Basic 101 Lite Show Presentation
Download
Report
Transcript Basic 101 Lite Show Presentation
Battery 101
Trojan Battery Company
Types of Construction
Lead Acid
Flooded
Maintenance
Free
Lead Calcium
• Deep Cycle 50%
• 100 - 300 Cycles
Maintenance
Lead Antimony
• Deep Cycle 80%
• 300 - 1000 Cycles
Sealed
(Valve Regulated)
Absorbed Glass
Mat (AGM)
Lead Calcium
• High Power
• Deep Cycle 50%
• 50 - 250 Cycles
Gelled
Lead Calcium
• Immobilized
Electrolyte
• Low Power
• Deep Cycle 80%
•200 -500 Cycles
Trojan Battery Company
Terminology
Watts = Volts x Amps = POWER
Watt-hours = Volts x Amps x Time (hours) =
ENERGY
Amp-Hours = Amps x Time(hours)
Trojan Battery Company
How a Lead Acid Battery Works
Discharge
PbO2 +
Pbo
+
2PbSO4 + 2H2O
2H2SO4
Charge
(Positive)
(Negative)
(Black/Dark
Brown)
(Gray)
(Lead
Peroxide)
(Sponge
Lead)
(Electrolyte)
(Lead Sulfate) (Water)
Trojan Battery Company
Definitions
Voltage (V) = Electromotive force
(potential of battery)
-
+
6.3V
•Open Circuit Voltage?
•Under Load Voltage?
•12V vs. 6V?
Trojan
2.1 Volt Cells
Trojan Battery Company
Voltage Relationships
Open Circuit Voltage Specific Gravity
Specific Gravity State of Charge
Specific Gravity + 0.845 = Open Circuit Voltage
Trojan Battery Company
Open Circuit Voltage
OCV or VOC: Voltage measurement made after
24 hours of battery rest (no load).
OCV vs. State of Charge (SOC)
Charge
Level
Specific
Gravity
Voltage
(12)
Voltage
(6)
100%
75%
50%
25%
Discharged
1.277
1.227
1.172
1.111
1.098
12.72
12.42
12.12
11.76
11.58
6.4
6.2
6.1
5.9
5.8
Trojan Battery Company
Typical Discharge Curve
at a Constant Discharge Current
Resistance
Voltage
Drop
Open Circuit Voltage
Voltage Under Load
Voltage
Coup De Fouet
End of Discharge
Voltage
1.75 - 1.70 VPC
Measured Capacity
IEICC
Time
Trojan Battery Company
Deep cycle
7 - 10
Amps/100AH
(C20*)
Charge Current
2.45 - 2.70 VPC*
1-3
Amps/100AH
(C20*)
2.05 - 2.25
Volts per cell
(80% DoD*)
Charge Voltage
Charge Time
IEICC
Trojan Battery Company
Series/Parallel Circuits
In a Series Circuit, Voltage is additive, Current stays the
same
Example: 2 T-605’s in series = 12 volts @ 190 AH
In a Parallel Circuit, Current is additive, Voltage stays the
same
Example: 2 T-605’s in parallel = 6 volts @ 380 AH
Trojan Battery Company
Definitions
Series Circuit
+
12V
-
+
+
• Voltage is additive
• Current is equal
-
-
(12V, 220 AH)
+
+
Parallel Circuit
+
6V
-
• Voltage is equal
• Current is additive
-
(6V, 440 AH)
Trojan Battery Company
Battery Capacity
A battery’s capacity is the amount of electricity
the battery can provide to the load and is
dependent upon the rate (speed) at which the
battery is discharged.
20 hour rating
8 hour rating
6 hour rating
3 hour rating
1 hour rating
= 100% Capacity
= 88% Capacity
= 84% Capacity
= 74% Capacity
= 59% Capacity
Trojan Battery Company
Amp Draw Vs. Run Time (Hours)
240
210
180
200
150
160
120
120
90
AH Rating
Discharge Current (A)
240
80
60
40
30
0
0
0
2
4
6
8
10
12
14
Discharge Time (hrs.)
16
18
20
AH Rating
Discharge
Rate
Trojan Battery Company
Temperature vs. Capacity
140
%
Capacity
120
100
80
60
40
20
0
0
20
40
60
80
Temperature (°F)
IEICC
100
120
Trojan Battery Company
Generic “Smart” Charge Curve
Voltage
(VPC)
Current
(A)
current
C20/5
2.60
2.37
voltage
C20/50
20%
80%
State of Charge (%)
IEICC
100%
Trojan Battery Company
Stratification
Specific gravity gradient that may result from
ineffective overcharging.
1.080
Normal Sp.G. = 1.277
(Full Charge)
1.400
Trojan Battery Company
SAFETY
Protect eyes and skin from exposure to electrolyte.
Don’t smoke when working around batteries or while
charging.
Insulate tools to prevent shorting across the posts.
Use good lifting mechanics when moving and installing
batteries.
Trojan Battery Company
SAFETY
Neutralize acid spills with baking soda or
soda ash, IMMEDIATELY.
Ventilate during charging to prevent gas
build-up.
Charge with vent caps securely in place.
When in doubt, contact your dealer.