Treatment Alternatives to Comply with Upcoming Regulations

Download Report

Transcript Treatment Alternatives to Comply with Upcoming Regulations

Treatment Plant Ozone
Retrofit Program
California Unified Program 8th Annual Training Conference
February 8, 2006
Presented by:
Paul G. Beswick
Metropolitan Water District of Southern California
Environmental Support Services
(213) 217-5533
[email protected]
Southern California’s Imported Water
High Salinity
Low DBPs
California
Aqueduct
Colorado
River
Aqueduct
Lower Salinity
High DBPs
SERVICE
AREA
Drivers for Treatment
Improvements
 Water Quality
– Regulatory compliance
– Salinity management
– Taste-and-odor control
 System Operations
– Remove plant capacity limitations
– Maximize flexibility of supply
Plant Process Layout
Plant Process Flow Diagram
Oxygen
Generation
Ozone
Generation
LOX
Ozone
Ozone Destruct
Hydrogen
Peroxide
Acid
Floc Aid
Caustic
Ozone
Contactors
Meter
Filter Aid
Chlorine
Ammonia
Flocculation
Poly
Chlorine
Alum/Ferric
Sedimentation
Flash
Mix
Ammonia
Chlorine
Caustic
Filtration
Finished
Water
Reservoir
To Member
Agency
Connection
ORP General Design Criteria

Plant Flow Range is 60 to 750 MGD

Design Ozone Dose of 2.6 mg/L at 750 mgd

8.6% Design Ozone Concentration

O3 Generation up 15,000 lb/day

Contactors Designed for 10 Minute HDT
Ozone Process Flow Diagram
OZONE
OZONE
LIQUID OXYGEN FEED
GENERATION
CONTACTOR
GAS SYSTEM
SYSTEM
SYSTEM
VENT OZONE
DESTRUCT SYSTEM
PSU
OZONE
OZONE
DESTRUCT
CATALYST
BED
LOX
LOX
OZONE
TANK
VAPORIZER
GENERATOR
CONTACTOR
OPERATING = 4
OPERATING = 6
OPERATING = 5
OPERATING = 2
STANDBY = 1
STANDBY = 1
FUTURE = 4
FUTURE = 1
OPERATING = 2
OPERATING = 1
STANDBY = 1
STANDBY = 1
STANDBY = 1
STANDBY = 0
FUTURE = 1
DEFROST = 1
FUTURE = 2
FUTURE = 2
HEATER
DESTRUCT
BLOWER
FUTURE = 1
NITROGEN SYSTEM
OPERATING = 1
DRYER
RECEIVER
TANK
COMPRESSOR
STANDBY IS A
BOTTLE SYSTEM
ORP Chemical Storage
Unit
Ozone
Qty
Capacity
N/A 90 pounds
LOX Tanks
3
44,000 gal. ea.
Hydrogen Peroxide (35%)
2
2,000 gal. ea.
Sulfuric Acid (93%)
2
80,000/25,000 gal.
Caustic (25%)
8
127K/50K gal.
Chlorine
Aqueous Ammonia (19%)
Sodium Hypochlorite (5.25%)
3
4
2
90 ton rail cars
13,000/10,000 gal.
2,000 gal.
LOX Tank Farm
Ozone Building
Ozone Generators
Ozone Contactor Schematic
Ozone Off Gas
Raw
Water
Ozone Feed Gas
Hydrogen Peroxide
Contactor Gallery
Lessons Learned
 Standardized Alarm Beacons
 Disconnected Sample Line Vent to Contactor
 Warning Signals on Ozone Building Roof
 Safety Signs Throughout Facilities
 Automatic Shutoffs in Boiler Room
 New Gasket Material for Sulfuric Acid
 New Gasket Material for Ozone System
 Contactor Sample System Modification
 Added check valve at O3 generator outlet
 Seal Drain Sumps and Contactor Cover Plates
 1 Year Life on O3 Ambient Detector Probes