fan for both systems
• Can attain both operating points with a
change in speed
• The increased in power consumption to
overcome System Effect is about 25%
◦ (1071/922)0.5 = 1.08 (Fan Law for pressure)
◦ 1.083 = 1.25 (Fan Law for Power)
The International Authority on Air System Components
Ducted Fan
Fan as Tested
C-D duct friction
A
free inlet
B-C outlet with straight duct attached for 2 or more diam.
750 Pa (duct design)
0 Pa (no SEF)
0 Pa (no SEF)
--------------------
REQUIRED Fan PS
750 Pa
The International Authority on Air System Components
Ducted Fan
Exhaust System
A
A-B
B
C
E
Entrance loss-sharp edge duct
Duct friction at 5000CMH
SEF 1 (Elbow at Inlet)
SEF 2 (Obstruction)
SEF 3 (Abrupt Discharge)
REQUIRED Fan Ps
100 Pa (duct design)
750 Pa (duct design)
150 Pa
50 Pa
150 Pa
------------------
1200 Pa
The International Authority on Air System Components
Deficient Fan/System
The International Authority on Air System Components
Speed Changes
• Before Increasing Speed
◦ Check with the manufacturer for max safe
operating speed
◦ Determine expected power increase
• Motor size
• Electric Service
◦ Expect more noise
The International Authority on Air System Components
Rules of Thumb
• Minimum 2.5 duct diameters on Outlet
• Minimum 3 to 5 duct diameters on Inlet
• Avoid inlet swirl
The International Authority on Air System Components
Recommendations
• Allow enough space in the building design
to allow for appropriate fan connections to
the system
The International Authority on Air System Components
Recommendations
• Use allowances in the design calculations
when space or other factors dictate less
than optimum arrangement of the fan
outlet and inlet connections
The International Authority on Air System Components
Recommendations
• Include adequate allowance for the effect
of all accessories and appurtenances on
the performance of the system and the fan
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
The International Authority on Air System Components
Thank you
AMCA International, Inc.
30 W. University Drive
Arlington Heights, IL 60004
USA
Tel: +1 847 394 0150 Fax: +1 847 253 0088
www.amca.org
Mark Stevens - [email protected]
The International Authority on Air System Components