Transcript Document
Integrating Sensor Data with Simulation Models for Data Center Optimization and Energy Reduction Paul Bemis President Applied Math Modeling Inc 1 Integrating Sensor Data with Simulation Models for Data Center Optimization • • • As the cost of sensors and simulation technologies continue to decline, there is now an opportunity to create a highly accurate predictive model of the data center based on measured data including temperature, humidity and pressure at a reasonable cost. The predictive model can then be used to determine the optimal operational point for minimizing energy consumption of a given data center. In this session we will review a case study that used this methodology to find the optimal operating point and illustrate the steps to create the model and used to find the minimum energy consumption while still maintaining an N+1 design. 2 Outline The Role of sensors in the data center Provides current state of operations Alert operators of change in state Allow energy optimization The Role of CFD in the data center Validate initial design Predict optimal operating point for current design Predict future condition or failure mode operation (DR modeling) 3 Outline (continued) Combining Sensor Data with CFD Modeling Sensors provide the current state These can be used to set up the CFD model And can be used to validate the CFD model The CFD model can then predict the optimal operating point Sensors can then be used to maintain it. And the data can be integrated into DCIM 4 Data Center Metrics Return Temperature Index (RTI) = Rack Flow Rate x 100 Air Handler Flow Rate or Return Temperature Index (RTI) = Air Handler Delta T Rack Delta T x 100 Interpretation of RTI RTI is a measure of net by-pass air or net recirculation air in the data center Interpretation RTI Value Balanced 100% Net Rack Recirculation > 100% Net By-Pass Airflow < 100% Return Temperature Index (RTI) is a Trademark of ANCIS Incorporated (www.ancis.us). All rights reserved. Used under authorization 5 Rack Cooling Index (RCIHI) = 1 - Rack Cooling Index (RCILO) = 1 - Total Over-Temp Max Allowable Over-Temp Total Under-Temp Max Allowable Under-Temp x 100 x 100 Interpretation of RCI ASHRAE Specifications: Recommended 64.4 – 80.6 F Allowable 59 – 89.6 F RCI is a measure of compliance with the ASHRAE thermal guideline Interpretation RCI Value Ideal 100% Good 95% to 100% Acceptable 90% to 95% Poor < 90% Rack Cooling Index (RCI) is a Registered Trademark of ANCIS Incorporated (www.ancis.us). All rights reserved. Used under authorization 6 Today’s Example Medium sized data center • 15,000 Sq Ft of white space • Raised floor design with ceiling plenum return. • 757 kW of heat load, 192 racks • RDX units on 11 high density rack rows • Multi level design: • Basement level is reserved for mechanical • Second floor is data center white space • Third level is return plenum. 7 Case example data center 8 Methodology for creating valid model 1. Build model of data center using CFD model builder • • • Avoid small details that will not affect airflow Focus on dominate parameters • • • • Geometric placement of inlets, cooling units, racks, etc Height of room, plenum, ceiling return Tile placement, % area open, ceiling grill placement Placement and size of racks • Can add detail later if necessary Begin with “average watts per rack” 2. Use measured data to set the boundary conditions of cooling equipment and racks • • • • Set supply air temperature (SAT) using measured data Measured “watts per rack” thermal loads Assume 20 F delta across racks Assume 156 CFM per kW for rack cooling 9 Methodology for creating valid model 3. Use measured data to Validate CoolSim model. a) b) Compare measured CRAC/CRAH return temperature to predicted return temperature. Should be < 20% Compare measured Rack Inlet Outlet temperature to predicted temperatures. Should be < 20% 4. Adjust model parameters until they match measured values within acceptable level Governing Equation: Q flowrate cP (TR TS ) 10 Case Example Model built from drawings Supply air flowrate/temp from measurements Rack positions from drawings Rack loads taken from rack power measurements 11 Rack Inlet Temperatures 12 Rack Inlet Temperatures Full Range 13 Initial Results Step 1: Check Air Handler Temperatures. Measured Return Temp CRAC Unit Name Downflow Units ahu_12 (A , 11) ahu_11 (A , 18) ahu_10 (A , 26) ahu_9 (A , 34) ahu_8 (U , 54) ahu_7 (AC , 54) ahu_6 (AK , 54) ahu_5 (AS , 54) ahu_13 (U , 1) ahu_2 (AC , 1) ahu_3 (AN , 1) ahu_4 (AW , 1) Error 79 80 79 76 78.5 0.21% Predicted Return Ave Supply Supply Flow Rate Heat Removal Temperature Temperature (cfm) (kW) o o 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 84,000 54.72 48.92 38.05 39.45 39.03 40.73 38.16 31.01 47.46 45.33 43.2 34.26 500.32 ( F) ( F) 85 82 77 78 78 78 77 74 81 80 79 75 78.7 60 60 60 60 60 60 60 60 60 60 60 60 14 Step 2: Check Rack Temperatures Supply Temperatures are acceptable Return Temperature need some adjustment Rack Temperatures Inlet Return Measured 68.77 76.75 Predicted 68.57 95 Error 0.3% 19% 15 Racks with large variances 16 Steps to adjust return temperatures 1. 2. 3. 4. Look for racks with large variance Check heat loads first Adjust temperature rise up, or flowrate down. Rerun simulation to “dial in” temperatures. 17 Rack data adjustments RDX heat exchangers were assumed to perform at 50% efficiency (10F temp drop). But for higher density racks (15-20 kW), this number increases to 75% Change delta T assumptions on highest density racks from 10F to 15F 18 Recheck Air Handlers Measured Return Temp CRAC Unit Name Downflow Units ahu_12 (A , 11) ahu_11 (A , 18) ahu_10 (A , 26) ahu_9 (A , 34) ahu_8 (U , 54) ahu_7 (AC , 54) ahu_6 (AK , 54) ahu_5 (AS , 54) ahu_13 (U , 1) ahu_2 (AC , 1) ahu_3 (AN , 1) ahu_4 (AW , 1) Average Error Ave Return Ave Supply Supply Flow Rate Heat Removal Temperature Temperature (cfm) (kW) 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 7,000 48.87 35.16 36.22 34.64 38.28 22.44 15.07 13.94 19.24 33.71 21.95 21.63 o 79 80 79 76 78 7% o ( F) ( F) 82 76 76 76 77 70 67 66 69 75 70 70 72.8 60 60 60 60 60 60 60 60 60 60 60 60 19 Revised Rack Temperatures Adjustments to model improve predictions Rack Temperatures Inlet Return Measured 68.77 68.77 Predicted 63.02 63.02 Error 8.4% 9% 20 Model is now valid for optimization scenarios Check the RTI and RCI values: RTI: 38% RCI (High): 98% RCI (Low): 62% More air from AHU than needed Some racks with hot spots Many racks below min temp Opportunity to reduce air volume and increase supply air temperature • May require air management 21 Visual representation of temperature data 22 Data Center Modifications Step 1: Decrease AHU airflow to reduce bypass airflow. Step 2: Increase SAT temperature to reduce energy consumption. 23 Step 1: Decrease AHU flowrate 30% Results: • Fan energy down 43% • Racks still in compliance 24 Step 2: Increase Supply Air Temperature 10F • For every 1.8F increase, 3.5% increase in mechanical energy efficiency alone. • • Does not take into account the improved efficiency of economizer due to increased window of use. Increased number of hours to operate airside economizer by 500 hours per year. 25 Results: RCI High now at 97% 26 Step 3: Manage the airflow where needed 27 Results: RCI high increases to 98% 28 Summary of steps 1. 2. 3. 4. 5. 6. Built CFD model of current design Validated CFD model with measurements Used model to predict the effect of change Reduced airflow first to improve RTI Increased Supply Air temp to reduce energy Used air management techniques to improve airflow in hot regions 29 Summary of results • Reducing AHU airflow 30% => 43% savings • Increasing Supply Air Temp 10 F => 20% savings • Adds an additional 500 hours to “free air” opportunity • Assuming cost to cool = cost to drive IT • Cost of electricity = $ .10/Kwh • Total savings potential = $400k/year 30 Paul Bemis [email protected] 31