48V Power Plant - Punjab Communications Limited

Download Report

Transcript 48V Power Plant - Punjab Communications Limited

MODULAR SMPS POWER PLANT
PUNCOM
offers
SMR-48V/33A
, a switch
mode rectifier module, designed to provide up to
33A of output current into a 48V nominal system
for
telecom,
datacom,
industrial
and
IT
applications. It Converts 150-275V AC input power
at 50 or 60 Hz into a highly regulated, filtered,
low noise and isolated 48V DC output. The unit is
designed for N+1 redundant configurations. Up to
eight rectifier modules can fit in a single 19” rack
to provide 231A of current in N+1 configuration.
Up to fifteen rectifiers can be configured in two
19” racks for a 462A ultimate capacity system in
N+1
configuration
using
one
control
and
supervisory unit (MiniCSU). The system can also be
monitored and controlled remotely through modem
or internet. The rectifier has been designed with a
“plug-and-play” feature i.e. when a rectifier module
is plugged into a live system the relevant system
parameters are automatically downloaded from the MiniCSU, making rectifier
replacement a completely hands-off operation. The unit is fully hot pluggable.
SALIENT FEATURES
 Hot Pluggable.
 231A in a 19” rack in N+1 configuration and 462A
in two 19” racks in N+1 configuration.
Active power factor correction > 0.98.
 Very High power density > 4.0W/inch3.
 High efficiency: better than 90%
at > 50% load.
 Plug and play capability without any
adjustments.
 Digital active current sharing.
 Password protection against
unauthorized parameters change.
 Wide range of AC input, 150-275V
provides protection from power
disturbances and in combination with high
interrupting capacity fast acting fuses
translates into better reliability.
 Battery temperature compensation
 Compliant to IEC 61000 & CISPR 22
specs for EMI/EMC.
 Optional RS 232, RS 485,10Base T
ethernet and modem interfaces.
 Fully menu driven with user friendly
navigator push buttons menu.
SPECIFICATIONS
INPUT CHARACTERISTICS
Voltage
Nominal
220VAC
Protection
Rated voltage range
150-275VAC
Reverse Polarity
Extended low
voltage range
90-150VAC (With 50% automatic
power derating)
Over voltage
Only faulty unit shuts down
Extended high
voltage range
275-290VAC
Over current
Can sustain short Circuit
Current
14A RMS at 150VAC
9A RMS at 220VAC
reverse polarity
indefinitely
Over temperature
Gradual reduction of power
limit if heat sink temp exceeds
Frequency
45-66Hz
Power factor
Harmonic Distortion
>0.98 at 40%-100% load
Current THD<6% (full load) if
Voltage THD<1%
Efficiency
Better than 90% at >50% load
Inrush Current
<8A peak at nominal mains voltage
Soft Start
Ramp up time 8 seconds to full load
FEATURES
Protection
HRC input fuse for input Live
Indicators
Voltage Withstand
Test
Fuse at output protects against
preset limit
Voltage Withstand
test
1000VAC output to chassis for one
minute
Status normal-green LED
Over voltage shutdown at 300VAC
Minor alarm-Yellow LED
Under voltage shutdown at 85VAC
Major alarm-Red LED
1500VAC input to chassis for one
minute
Controls/Adjustments
Float/equalize voltage
(Via MiniCSU)
Current limit
HVSD level and reset
Equalize mode
Individual remote shutdown
OUTPUT CHARACTERISTICS
Voltage
MECHANICAL
Float
48-58V
Equalize
50-59.9V
Dimensions
Current Limit
5A to 34A
Rack
1800W
Module W x H x D
87mm x 266mm x 320mm
Static Regulation
MINICSU W X H X D
176mm x 44mm x 266mm
Line
Better than ±0.02%
Weight SMR/MINICSU
< 6Kg/1.3KG
Load
Voltage drops by 0.56V ±0.03V
from zero to 33A for stand alone &
better than ± 0.05% for MiniCSU
controlled unit
Power
Dynamic Regulation
WxHxD
ENVIRONMENTAL
Temperature
Operating range
-25oC to +50oC
Derated operation
50oC to 70oC, 50% automatic power
step change
Storage
-40oC to +70oC
±0.1% for a 25% step change in AC
input voltage
Humidity
0 to 95% RH non-condensing
Cooling
Natural convection / Forced Cooling
<2mV RMS psophometric weighted
Altitude
Derate max ambient temperature by
±5% for 10% to 90% step load
±1% of final value within 1msec of
Noise
derating
<10mV RMS (10KHz-100MHz)
4oC per 1000m above sea level to
<100mV peak to peak (10KHz100MHz)
Load Sharing
600mm x 1465mm x 595mm (max.)
3000m
EMI/EMC
Better than ±5% of full scale
with active current sharing from
Meets IEC 61000 specs for EMC
immunity and CISPR 22 class B for
EMC emissions
MiniCSU
Specifications subject to change without prior notice.
Punjab Communications Limited
B-91, Phase VIII, Industrial Area, Mohali, Punjab 160059 India
Phone: +91-172-2237101, Fax: +91-172-2237125, 2237126
E-mail: [email protected]
Visit us at: www.puncom.com
040605