Transcript Slide 1
Lessons Learned from the Texas Synchrophasor Network by W. Mack Grady and Moses Kai, U.T. Austin Bill Flerchinger and David Costello, Schweitzer Engineering Labs Karen Forsten and Daniel Brooks, EPRI Presented at the North American Synchrophasor Initiative (NASPI) Meeting Toronto, Ontario Thursday, June 9, 2011 1 The Texas Synchrophasor Network Six 120V single-phase PMUs, One 69kV three-phase PMU Blue outlines: Central ERCOT Brazos Electric PMU McDonald McDonald Observatory Waco Wind country Austin 120V and Austin Harris 69kV Boerne (SEL) Austin Energy PMU Houston (SEL) • Funding provided by EPRI • Equipment provided by Schweitzer Engineering Labs UT Pan Am UT Am Concentrated distant load 2 Wind Generation in ERCOT - MW March 25, 26, 2010 6000 Lesson 1. Every Day has Synchrophasor Surprises 2 days 5000 Wind generation and West Texas phase angle can go through large daily swings 3000 Thur Fri 2000 1000 0 24 36 48 60 72 McDonald Observatory Voltage Phase Angle with respect to U.T. Austin March 25, 26, 2010 60 West Texas voltage phase angle swings nearly 100º and back with respect to U.T. Austin in about 24 hours 40 20 Degrees MW 4000 0 -20 -40 -60 24 36 48 60 4836 Hours Beginning 12am, March 24, 2010 72 3 Texas Nodal Market Has Created a New West Texas Resonant Mode with Time Period = 30 minutes 12 hours ERCOT’s graph of West-to-North P flow McDonald Observatory Voltage Phase Angle Relative to Central ERCOT 40 Texas Synchrophasor Network’s graph of West-to-Central ERCOT Voltage Angle Degrees 30 20 10 0 -10 -20 0 1 2 Lesson 1. Daily surprises, cont. 3 4 5 6 7 8 Hour of March 11, 2011 9 10 11 12 4 Transmission Events Also Produce Angle Rings 2011/06/03, 00:54 GMT McD Angle 2 minutes • The angle ring observed at McD and Waco was likely caused by a transmission event and was a precursor to a gradual frequency slump. • Angle ring is approx. 1 degree peak to peak (2nd significant digit) • Frequency ring is only about 0.01 Hz peak to peak (4th significant digit) 60.02 Hz McD, PanAm, Waco Frequencies 5 minutes 2 minutes 3600 points Lesson 1. Daily surprises, cont. 59.94 Hz Frequency Slump 5 Lesson 2. 120V Wall Outlets Work for Synchrophasors (of course, we would prefer to have three-phase grid PMUs) Voltage Ringdown at McDonald Observatory Observed at the Following Two Locations in Austin: a 120V Wall Outlet onObservatory Campus,Voltage and the Harris Substation thatHarris Feeds McDonald Phase Angle69kV w.r.t U.T. Austin 120V and 69kVthe Campus -10 20 seconds 10 seconds Degrees -11 w.r.t U.T. Austin -12 w.r.t Harris 69kV -13 -14 1600 1700 1800 1900 2000 2100 2200 Sample (30 samples per second) • The fixed net multiple of 30 degree phase shift between U.T. Austin 120V and Harris 69kV has been removed. The variable but steady power flow phase shift through the substation transformer has also been removed. 6 Steady-State Voltage Angle Between Austin Energy 69kV Substation Monitor and UT ECE Building 120V Wall Outlet Varies Slowly with UT Generation and Load Week Starting Sunday, Mayto29, Voltage Phase Angle Relative UT 2011 Austin 1-Minute Averages, Beginning Sunday, May 29, 2011, Beginning 00:00 CDT 1 week Degrees 1 0 Ha -1 0 24 Note – angles shown were rounded to 0.1º Lesson 2. 120V OK, cont. 48 72 96 120 144 168 Hour of the Week, CDT 7 Lesson 3. You Can Estimate Thevenin Equivalent Impedances Across the Grid with Synchrophasors Vangle = δ Pexport Bus 7 WIND 500 km Thevenin Impedance jXTH Central ERCOT Vangle = 0 Local conventional Pload,conv − Pgen,conv Use the Excel Solver with angle measurements to minimize least-squared error and obtain Xth McDonald Observatory Voltage Phase Angle Relative to Central ERCOT 40 Degrees 30 V1V2 P sin( ) X TH 20 10 0 -10 -20 0 1 2 3 4 5 6 7 8 Hour of March 11, 2011 9 10 11 12 8 Lesson 4. A Small but Tightly-Clustered 2 Hz Mode in Ambient Oscillation Sometimes Forms with High Wind Generation Small Wind (2%) without 2 Hz Cluster March 12, 02:00 – 03:00 Wind Generation ≈ 2% Big Wind (20%) with 2 Hz Cluster March 18, 02:00 – 03:00 Wind Generation > 20% 1 hour 2 Hz Cluster 9 Lesson 5. Wind Generation Does Not Appear to Impact System Damping or Damped Resonant Frequency 5 minutes of frequencies 59.74 McD Modest wind 1 minute of angles PanAm Waco 10 Let Excel Solver Curve Fit the 2nd Order Damped Response Start Sec 5.5 Stop Sec 11 Exponential Steady State Transition Curve A B T1 Tau1 17.05 18.58 5.91 0.24 Steady-State Change = 18.58 – 17.05 = 1.53 degrees C 1.73 T2 6.18 Damped Sinusoidal Term Tau2 Tdamp Fdamp 4.64 1.59 0.628 Zeta 0.055 Damped Resonant Frequency, Hz Ring Magnitude, degrees Unit Trip 2011/05/30 03:03:00 GMT. UT Pan Am Relative to U.T. Austin. Measured Avg. Sum Squared Error 0.0044 Alpha 0.215 F0 0.629 Normalized Damping Ratio Total Curve Fit 21 10 seconds Degrees 20 19 18 (t T1 ) 17 B A B e 1 16 5 6 7 8 (t T2 ) u(t T1) C e 2 9 10 11 sind (t T2 ) u(t T2 ) 12 13 14 15 Second Lesson 5. Wind does not impact damping, cont. 11 Ringdown Analysis of More Than 100 Unit Trips Yields No Clear Relationship Between Wind MW and Normalized Damping Ratio Damping Ratio vs Wind Generation (% of Total), Sep 2009 - Feb 2010 1.2 Does Wind Generation Impact Grid Stability? Normalized Damping Ratio 6 months 1 0.8 0.6 0.4 0.2 0 0 2 4 6 8 10 12 14 16 18 20 Wind Generation (% of Total) Lesson 5. Wind does not impact damping, cont. 12 Lesson 6. Wind Generation Does Not Appear to Reduce System Inertia (but no generator operating at max power can contribute to governor response) EPRI Study. Purpose – to compute ERCOT System Inertia Constant H From Frequency Response During 42 Unit Trips Having 0.1 Hz or Greater Freq. Drop. 2 minutes Zoom 10 seconds Event 7, 8/24/2010 07:31:00 PM GMT Minute 60.00 59.98 59.96 Frequency 59.94 UT Austin 59.92 Harris 69 McD Nadir slope 59.90 59.88 59.86 UT PanAm Inertia slope 59.84 59.82 56 57 58 59 60 61 62 Second of the Minute 63 64 65 66 13 42 Major Unit Trips, 0.1 Hz or Greater. Any Correlation Between System Inertia and Wind Generation (% of Total Gen)? 6 months Estimated System H versus % Wind Generation (42 Unit Trip Events, June through November 2010) 12 Estimated H 10 8 6 4 2 0 0 5 10 15 20 Wind Generation - % of Total Generation Lesson 6. Wind does not reduce system inertia, cont. 14 Texas Synchrophasor Network Thanks to • Schweitzer Engineering Laboratories, especially Mr. David Costello, for providing all the equipment and technical support that we need • EPRI, especially Ms. Karen Forsten and Mr. Daniel Brooks, for past, present, and future funding of graduate students and faculty summer support • Startup money in 2008 from the Texas Governor Rick Perry’s Emerging Technology Fund through CCET, Dr. Milton Holloway • Austin Energy, especially Mr. Scott Bayer, for installing the 69kV phasor measurement unit, and providing advice on system operating and protection • Mr. Andrew Mattei of Brazos Electric, Waco, for installing and operating a 120V PMU • PhD student Moses Kai at U.T. Austin for his dedication and research in synchrophasors and their applications to power grids 15