Integrated Controller V series model 1000

Download Report

Transcript Integrated Controller V series model 1000

Integrated Controller V series model 1000
& LC500 Introduction
Flexible modular-based
solution for small applications
Model 3000
Model 1000
Model 2000
Automation Group
August 2002
Copyright © 2002 Toshiba International Corporation. All rights reserved.
Rev.1 on Aug 1 2002
New One-loop controller LC500
 A unified display function and Intelligent I/O
based on model 1000
 IEC61131-3 V-Series engineering tool
 High-speed redundant optical loop TOSLINES20LP
 I/O:
Analog input:
Digital input:
MV output:
Analog output:
Digital output:
4 points
3 points
1 point
2 points
3 points
One loop controller LC500
2
/
Integrated Controller V series model 1000
New One-loop controller LC500
RS485
 Flexible addition and integration of
loops
– Max. 8 PID loop control
 Multi -loops system
512 H
512H
512H
512H
512H
512H
512H
Loop 2
Loop 3
Loop 4
Loop 5
Loop 6
Loop 7
Loop 8
IOBUS
RS485
Intelligent PI/O
Max. 15 modules
– Display unit and I/O can be
extended
 Side keyboard
– Parameter display and setup on
the site
Max. 8 loops
LC511/512
Multi-loops system
Side keyboard
 New Instrument Function Block and
Model Driven - PID Control
– Supported
I/O terminal
block
Side keyboard
3
/
Integrated Controller V series model 1000
Model 1000 Summary
• Entry model for V series product line.
• Offers variety of solutions
– Loop-controller solution for up to 8 physical PID loops
– Data logging solution for up to 128 analogs
– Inputs - 4-20mA, 1-5V, mV, Thermocouple, RTD, pulse
– Sequence control for up to 96DI plus 96DO
– Combination of loop, monitoring and sequence.
– Remote I/O up to 1km (3,280 feet)
– Traditional Loop Display available
• Tag-based Process-Control-like Engineering
– Common engineering tool over the whole V series product line
– Function block and ladder diagram available
– Tag-based I/O database configuration
4
/
Integrated Controller V series model 1000
Model 1000 with Loop Display Interface
• Conventional panel-instrumentation-based operation
• One loop display shared by multiple loops
PS591
100.0
L1P
U11
C
A
M
V
PS591
PS591
V
100.0
L1P
U11
L1P
U11
100.0
C
A
M
One loop
configuration per
each unit
C
A
M
V
Up to 8 loop display
units connected to
CPU for operation in
parallel.
PS591
100.0
L1P
U11
C
A
M
V
One loop display unit
can switch indication
among up to 8 loops
in CPU
PS591
L1P
U11
V
5
/
Integrated Controller V series model 1000
100.0
100.0
C
A
M
100.0
100.0
C
A
M
100.0
C
A
M
100.0
C
A
M
100.0
C
A
M
C
A
M
100.0
C
A
M
C
A
M
Model 1000 with Touch Panel Graphic Display
• LCD Touch Panel for graphically aided operation
DATA LOGGER
• Network among Graphic Display
• Integration with PC package
Network via
Touch panel
with PC
FURNACE TEMP. CONTROL
LCD touch panel
display for GUI
(Graphical User
Interface) based
operation
SV1
600
SV2
400
PV1
597
PV2
401
Ethernet
LOCAL
OPERATOR
INTERFACE
PS591
L1PU11
V
PROGRAMMABLE OPERATOR INTERFACE
PROFACE GP377
http://www.pro-face.com/product/gp/gp377/gp377.htm
6
/
Integrated Controller V series model 1000
PS591
L1PU11
V
Model 1000 with Human Interface Integration
– Real DCS-oriented Human Interface
– Remote I/O up to 1km(3,280 Feet).
– Integration with model 2000 and/or model 3000
OIS-DS
OIS-DS
Ethernet
PS591
100.0
PS591
C
A
M
L1PU11 EN531
PS692
L1PU11 EN531
V
1km (3,280 Feet)
L1PU11 EN531
V
Model 1000
7
/
Integrated Controller V series model 1000
DI635
DI635
DO635
DO635
Model 2000
Model 1000
PS591
EN631
V
V
Model 1000
S2PU72
Remote I/O
Model1000 vs EC321 loop controller
• Model 1000 has more flexibility in configuration and maintenance.
Model 1000
EC321
Build
Modular
All-in-one
Display
Up to 8 loop display units per CPU.
One build-in loop display per CPU.
Flat panel screen available also.
Independence of loops
One CPU per up to 8 loops,
One CPU per up to 4 loops, 2 of
running under independent tasks.
them with real output, running in
shared task.
Integration of loops
No necessity of peer-to-peer
No necessity of peer-to-peer
comm up to 8 loops
comm up to 4 loops, 2 real
outputs. Need peer-to-peer comm
for integration of more loops
Maintenance
8
Flexible on module basis
/
Integrated Controller V series model 1000
Whole-unit basis.
Configuration 001: Remote Hybrid I/O Application
• Remote I/O connection up to 1km(3,280 Feet).
• Hybrid I/O module to handle a variety of signals at every location.
• Ethernet link to HMI package
Ethernet link
For HMI linkage
Ethernet
Item
Description
Code No.
CPU module
Ethernet module
Terminal Block
Loop unit
Terminal block
Terminal block
User loop number 8loop, 6ks, 24Vdc input
10BASET interface
For Ethernet-based system(EN531+L1PU11)
4 1-5V-AI, 1 4-20mA-AO, 2 1-5V-AO, 3DI, 3DO)
For LP01/LP02 Loop unit
For IOBUS relay terminal block, cable connection type
L1PU11
EN531T
TB522
LP01
UT5L12
3Y8A2156G001
Remote
Hybrid I/O
L1PU11 EN531
4 1-5V in
1 4-20mA out
2 1-5V out
3 digital in
3 digital out
V
Model 1000
Twisted pair
Cable up to
1km (3,280 Feet)
Total
9
/
Integrated Controller V series model 1000
Configuration 002: Remote Temperature Data Logging
• Remote I/O connection up to 3,280 Feet.
• Intelligent RTD I/O module configurable on engineering tool
• RS-485 computer link for economical solution
RS-485 link
For HMI connection
Item
Description
Code No.
CPU module
Terminal Block
RTD input
Terminal block
Terminal block
User loop number 8loop, 6ks 24Vdc input
For CPU unit
4 channels, Resistance temperature detector:Pt100
For SRT01 RTD input, European type
For IOBUS relay terminal block, cable connection type
L1PU11
TB521
SRT01
EC352RT0151
3Y8A2156G001
Intelligent
RTD I/O
For Scaling&
Linearization
L1PU11
V
4 RTD inputs
Model 1000
Twisted pair
Cable up to
1km (3,280 Feet)
Total
10
/
Integrated Controller V series model 1000
Configuration 003: Hybrid Control Station
– 8 RTD inputs, 8 1-5Vdc inputs, 8 4-20mA output, 32 DIs, 32DOs on a
DIN-rail controlled by one CPU.
– Integration with multiple control stations.
– HMI connection via Ethernet.
Ethernet
PS591
L1PU11
Item
Description
Code No.
CPU module
Ethernet module
Terminal Block
RTD input
Terminal block
Analog input
Terminal block
Analog output
Terminal block
Digital input
Terminal block
Digital output
Terminal block
User loop number 8loop, 6ks, 24Vdc input
10BASET interface
For Ethernet-based system(EN531+L1PU11)
4 channels, Resistance temperature detector:Pt100
For SRT01 RTD input, European type
8 channels, 1-5V/mV/TC input, None isolated
For SAI01/SAI06 Voltage input , European type
8 channels, 4-20mA output, None isolated
For SAO01/SAO06 analog output, cable connection type
32 points, 24Vdc-5mA,
For SDI01 digital input, cable connection type
32 points, 24Vdc-100mA,
For SDO01 digital output, screw terminal block type
L1PU11
EN531T
TB522
SRT01
EC352RT0151
SAI01
EC352AI0151
SAO01
EC352AO0151
SDI01
EC352DI0151
SDO01
EC352DO0151
PS692
EN531
PS591
L1PU11
S2PU72
EN631
DI635
DI635
DO635
DO635
EN531
V
V
V
Model 1000
11
/
Model 1000
Integrated Controller V series model 1000
Model 2000
Configuration 004: Pipeline Instrumentation
• Hybrid input/output module for signals around pump station.
• Conventional loop display for local monitoring & operation
• User-defined function block for ease of ‘repeat configuration’
Item
Description
Code No.
CPU module
Terminal Block
Loop unit
Terminal block
Display unit
User loop number 8loop, 6ks, 24Vdc input
For CPU unit
4 1-5V-AI, 1 4-20mA-AO, 2 1-5V-AO, 3DI, 3DO)
For LP01/LP02 Loop unit
One loop display for switchable 8 loops, 24Vdc input
L1PU11
TB521
LP01
UT5L12
LD512
12
/
Integrated Controller V series model 1000
100.0
L1PU11
C
A
M
V
Model 1000 Options
Item
24Vdc power supply
PS591
Loop display
100.0
C
A
M
Engineering Tool
13
/
Description
24Vdc Power supply
Power unit
24Vac power supply for 100 to 240Vac input
Terminal Block
For Power unit(PS591)
Loop Display
Display unit
One loop display for switchable 8 loops, 24Vdc input
Engineering tool
Engineering tool
Require Windows2000 based PC
Tool's Cable
5m RS232C Cross cable (model1000, D-Sub/RJ45)
I/O modules
Loop unit
Loop unit
Terminal block
Analog input
Terminal block
Terminal block
Analog input
Terminal block
Terminal block
Analog input
Terminal block
Terminal block
Thermocouple
Terminal block
RTD input
Terminal block
Analog output
Terminal block
Analog output
Terminal block
Pulse input
Terminal block
Digital input
Terminal block
Digital output
Terminal block
Terminal block
Code No.
PS591
TB511
LD512
GET91E*SS
GCU505*CS
1 loop, current output type (4AI, 1MV, 2AO, 3DI, 3DO)
LP01
1 loop, pulse output type
LP02
For LP01/LP02 Loop unit
UT5L12
8 channels, 1-5V/mV/TC input, None isolated
SAI01
For SAI01/SAI06 Voltage input , European type
EC352AI0151
For SAI01/SAI06 Voltage/Current input, European type
EC352AI0171
4 channels, 1-5V input, each channel isolated
SAI02
For SAI02 Voltage input, European t ype
EC352AI0251
For SAI02 Voltage/Current input, European type
EC352AI0271
4 channels, 1-5V input, each channel isolated, with distributor SAI03
circuits
For SAI03 Voltage input, European type
EC352AI0351
For SAI03 Voltage/Current input, European type
EC352AI0371
8 channels, Thermocouple: K,J,T,E,R,S,B, each channel isolated
STC01
For STC01 Thermocouple input, European type
EC352TC0151
4 channels, Resistance temperature detector:Pt100
SRT01
For SRT01 RTD input, European type
EC352RT0151
8 channels, 4-20mA output, None isolated
SAO01
For SAO01/SAO06 analog output, European type
EC352AO0151
4 channels, 4-20mA output, each channel isolated
SAO02
For SAO02 analog output, European type
EC352AO0251
4 channels, 50pps(max.), 24V input
SPI01
For SPI01 pulse input, cable connection type
EC352PI0151
32 points, 24Vdc-5mA,
SDI01
For SDI01 digital input, European type
EC352DI0151
32 points, 24Vdc-100mA,
SDO01
For SDO01 digital output, European type
EC352DO0151
For SDO01 , for connection to OMRON G79 relay terminal
EC352DO0161
Integrated Controller V series model 1000