Meeting 33 Fingleton and White Slides
Download
Report
Transcript Meeting 33 Fingleton and White Slides
Demand Side Units with a Maximum
Export Capacity < 10MW
1st February 2010
Michael Peters
Introduction
DSU sites which can offer demand reduction through a
combination of:
Load Reduction (refrigeration, pumps etc.)
Standby diesel generators
Inactive CHP plant (possibly seasonal)
Sites with large heat load typically have export capacity –
but profile still similar to demand only site
Modification Proposal
The demand site shall have a Maximum Import Capacity
and shall not have a Maximum Export Capacity greater
than the De Minimis Threshold.
DSU Import Only – Normal Operation
Grid
3
M
Site Load:
8MW
CHP Generation:
5MW
Grid Import:
3MW
Maximum Export Capacity = 0
8
5
Load
CHP
DSU Import Only – Load Reduction
Grid
1
3
M
Load Reduction:
2MW
Revised Site Load:
6MW
CHP Generation:
5MW
Revised Grid Import:
1MW
Maximum Export Capacity = 0
6
8
Load Reduction of 2 MW
5
Load
CHP
DSU with MEC – Normal Operation
Grid
1
M
Revised Site Load:
2MW
CHP Generation:
5MW
Revised Grid Export:
3MW
Maximum Export Capacity 3MW
4
5
Load
CHP
DSU with MEC – Load Reduction
Grid
3
1
M
Load Reduction:
2MW
Revised Site Load:
2MW
CHP Generation:
5MW
Revised Grid Export:
3MW
Maximum Export Capacity 3MW
2
4
5
Load
Load Reduction of 2 MW
CHP
Load Reduction Profile
2MW Load Reduction
has the same benefit
to the system whether
it is reducing demand
or “negative demand”
Why not participate as AGU?
Does not capture load reduction potential
Gross settlement results in excessive import costs
If generation capacity > MEC => Non-Firm Access
Conclusion
The Modifcation Proposal:
Encourages greater participation of Large Energy Users in
wholesale market through DSUs
Furthers Code Objectives through:
Development of SEM
Promotes competition
Promotes long-term interests of consumers