Power quality management for
induction furnace foundry
Mr.Danaisak Tangsakha
Provincial Electricity Authority (PEA)
Thailand
Topic
• Introduction
• Problem & Mitigation Techniques
• Conclusion
Provincial Electricity Authority, Thailand
17 July 2015
2
What is “Harmonics
Voltage”?
A sinusoidal voltage with a frequency equal
to an integer multiple of the fundamental
frequency of the supply voltage (EN50160)
Order 3 : 3 × 50 Hz = 150 Hz
Provincial Electricity Authority, Thailand
17 July 2015
3
Where is the source of the harmonics?
Other loads
Other loads
Harmonic
current
flow
(a) Power flow at the fundamental frequency
Three-phase
voltage and current
measurements
Motors and all
other linear
loads
PF Correction
Capacitor Banks
Nonlinear Load
Provincial Electricity Authority, Thailand
(b) Harmonic power flow
17 July 2015
4
Single Line Diagram
PEA System
115 kV
GENERAL
LOAD
GENERAL
LOAD
Provincial Electricity Authority, Thailand
GENERAL
LOAD
GENERAL
LOAD
17 July 2015
INDUCTION
FURNANCE
LOAD
5
INDUCTION FURNANCE
• Induction Furnace inverter 24 pluse
• Ideal harmonic h=p±1 order 23, 25
• 4 unit and Full Load 3 unit (39.80 MW)
Provincial Electricity Authority, Thailand
17 July 2015
6
INDUCTION FURNANCE
PEA System
115 kV
INDUCTION
FURNANCE
Provincial Electricity Authority, Thailand
INDUCTION
FURNANCE
17 July 2015
7
Load Characteristic
Time plot
10000
10 pm – 9 am
kW
7500
5000
2500
0
TOT P (kW) (max)
16:00
12/07/2009
Sunday
18:00
20:00
22:00
00:00
13/07/2009
Monday
02:00
04:00
06:00
08:00
10:00
Event #12 at 04/07/2009 09:50:11.040
AVrms, BVrms, CVrms Ins tantaneous Sag
TOU rate : Customer Loads operated in off-peak period
Provincial Electricity Authority, Thailand
17 July 2015
8
Problem
• Induction Furnace Load THD over limit
Harmonics Standard in Thailand
• Adjacent 22 kV Customers complaints
included flickering lights, UPS alarms,
drive trips, impairment of electronic
equipments
Provincial Electricity Authority, Thailand
17 July 2015
9
Total Harmonic Distortion ,THD
Provincial Electricity Authority, Thailand
17 July 2015
10
Harmonics Standard in Thailand
Table 1 Harmonics Current Limit (Base 1,000 MVA)
Tolerances 10% or 0.5 A , 2 order
PRC - PQG - 01 / 1998
Provincial Electricity Authority, Thailand
17 July 2015
11
Harmonics Standard in Thailand
Table 5-2 limit of Total Harmonic Distortion VoltageTHDv (%)
Point of Common Total Harmonic
Coupling : PCC Distortion Voltage
(kV)
THDv (%)
Individual Harmonic
Distortion Voltage(%)
Odd
Even
0.4
5
4
2
11 and 12
4
3
1.75
22 ,24 and 33
3
2
1
69
2.45
1.63
0.82
115 and above
1.5
1
0.5
PRC - PQG - 01 / 1998
Provincial Electricity Authority, Thailand
17 July 2015
12
Voltage Fluctuation Standard in Thailand
Point of Common Coupling
: PCC (kV)
Below 115 kV
More than 115 kV
Pst
Plt
1.0
0.8
0.8
0.6
Pst ; Short-Term Severity Values (10 minutes)
Plt : Long-Term Severity Values (2 hours)
PRC - PQG - 02 / 1998
Provincial Electricity Authority, Thailand
17 July 2015
13
Mitigation Techniques
•
•
•
•
Connect to Network
Monitoring
Harmonic Filter
Simulation
July,2009
Provincial Electricity Authority, Thailand
Sep,2009
17 July 2015
14
Network Configuration
230/115 kV
230/115 kV
BPA
SPA
115/22 kV
115/22 kV
NPA
NPB
LNS
Provincial Electricity Authority, Thailand
END LINE
17 July 2015
15
Monitoring With out Harmonics Filter
• Harmonics current at PCC:115kV at Ling Nan
Steel for 1 EAF with out Harmonics Filter
Case
MVA
Base
1
2
Harmonics Order
3
4
5
6
7
8
9
With out Harmonics
- 70.28 5.85 6.33 7.91 6.55 6.6 2.48 0.91 1.22
Filter
With Harmonics Filter
Harmonics Current Limit
1,000 5
4
3
4
2
3
1
1
at Base 1,000 MVA
Ih limit Base on 115kV
1,984 - 9.92 7.99 5.99 7.99 3.99 5.99 2
2
Nakorn Pathom2
Remark
×
×
Provincial Electricity Authority, Thailand
17 July 2015
16
Monitoring With out Harmonics Filter
• Harmonics current at PCC:115kV at Ling Nan
Steel for 1 EAF with out Harmonics Filter
Case
MVA
Harmonics Order
Ih rms
Base 10 11 12 13 14 15 16 17 18 19
- 1.04 3.95 0.92 2.98 0.49 0.65 0.73 1.18 0.57 0.97 16.19
-
With out Harmonics Filter
With Harmonics Filter
Harmonics Current Limit at
1,000 1
Base 1,000 MVA
Ih limit Base on 115kV
1,984 2
Nakorn Pathom2
Remark
Provincial Electricity Authority, Thailand
3
1
3
1
1
1
1
1
1
10.34
5.99
2
5.99
2
2
2
2
2
2
20.63
17 July 2015
17
Harmonic Filter
• Tuned Filter Order 4 and 5
• High pass filter Order 6
Provincial Electricity Authority, Thailand
17 July 2015
18
Simulation by DIgSILENT
On Site Tuned Filter
Provincial Electricity Authority, Thailand
17 July 2015
19
Harmonic Filter
4th
5th
6th
Provincial Electricity Authority, Thailand
17 July 2015
20
Harmonic Filter
Provincial Electricity Authority, Thailand
17 July 2015
21
Simulation by DIgSILENT
Provincial Electricity Authority, Thailand
17 July 2015
22
Monitoring and Simulation
Case
1
2
-
9.92
7.99
5.99
198.89
1.14
7.70
177.1
0.79
3.69
Ih limit Base on 115kV
Nakhon Pathom2
With Harmonics Filter
Simulation : DigSILENT
Remark
Case
Harmonic Order
3
4
5
6
7
8
9
7.99
3.99
5.99
2
2
1.93
5.20
0.91
1.81
0.45 0.45
0.36
0.03
0.12
0.21
0.83 1.44
16
17
18
19
2
2
Harmonic Order
13
14
15
10
11
12
Ih limit Base on 115kV
Nakhon Pathom2
2
5.99
2
5.99
2
2
2
2
With Harmonics Filter
0.45
2.49
0.45
1.81
0.45
0.45
0.45
0.45
0.45 0.68
Simulation : DigSILENT
Remark
0.07
4.1
0.12
1.39
0.51
0.5
0.6
0.83
1.44 0.33
Provincial Electricity Authority, Thailand
17 July 2015
23
Conclusion
• The network configuration in this case reduced
the affect to nearby customers and also improved
voltage level.
• The results of harmonic filters are
dramatically reduced voltage distortion on the 22
kV and not to affect the nearby customer
• Customer run 3 unit from 4 unit because harmonic
filters design for 3 unit.
Provincial Electricity Authority, Thailand
17 July 2015
24
Thank you for your attention…