Transcript Trafag – Sensors and Controls
SF
6
Gas Density Monitoring
Very low temperature and liquefaction situation with Trafag 87X6 SF
6
gas density monitor
05.02.07/ nip
The Reference Gas Principle (Theory) SF 6 filled switchgear SF 6 filled reference chamber DM
05.02.07/ nip
separating membrane The temperatures of the gas in the switchgear and the gas in the reference chamber of 87x6 density monitor are „the same“ (depends on the mounting situation) Conclusion: „fully temperature compensation over the whole temperature range“
The Density Monitor with Reference Chamber (Picture shows the “older” 87x0 density monitor generation)
...inside the monitor Tappet moves when SF 6 leaks from tank and triggers alarm switch Reference chamber filled with gas SF 6 gas inlet (connection to tank) 05.02.07/ nip
Behavior of bimetalic compensated Systems
Isochoren von xyz No. 06397
8.000bar
7.500bar
7.000bar
6.500bar
6.000bar
5.500bar
5.000bar
4.500bar
4.000bar
Contact 1, falling (bimetal comp, non-Trafag) True isochor Tolerance band of Trafag DM for calibration Schalter 1 sinkend Contact 2, falling Isochore 6,4 bar +8 kPa -8 kPa Tolerance band of Trafag DM for calibration
The accuracy of the alarm levels
3.500bar
-40.0°C -30.0°C -20.0°C 3.000bar
-10.0°C 0.0°C 10.0°C 20.0°C 30.0°C 40.0°C 50.0°C 60.0°C 05.02.07/ nip
05.02.07/ nip
Density Monitor at temperature below -55C
•
Due to the mechanical system the density monitor will still operate below -55 °C
•
May be the specifications like accuracy and so on are out of the from Trafag specified values on the datasheets
•
The tolerances of the mechanical system may be are to high for a proper function
05.02.07/ nip
Liquefaction?
•
The reference chamber of 87x6 density monitor is filled at previous alarm density level (1. stage)
•
In regular operation the density at switch breaker is higher (somewhere between filling pressure and previous alarm level) as previous alarm level in reference chamber of 87x6 density monitor
•
Therefore, the liquefaction in switch breaker starts at higher temperature (that means earlier) as in the reference chamber of 87x6 gas density monitor
• •
Benefits: Small local liquefaction in the switch breaker will not be detected by the 87x6 density monitor Serious liquefaction which can create a critical situation for the switch breaker get detected by the 87x6 density monitor