Distribution Solution
Download
Report
Transcript Distribution Solution
Distribution Solution
Distribution Solution - Topics
Substation Automation
Conventional vs New Technology
RED 500 protection relays
REJ, REU Multipurpose Relays
REX521 Feeder Protection
REF54x Feeder Terminal
REM54x Machine Terminal
MicroSCADA Network and Control System
Station Automation (SCS)
Network Control System (NCS)
Summary
Distribution Solution - Substation Automation
Conventional Technology
control panel, separate relay room, connectivity through hardwiring.
New Technology
local control, multifunction relays, connectivity through serial communication.
Distribution Solution - Example of automation
Cost benefits for a new substation construction: conventional
substation design compared with automated substation design.
Configuration:
6 x 138 kV Circuit breakers, 1 1/2 CB arrangement
1 x 138/15 kV Transformer
2 x 6 lineups of 15 kV metalclad distribution switchgear
Distribution Solution - Automation vs Conventional
Estimated benefits
Qty
cost / unit
Total
control panels
-6
10.000
- 60,000
relay panels
-4
7.000
- 28,000
metering relays
-2
4.300
- 8,600
feeder relays
- 10
3.300
- 33,000
reduced conduit (ft)
- 2000
9
- 18,000
reduced wiring (ft)
- 6000
8
- 48,000
bulding size m2
- 160
215
- 34,400
reduced RTU
-1
48,000
- 48,000
fault recorder
-1
29,000
- 29,000
reduced seq. event rec.
-4
7,000
- 28,000
reduced annunciator
-2
3,800
- 7,600
Total
Appr. Price for new installation
Savings
- 336,600
Source: Newton & Evans report
150,000 - 250,000
86,000 - 186,000
Distribution Solution - Multipurpose Relays
Multipurpose protection relay series
Voltage relays:
REU 523 & REU 513
Overcurrent & earth-fault relays:
REJ 525 & REJ 515
Overcurrent relays:
REJ 523 & REJ 513
Earth-fault relays:
REJ 521 & REJ 511
Directional earth-fault relays:
REJ 527 & REJ 517
Distribution Solution - Multipurpose Relays
Features
A wide range of protection functions
Wide and accurate numerical settings with perfect
long-time stability
Two sets of relay settings available
Recorded and time-stamped data of the latest 5 events
Event code buffer of the latest 60 events
Disturbance recording function for fault analysis
Output relay functions freely configurable for tripping
and signalling
Circuit-breaker failure protection unit
Distribution Solution - Multipurpose Relays
Features
Binary input for blocking, external resetting, triggering and
selection of setting group
Optical serial interface on the front panel for communication
with portable computer
Powerful and easy-to-use software tools for relay setting
High system reliability and availability due to continuous
hardware and software self-supervision
High immunity to electrical and electromagnetic interference
Relay case with a degree of protection according to IP 54
Rated frequency user-selectable 50/60 Hz
CE marking according to the EC directive for EMC
Distribution Solution - REX521 Feeder Protection
The supervision of your network will be
enhanced by using REX 521
Easy to use - ready made configurations =
local adaptations are not needed
Wide protection functionality - covering the
most essential protection functions
Condition monitoring functions - for
continuos supervision
Control functions - local or remote
Measurements
Connectivity - for remote control and
monitoring
Easy to integrate in systems through
communication protocols
Easy to order
Distribution Solution - REX521 Feeder Protection
Functionality
Protections
Measurements
3 stages non directional OC
3-phase current
3 stages directional or non
directional EF
Earth fault current
Neutral current
Disturbance recorder
Harmonics up to 13th
3-phase voltage
Active & reactive power
Active & reactive energy)
Frequency & cos Ø
Phase discontinuity protection
Thermal protection for cables
Circuit breaker failure protection
Autorecloser
Directional OC
Over / under voltage
Residual over voltage
Frequency
Syncrocheck
Distribution Solution - REX521 Feeder Protection
Functionality
Control
Control of one circuit breaker
SPA, LON and IEC103 protocol
Indication of 3 objects
Pre-programmed interlocking
conditions
Set values, measured values,
registered values / events,
uploading of disturbance recorder
data, control, etc. available
trough communication
Communication
Condition Monitoring
Self supervision (IRF)
Trip circuit supervision
Circuit-breaker wear
Phase current supervision (MCS 3I)
Phase voltage supervision (MCS 3U)
Easy to use
Measured values shown as
primary values
The settings are made in primary
values
Easy menu navigation
MMI in several languages
Distribution Solution - REF54x Feeder Terminal
Everything in one box
Distribution Solution - REF54x Feeder Terminal
Flexibility
Full range of protection, measuring,
control and supervision functions
Large amount of generic functions
Freely drawable mimic view
Freely programmable alarm indications
Freely configurable function button
Application-specific functionality
Distribution Solution - REF54x Feeder Terminal
Protection Functions
Auto-reclosing (5 shots)
Residual overvoltage l, h, i
Phase discontinuity
Synchro/voltage-check 1 - 2
Non-directional earth-fault I, h, i
Thermal overload for cables
Directional earth-fault l, h, i
Non-directional overcurrent l, h, i
Directional overcurrent l, h, i
Under/overfrequency 1 - 5
Transformer inrush and motor start-up
current detector
Overvoltage l, h
Undervoltage l, h
Distribution Solution - REM54x Machine Terminal
Innovative total solution for rotating
electrical machines
Motor Protection
Optimized protection functionality for
asynchronous motor application
Generator Protection
Wide range of protection functions
covering also generators and
synchronous motors
Distribution Solution - REM54x Machine Terminal
Motor protection
Motor start-up supervision (48,14, 66)
Thermal overload (49)
Unbalance (46)
Under current (37)
Reverse phase rotation (46R)
Over current and short circuit (50/51)
High-impedance based /Flux-balance
principle based 3-phase differential
protection (87M)
Earth fault, non-directional (51N) and
directional (67N)
RTD/analogue inputs
Analogue outputs
Distribution Solution - REM54x Machine Terminal
Generator protection
Over current and short circuit (50/51)
Over current and short circuit (50/51)
Voltage dependent over current (51V)
Overexcitation protection (24)
Underimpedance protection (21G)
Under excitation (40)
Fuse failure supervision (60)
Thermal overload (49)
Stabilized differential protection
Unbalanced load, NPS (46)
High-impedance based /Flux-balance
principle based 3-phase differential
protection (87G)
Reverse and forward power (32)
Abnormal frequency including df/dt
(81O/81U)
Earth fault, non-directional (51N) and
directional (67N)
Residual over voltage (59N)
Over and under voltage (59, 27)
Positive/negative phase sequence
voltage protection (27,47,59)
Distribution Solution - MicroSCADA
MicroSCADA,
the ABB solution for control and
automation of power distribution
for utilities and industry.
Distribution Solution - MicroSCADA
Substation automation (SCS)
Protection
Monitoring and control
Communication with NCC
Power quality measurements
Time synchronization
Interlocking
Metering
MV & HV
Distribution Solution - MicroSCADA
Network control system (NCS)
Distribution Solution - MicroSCADA
MicroSCADA technology highlights
- Based on industry standards
• Windows NT operating system
• Standard hardware
- Open
• Wide range of communication protocols
• Interface to third-party SW and
databases
- Database
• Logical name (LN) 500.000
• Index 10.000/LN
• Address space for RTUs 1-999
- High performance, unique functionality
• Advanced process database, datalogging functions and timing functions
• Unique high-level programming
language for the application engineer
• User authorization mechanism
- Scalability
• From mobile lap-top to hot stand-by
- Continuity
• Compatibility between program versions
• Consistency between application levels
• Upgradable. Continuity in development.
- High system availability based on
• Verified SW development
• Rigorous test procedure for new
releases (PVC)
• Coordination of system releases
- Built for local engineering
• Easy engineering using library modules
• Established support concepts
- Connection to office programs
• Reports to Excel, etc.
Distribution Solution - Summary
ABB advantages
Cost efficiency
Ready made solutions available - local adaptations not needed
By automating your substation you will be able to reduce hardware and
installation time
Compact design and size for easy installation
Freedom of choice
A wide range of products meeting all your needs and requirements
Added value
Products at all levels of automation, from stand-alone to a complete solution
We have
The experience and the know-how
Improve efficiency through data information and prevent
accidents from happening!