PROTECT 3.M
15 – 120kVA
PROTECT 3.M
the new generation of
uninterruptible power supplies (UPS)
with
3-phase Mains input and
3-phase Mains output
PROTECT 3.M General data
PROTECT 3.M will be offered in two cubicle variances.
Variance 1:
Cubicle dimensions: (W x H x D) 600mm x 1600mm x 1000mm
Maximum 6 modules each 15kVA = 90kVA per cubicle
Variance 2:
Cubicle dimensions: (W x H x D) 600mm x 2000mm x 1000mm
Maximum 8 modules each 15kVA = 120kVA per cubicle
15kVA per Modul (hot-swappable)
Degree of redundancy selectable via Display
Each Modul is independent , Controllcard/Display are just for Communication
and Indication.
Integrated Distribution with up to 36 breakers as an option
LCD Display
Communication via RS232, RS485, SNMP & AS400
PROTECT 3.M General data
1.6 m cubicle
MB at the bottom
2.0 m cubicle
MB at the top
PROTECT 3.M
High MTBF ability
Each UPS module in the Protect 3.M is the full function UPS. There is
no additional controlling
module to the parallel application and load sharing. Regarding to the
serious calculation on the system MTBF, if you have two more UPS
modules for parallel redundancy, the system ability is
above 99.999% and the MTBF will be close to 15 Million Hours.
MTTR
Once the system has one more UPS module for parallel redundancy,
the system will still keep
working if one of the UPS modules fails. If the failed modules exceed
the parallel redundancy modules, the module replacement procedure
only need 5 minutes for system recover.
PROTECT 3.M Battery
Battery
+/- 240Volt DC (20 bloc for each string)
Integrated batteriecharger in each Module (2700W / 4.5A)
Battery Management in two steps
Step 1) up to 90% battery capacity  constant current
Step 2) above 90% capacity constant voltage
PROTECT 3.M Technical data part I
Classification VFI SS 111 acc. to IEC 62040-3
Type power
max. modules per rack
Protect 3.M 1.6m rack
Protect 3.M 2.0m rack
90 kVA
120kVA
72 kW
96 kW
6
8
UPS-input
Input voltage
400 / 230Vac (3/N/PE~)
Input voltage range without battery mode
277 - 520Vac(3ph~)
Frequency
Current consumption (max.)
50 Hz / 60Hz
120A with 6 modules
Power factor
160A with 8 modules
> 0.99 at 100% Load
THD(i)
<=5%
UPS-output
Rated output voltage
400V ± 2%
Frequency in battery mode
Output current
Transfer time at mains outage
Voltage waveform
Overload response (online mode)
Crest factor
50 Hz ± 0.5%
22 A / per module
132A with 6 modules
22 A / per module
176A with 8 modules
0 ms ( zero transfer )
Sinusoidal
130% for 10min / 150% for 1min
3
PROTECT 3.M Technical data part II
Battery
Nominal voltage
240VDC (40pcs for each set in series connection.
One battery neutral wire from the central)
Autonomy time
Overload / deep discharge protection
Free to choose runtime extension with scalable external
battery.
Available configurations with 24,38 or 65 Ah)
Yes
Communication
Interfaces
RS232 / RS485 for status and measurement values,
Communication slot ( for pot.-free contacts or SNMP
adapter)
Shutdown software (on CD)
Included for all typical operating systems (e.g. MSWindows,Novell Netware,Mac OS,Linux,Unix derivates,
etc.)
Failure indicators (acoustic/optical)
LCD with digital information of input and output parameters
(voltage,frequency,power etc.) battery parameter incl.
failure diagnosis by password protect level, LED for status
and main failures.
PROTECT 3.M Technical data part III
General data
Efficiency total
> 90%
Audible noise (1m distance)
<62 dB
Operating temperature range
0º - 40 ºC
Humidity
20% - 90%
Installation height
up to 1000m, at nominal load
Equipment colour
RAL 7035
Size approx.W x H x D (mm)
600 x 1600 x 1000
600 x 2000 x 1000
250kg rack +
35kg per module
300kg rack +
35kg per module
Weight appr. (kg)
Certification
CE
PROTECT 3.M · Applications
Single- and multi-user systems
( Workstations, FileServer, Application Server, ... )
Network protection (client / server architecture)
e.g. intranet / internet application
EDP - equipment (CAD - systems, ...)
Communication equipment (IT- sector)
Component protection of telecommunication
Cash systems (trade)
Other user-critical applicationen
(process systems (stored-program contoller, ... ))
PROTECT 3.M · conceptual highlights
Modularity with UPS plug-in modules
in VFI (double-conversion) technology
n + x technology
free choice of redundancy level
scalable design for flexible
power- / autonomy time requirements
central simplified management
more efficient service
independent UPS - modules
(without any central control logic)
PROTECT 1.M · UPS classes
Voltage Phenomenon
1. Outage - blackouts
Time
> 10 ms
2. Sags / brownouts
3. Dynamic overvoltage
e. g.
IEC
62040-3
VFD
UPS solution
Classification 3
Voltage +
Frequency
Dependent
Offline
4. Undervoltage
continuous
VI
Classification 2
5. Overvoltage
continuous
Voltage
Independent
LineInteractive
6. Lightning
7. Transients (Surge)
sporadic
< 4 ms
8. Frequency variations
sporadic
9. Voltage distortion (Burst)
periodic
10. Voltage harmonics
continuous
...........
VFI
Classification 1
Voltage +
(true) Online
Frequency
Independent
real DoubleConversion
by additional
lightning arrestors
Protect 3.M System architecture
Integrated Distribution
with up to 36 breakers as
an option
Communication module
incl. communication
port
LCD-Display
UPS-modules each 15kVA
PROTECT 3.M · UPS module design
Diagram of an UPS PROTECT module :
Electronic
static bypass
Mains
filter
Load
PFC
Mains
~
Filter
~
High power reserves as
a result of a max. 24 kVA
total output
High safety reserves as
a result of n+x technology
Inverter
Rectifier
DC/DC Booster
~
DSP / CanBus
control logic unit
Battery charger
Battery system
RS232
SNMP
Independent UPS modules
(no central control) slide-in
types; suitable for rackmount
PROTECT 3.M · n + x technology · redundancy level
Quantity of
UPS modules
1
2
3
4
5
6
7
8
modul
modules
modules
modules
modules
modules
modules
modules
15 kVA
n+1
(15 kVA)
n+2
(30 kVA)
n+3
(45 kVA)
n+4
(60 kVA)
n+5
(75 kVA)
n+6
(90 kVA)
n+7
(105 kVA)
30 kVA
no
redundancy
n+1
(15 kVA)
n+2
(30 kVA)
n+3
(45 kVA)
n+4
(60 kVA)
n+5
(75 kVA)
n+6
(90 kVA)
no
redundancy
n+1
(15 kVA)
n+2
(30 kVA)
n+3
(45 kVA)
n+4
(60 kVA)
n+5
(75 kVA)
no
redundancy
n+1
(15 kVA)
n+2
(30 kVA)
n+3
(45 kVA)
n+4
(60 kVA)
no
redundancy
n+1
(15 kVA)
n+2
(30 kVA)
n+3
(45 kVA)
no
redundancy
n+1
(15 kVA)
n+2
(30 kVA)
---
no
redundancy
n+1
(15 kVA)
---
no
redundancy
Load
no
redundancy
45 kVA
60 kVA
---
75 kVA
90 kVA
105 kVA
-------
---
120 kVA
n + x technology
advantage
Higher reliability
Easy to increase overall capacity
Modules hot - swapable
(without any interruption)
Protect 3.M Usage >> Delivery
Cubicle packing
Module packing
Protect 3.M - Mains connection
Mains
Battery
Load
PROTECT 3.M – LCD display
Appear „green light“
Appear „yellow light“
Appear „yellow light“
Appear „red light“
and warning alarm
PROTECT 3.M Communication interface
“Dual monitoring“ interface
from left to the right:
- Expansible
AS/400 card
with potential-free contacts
SNMP / SNMP PRO card
(with connector for additional
temperature measurements)
- RS485
- RS485
- RS232
- RS485
PROTECT 3.M SNMP-Adapter
SNMP Slot-Adapter for UPS
Features:
Agent for RFC1628 MIB UPS standard MIB
Embedded Web-Server
 Monitoring via Web
 Configuration via Web
Embedded Event Manager
 Start of different Jobs
 Net Broadcast
 E-Mail
Monitoring of environmental conditions
 Temperature, Humidity, GenSet, Fire, Air
condition, Smoke shutter...
Support Software products
 Network Management Software „NMS“
 NMS special for Power Supply Systems
SNMP Adapter Pro: 6000001271
SNMP Adapter:
6000004036
 Shutdown Software “CompuWatch”
 Direct multi-server shutdown of different OS
with communication modules
PROTECT 3.M AS/400 slotcard
Pinassignment
Description
1
UPS Failure
2
Summary alarm (signal of pins 1, 7and 9)
3
Emergency shutdown, e.g. connection of an
external switch for EPO (closer)
4
5
Common ground for pins 1, 2, 6, 7, 8 und 9
6
Bypass active
7
Battery low
Pin 2:
8
UPS on
Pin 3 and 4:
9
Utility Failure
Pin 5:
Pin 6:
Pin 7:
Pin 1:
Pin 8:
Pin 9:
UPS Fault
Battery below cutoff voltage
Summary Alarm:
UPS failure, Utility power failure, Battery low
Short from Pin 3 to 4 generates an UPS shutdown,
e.g. by installing an external switch for EPO.
Common ground for relays (pins 1, 2, 6, 7, 8 und 9)
Bypass active; mains operation
Battery low
Battery voltage is below the predetermined level
UPS on; normal operation
(relay closed during normal operation)
Utility Failure; battery operation
Attention ! Contact load rating: AC / DC  24 V / 0,5 A
UPS system: PROTECT 3.M
Graphical front-end of CompuWatch
Normal operation
PROTECT 3.M