THE AIRSIDE DELIVERY BUILDING BLOCK PUZZLE

Download Report

Transcript THE AIRSIDE DELIVERY BUILDING BLOCK PUZZLE

AIRSIDE DELIVERY
PUZZLE
WELGUISZ
APPLICATION ENGINEERING
Introduction
Loran Dailey
WELGUISZ
APPLICATION ENGINEERING
AIRSIDE DELIVERY
PUZZLE
Goal
To have an Understanding
of the
Air Delivery System
and the
Airside Accessories
and how
Equipment Airflow and Pressure Drop
is affected
WELGUISZ
APPLICATION ENGINEERING
Goal
Diagnose and Troubleshoot
Airflow “Pinch / Problem Points”
Needing Improvements
In order to provide good airflow
WELGUISZ
APPLICATION ENGINEERING
Designer’s Goals
Design the Air Distribution System
“to work”
within the Blower Delivery Range
of the
Furnace/Air Handler Blower System
WELGUISZ
APPLICATION ENGINEERING
REGISTERS, GRILLS
& DIFFUSERS
COOLING
COIL
PRESSURE DROPS
PRESSURE
DROP
AIRSIDE DELIVERY
PUZZLE
BLOWER
AIRFLOW & PRESSURE
CAPACITY
RETURN SIDE
DUCTWORK
PRESSURE DROP
SUPPLY SIDE
DUCTWORK
PRESSURE DROP
Are we playing with all the pieces?
REGISTERS, GRILLS
& DIFFUSERS
PRESSURE DROPS
COOLING
COIL
PRESSURE
DROP
AIRSIDE DELIVERY
PUZZLE
AIRSIDE
ACCESSORY
PRESSURE
DROP
AIRFLOW & PRESSURE
BLOWER CAPACITY
RETURN SIDE
DUCTWORK
PRESSURE DROP
SUPPLY SIDE
DUCTWORK
PRESSURE DROP
REGISTERS, GRILLS
& DIFFUSERS
COOLING
COIL
PRESSURE DROPS
DIRTY FILTER
PRESSURE
PRESSURE DROP
DROP
AIRSIDE DELIVERY
PUZZLE
DIRTY COIL
PRESSURE DROP
AIRFLOW &
PRESSURE
AIRSIDE
ACCESSORY
BLOWER CAPACITY
PRESSURE
DROP
SUPPLY SIDE
RETURN SIDE
DIRTY BLOWER
PRESSURE DROP
DUCTWORK
PRESSURE DROP
DUCTWORK
PRESSURE DROP
Supply Air Registers
Supply Air Ductwork
Transports Air to Space
KEY DESIGN
PRESSURE DROP CONSIDERATIONS
A-COIL
Air
Mover
FURNACE
FILTER
•Ductwork
•Cooling coil
•Supply side registers / diffusers
•Return side grills / registers
•Filter pressure drop
•Dampers (Zoning / Balancing)
•UV lamps pressure drop
•Humidifier pressure drop
•Hot Water coil
•Future Accessories ????
Return Air Grills
Return Air Ductwork
Transports Air to Equipment
Situations Influencing
Equipment and Air Delivery
•
•
•
•
•
•
•
•
•
WELGUISZ
Minimum System Airflow
Contractors Rules of Thumb
Ductulator “Missed” Conceptions
Installed Duct Work Pressure Ranges
Ductwork Airflow Eating Pressure Drops
Determining the Ductulator Friction Setting
Equipment Adjustments that Gain Airflow
Filter Impact
Measuring Key Pressure Points
APPLICATION ENGINEERING
MINIMUM AIRFLOW
CFM / TON
What Minimum Do You Believe is Required for
Trouble Free Equipment Operation?
•
•
•
•
COOLING CFM = 325 to 400 CFM / TON
HEAT PUMP = 350 to 425 CFM / TON
GAS FURNACE = max temp rise CFM
ON AVERAGE = 350 to 375 CFM / TON
coil area and entering wet bulb determine minimum cfm
WELGUISZ
APPLICATION ENGINEERING
Typical Contractor’s Guideline
Static(Pressure)
Set on Ductulator
Supply
Return
0.10”
0.08”
0.08”
0.05”
Caution!
Rules of Thumb
Can Lead to
Design and Operational Problems
WELGUISZ
APPLICATION ENGINEERING
Ductulator
Mis(Missed)
Conceptions
WELGUISZ
APPLICATION ENGINEERING
Ductulator
Mis(Missed)
Conceptions
WELGUISZ
APPLICATION ENGINEERING
Setting @ 0.10
means
The Designer has Determined
that His Design
Can Handle a
Static Pressure Loss
of 0.10 inch w.g.
per 100 equivalent ft
of Duct Work
and
NOT THAT THE
DUCTWORK WILL
ONLY HAVE A
0.10” PRESSURE LOSS
WELGUISZ
APPLICATION ENGINEERING
Key points
Ductulator
is in
“inches water gauge” (w.g.)
1 psi = 27.708 inch or 2.31 ft w.g.
32 psi = 887 inch or 73.9 ft w.g.
Equipment Range
VS = 0.90” w.g.
PSC = 0.50” to 0.75” w.g.
WELGUISZ
APPLICATION ENGINEERING
DUCT WORK SYSTEM
PRESSURE CHARACTERISTICS
OPTIMUM
Supply Grill(s)
Return Grill(s)
Supply Ductwork
Return Ductwork
Totals
TYPICAL
0.03” w.g.
0.03” w.g.
0.12” w.g.
0.08” w.g.
0.26” w.g.
0.03” w.g.
0.03” w.g.
0.22” w.g.
0.12” w.g.
0.40” w.g.
(0.18” to 0.32”)
(0.33” to 0.50”)
HIGH STATIC
0.03” w.g.
0.03” w.g.
0.40+” w.g.
0.28+” w.g.
0.74+”w.g.
.
.
.
.
.
(0.51” to 1.00”+)
Note: These “base line static's” must be overcome just to deliver the air to space and return the air
back to the blower and do not consider other pressure drops from cooling coils or external filters.
WELGUISZ
APPLICATION ENGINEERING
DUCT WORK SYSTEM
PRESSURE CHARACTERISTICS
OPTIMUM
Supply Grill(s)
Return Grill(s)
Supply Ductwork
Return Ductwork
Totals
0.03” w.g.
0.03” w.g.
0.12” w.g.
0.08” w.g.
0.26” w.g.
@ 0.10”wg
200 equ. Ft.
(0.10”/100 ft) x (120 ft) = 0.12”
(0.10”/100 ft) x (80 ft) = 0.08”
TYPICAL
0.03” w.g.
0.03” w.g.
0.22” w.g.
0.12” w.g.
0.40” w.g.
@ 0.10”wg
340 equ. Ft.
HIGH STATIC
0.03” w.g.
0.03” w.g.
0.40+” w.g.
0.28+” w.g.
0.74+”w.g.
.
.
@ 0.10”wg .
680 equ. Ft. .
.
(0.10”/100 ft) x (220 ft) = 0.22”
(0.10”/100 ft) x (120 ft) = 0.12”
Note: These “base line static's” must be overcome just to deliver the air to space and return the air
back to the blower and do not consider other pressure drops from cooling coils or external filters.
WELGUISZ
APPLICATION ENGINEERING
Air Flow Eating Pressure Drops
WELGUISZ
APPLICATION ENGINEERING
Static Drop = (0.10”/100ft) x 150ft = 0.15” w.g.
Air Flow Eating Pressure Drops
Pressure Drop = (0.10”/100ft) x 120ft =0.12”
Pressure Drop = (0.10”/100ft) x 20ft =0.02”
Reduction of 0.10” or 83% of the loss!
WELGUISZ
APPLICATION ENGINEERING
Air Flow Eating Pressure Drops
Pressure Drop = 0.10”/100ft x 85ft =0.085”
Pressure Drop = 0.10”/100ft x 10ft =0.01”
reduction = 0.075” or 88% of the original loss!
WELGUISZ
APPLICATION ENGINEERING
Air Flow Eating Pressure Drops
Pressure Drop = 0.10”/100ft x 470ft =0.47”
WELGUISZ
APPLICATION ENGINEERING
Air Side Pressure Losses
•
•
•
•
•
•
•
•
Supply side registers / diffusers
Return side grills
Hi-efficiency filter (Owner or Dealer Furnished)
Dampers
UV lamps
Humidifiers
Cooling coil
Hot Water coil
WELGUISZ
APPLICATION ENGINEERING
Air Side Pressure Drops
Minimum
Maximum
0.10” Cooling Coil
0.01” Supply Grill
0.01” Return Grill
0.08” High Eff Filter
0.01”
Damper
WELGUISZ
APPLICATION ENGINEERING
0.50+”
0.05”
0.05”
0.50+”
0.05”
__?__
Other Items
__?__
0.21”
Total
1.15+”
Outside of
Equipment Pressure
Operational Range
Using the
Ductulator Correctly
We Need to Know!
• Available Blower (Static) Pressure @ Design CFM
• Accessory / Component Air Side Pressure Drops
• Total (Static) Pressure Available to Move the Air thru
the Duct System (Different than Blower (Static) Pressure)
• Total Feet of Duct Work Resistance
a) Equivalent Feet of Fittings (Manual “D” / Appendix 3) plus (+)
b) Straight Runs of Duct
WELGUISZ
APPLICATION ENGINEERING
Available (Static) Pressure
to Move Air thru Duct Work
Available Static @ Furnace = 0.68”
less Air Side Components P.D. = 0.33”
(cooling coil / supply registers and return grills)
Pressure Available To Deliver Air 0.35”
i.e. design ductwork
WELGUISZ
APPLICATION ENGINEERING
Using the
Ductulator Correctly
•
Set Ductulator
Friction Loss @
Pressure Available to Move the Air thru the Duct System
Total Feet of Duct Work Resistance
•
Set Ductulator
Friction Loss @
0.35”
200 ft
0.175”
•
Set Ductulator
Friction Loss @
0.35”
700 ft
0.05”
WELGUISZ
APPLICATION ENGINEERING
Future Classes
1 to 2 DAY
DUCT DESIGN CLASS
PRESENTATION MATERIALS
TO INCLUDE COMPARTMENTALIZE CD
BREAKING CLASS INTO 3 to 4 HOUR PRESO’S
WELGUISZ
APPLICATION ENGINEERING
Future Classes
FOE Fundamental Development Program
Airflow Measurement and Trouble Shooting
AUGUST 2006
WELGUISZ
APPLICATION ENGINEERING
Determining Accessory and
Component Pressure Drops
Cooling Coil Pressure Drops
3 Ton Coil
17.5” wide coil
1200 CFM
4.13 ft2 / 3 rows / 12 fpi
TXC036C4 has 0.30” w.g. P.D.
WELGUISZ
APPLICATION ENGINEERING
FURNACE AIRFLOW DELIVERY
17.5” wide furnace
A/TUE080A936 / A/TUD080C936 / A/TUD080R936
TABLES SHOW SAME AIRFLOW VS PRESSURE
High Speed fan tap
1189 CFM @ 0.70” w.g.
1247 CFM @ 0.60” w.g.
1296 CFM @ 0.50” w.g.
or
1200 CFM @ 0.68” w.g.
Furnace has 0.68” w.g. to overcome system static's
WELGUISZ
APPLICATION ENGINEERING
AVAILABLE WORKING PRESSURE
17.5” (936) Furnace
3 Tons / 1200 CFM
OPTIMUM
Available (Furnace) 0.68” w.g.
Ductwork / Grills
(0.26)” w.g.
Cooling Coil
( 0.30)” w.g.
Totals
0.12” w.g.
TYPICAL
0.68” w.g.
(0.40)” w.g.
(0.30)” w.g.
(0.02)” w.g.
HIGH STATIC
0.68” w.g.
(0.74+)” w.g.
(0.30)+” w.g.
( 0.36)+”w.g.
In conclusion, the 17.5 inch furnace has the static capacity to deliver
the required airflow, except thru the high static system.
Blower Upgrade or Lower Pressure Drop Cooling Coil
May Be Required for airside accessories!
WELGUISZ
APPLICATION ENGINEERING
.
.
.
.
TESTED
0.68” w.g. available
17.5 inch 936
0.30” w.g. required
FURNACE
17.5 “ wide
TXC036C4
COOLING COIL
3 TON AIRFLOW of 1200 CFM
WELGUISZ
APPLICATION ENGINEERING
WHEN COMBINED
0.30” w.g. required
17.5 “ wide
TXC036C4
COOLING COIL
DRAIN PAN RESTRICTION
ON FLUSH FIT MODELS
0.68” w.g. available
17.5 inch 936
FURNACE
3 TON AIRFLOW of 1200 CFM
WELGUISZ
APPLICATION ENGINEERING
CHANGING COMPONENTS
TO INCREASE AVAILABLE PRESSURE
0.20” w.g. required
21 “ wide
TXC037C4
COOLING COIL
ELIMINATE
DRAIN PAN RESTRICTION
ON FLUSH FIT MODELS
0.68” w.g. available
17.5 inch 936
FURNACE
3 TON AIRFLOW of 1200 CFM
WELGUISZ
APPLICATION ENGINEERING
Cooling Coil Pressure Drops
3 Ton Coils
21” wide coil
1200 CFM
4.13 ft2 / 3 rows / 12 fpi
Same Area and slabs, larger opening
TXC037C4 has 0.20” w.g. P.D.
Reduces P.D. by 0.10” w.g.
WELGUISZ
APPLICATION ENGINEERING
Changing the Airside Puzzle
Available Pressure to Deliver
17.5” (936) Furnace
3 Tons / 1200 CFM
OPTIMUM
Available (Furnace) 0.68” w.g.
Ductwork / Grills
(0.26)” w.g.
Cooling Coil
( 0.20)” w.g.
Totals
0. 22” w.g.
TYPICAL
0.68” w.g.
(0.40)” w.g.
(0.20)” w.g.
0.08” w.g.
HIGH STATIC
0.68” w.g.
(0.74+)” w.g.
(0.20)+” w.g.
( 0.26)+”w.g.
In conclusion, the 17.5 inch furnace has the static capacity (with some to spare)
to deliver the required airflow, except thru the high static system.
Blower Upgrade May be Required for some airside accessories!
WELGUISZ
APPLICATION ENGINEERING
.
.
.
.
FURNACE AIRFLOW DELIVERY
17.5” (948) wide furnace
A/TUE080A948 / A/TUD080C948 / A/TUD080R948
TABLES SHOW SAME AIRFLOW VS PRESSURE
Med-High Speed fan tap
1165 CFM @ 0.90” w.g.
1201 CFM @ 0.80” w.g.
1246 CFM @ 0.70” w.g.
or
1200 CFM @ 0.80” w.g.
Furnace has 0.80” w.g. to overcome system static's
Increases Working Pressure by 0.12”
WELGUISZ
APPLICATION ENGINEERING
AVAILABLE / LEFT OVER
PRESSURE to WORK WITH!
4 Ton 17.5” Furnace w/ 21 inch A-Coil
3 Tons / 1200 CFM / Med High tap
OPTIMUM
Available (Furnace) 0.80” w.g.
Ductwork / Grills
(0.26)” w.g.
Cooling Coil
( 0.20)” w.g.
Totals
+ 0.34” w.g.
TYPICAL
HIGH STATIC
0.80” w.g.
(0.40)” w.g.
(0.20)” w.g.
0.80” w.g.
(0.74+)” w.g.
(0.20)+” w.g.
+0.20” w.g.
( 0.14)+”w.g.
In conclusion, by going to a A-coil with a lower pressure drop,as well as to a furnace
with a stronger CFM / Pressure Delivery capability, the equipment has excess
“Pressure Capacity” to handle accessories with moderate pressure requirements.
WELGUISZ
APPLICATION ENGINEERING
.
.
.
.
TESTED SEPARATELY
0.68” w.g. available
A/TFD175ALFR
0.19” W.G.
17.5 inch 936
0.30” w.g. required
FURNACE
17.5 “ wide
TXC036C4
COOLING COIL
3 TON AIRFLOW of 1200 CFM
WELGUISZ
APPLICATION ENGINEERING
required
HOW COMBINED
DETERMINES AVAILABLE PRESSURE
0.30” w.g. required??
17.5 “ wide
TXC036C4
COOLING COIL
DRAIN PAN RESTRICTION
ON FLUSH FIT MODELS
3 TON AIRFLOW
of
1200 CFM
0.68” w.g. available A/TFD175ALFR
0.19” W.G.
17.5 inch 936
MOTOR
RESTRICTION
required
FURNACE
Side Return
A/TFD175ALFR
0.19” W.G.
required
Bottom Return
WELGUISZ
APPLICATION ENGINEERING
Duct System Design Goals
To Deliver
“The Just Right Amount of Conditioned Air”
(Right Temperature at Right Humidity)
Not too Little
(cold in winter / warm in summer)
Not too Much
(Stuffy and Dry in winter / Cold and Damp in summer)
WELGUISZ
APPLICATION ENGINEERING
Designer’s Goal
Design the Air Distribution System
“to work”
within the Blower Delivery Range
of the
Furnace/Air Handler Blower System
WELGUISZ
APPLICATION ENGINEERING
Available Static to Move Air
Available Static @ Furnace = _0.80”_
Pressure Drops
0.10” Cooling Coil 0.50+”
0.01” Supply Grill 0.05”
0.01” Return Grill 0.05”
0.08” High Eff Filters 0.50+”
0.20”_
Totals
1.10+”
0.60” To Deliver Air ____
PROBLEMS
WELGUISZ
APPLICATION ENGINEERING
FILTER IMPACT on EQUIPMENT LIFE
400
350
300
Caution
Safe Operation
Clean
Filter Loading
(time)
Equipmen
t
Damage
Coil
Frosting
Application Engineering
FILTER IMPACT on EQUIPMENT LIFE
400
Filter
Change
350
300
Clean
Equipmen
t
Damage
Caution
Safe Operation
Filter Loading
(time)
End of
Useful Filter Life
Coil
Frosting
Application Engineering
Filter Impact on Equipment Reliability
OEM Filter vs. 1”Pleated Retail Filter
400
OEM
Equipment
Filter
350
Homeowner
Purchased Retail
1 inch pleated filter
300
Change Filter Time
Safe Operation
1.0” to 1.50” w.g.
Equipmen
t
Damage
Caution
Pressure Drop Must Be Considered
When Using Different Accessories!
Clean
Filter Loading
(time)
Filter
Change Out
Required
Coil
Frosting
Application Engineering
AccuCleanTM / CleanEffectsTM
No Pressure Drop Consideration
400
OEM Filter
Pre Filter
Cleaning
clean
pre-filter
350
Days Lost
Knowledge is Key
for
300
Customer Satisfaction
Clean
Equipmen
t
Damage
Caution
Safe Operation
Filter Loading
(time)
Pre Filter
Cleaning
Required
Coil
Frosting
Application Engineering
AccuCleanTM / CleanEffectsTM
With Pressure Drop Adjustment
400
clean
Pre Filter
Cleaning
pre-filter
350
Customer Satisfaction
is easily Assured
with Proper Application
300
Clean
Equipmen
t
Damage
Caution
Safe Operation
Filter Loading
(time)
Pre Filter
Cleaning
Required
Coil
Frosting
Application Engineering
Installing Any Airside Accessory
Dealer needs to check Pressure Drops
New Systems:
Allow for Accessory Pressure Drop
Existing Systems or System Change Outs:
Check Pressure at several points. Determine if
possible problems already exist or if the accessory
could create a problem.
WELGUISZ
APPLICATION ENGINEERING
Measuring Furnace Pressures
Supply Duct
a
Pressure Across
Cooling Coil
Pressure In Supply Duct
COOLING COIL
(b-a)
b
FURNACE
Pressure Across Furnace
with Filter
(b+d)
c
Pressure Across Filter
(c-d)
Filter
d
Return Duct
Pressure In Return Duct
See Pub. No. 34-4051-04
WELGUISZ
APPLICATION ENGINEERING
Airflow Measurement
PSC Furnace Motor
Trane Residential Systems
.
Numbers are general estimates based on 400 CFM/Ton @ 0.65” w.g.
and will vary depending on Blower / Motor pressure tables
Good to Go!
Sea level to 2,000 ft
Caution
a Supply Duct
0.0
b Top of Furnace
Bottom of Coil
0.0
0.35
0.0
0.20
c
Inside Furnace
Blower Compartment
w/ factory filter
d Return Duct Only
No Filter P.D.
(a to b)
Cooling Coil P.D.
(b to d)
Furnace Pressure
(c to d)
Pressure Across
Clean Filter
WELGUISZ
APPLICATION ENGINEERING
0.15
0.0
0.10
0.0
0.20
0.0
0.0
0.40
0.20
Needs Improvement
0.25
0.30
0.40
0.35
0.15
0.08
0.60+
0.40
0.50+
0.30
0.70
0.12
0.60+
0.50
0.20
0.25
0.50
0.40
0.25
0.30+
0.35
0.40+
0.80
0.20
0.90+
0.30+
Measuring Air Handler Pressures
Supply Duct
Pressure In Supply Duct
a
Pressure Across Air Handler
AIR
HANDLER
with Filter
(a+c)
b
Pressure Across Filter
(b-c)
Filter
c
Return Duct
Pressure In Return Duct
See Pub. No. 34-4051-04
WELGUISZ
APPLICATION ENGINEERING
Airflow Measurement
PSC Air Handler Motor
Trane Residential Systems
.
Numbers are general estimates based on 400 CFM/Ton @ 0.50” w.g.
and will vary depending on Blower / Motor pressure tables
Good to Go!
Sea level to 2,000 ft
a
Supply Duct
0.0
b Inside Air Handler
between coil and filter
0.0
c Return Duct
No Filter
0.0
c Return Duct with
Filter Grills
0.0
(a to c)
Air Handler Pressure
0.0
(b to c)
Filter P.D.
0.0
WELGUISZ
APPLICATION ENGINEERING
0.15
Caution
0.20
0.25
0.25
0.10
0.20
0.40
0.08
Needs Improvement
0.30
0.30
0.15
0.35
0.40
0.20
0.25
0.35
0.55
0.12
0.30+
0.40
0.60
0.16
0.60+
0.50+
0.25
0.30
0.50
0.40
0.45+
0.65
0.20
0.70+
0.25+
OUR HOPE IS THAT THE
AIRSIDE DELIVERY PUZZLE
IS COMING TOGETHER FOR YOU
COOLING
DIRTY FILTER
PRESSURE DROP
PRESSURE
PRESSURE DROPS
DROP
AIRFLOW & PRESSURE
DIRTY COIL
COIL
REGISTARS, GRILLS
& DIFFUSERS
BLOWER CAPACITY
PRESSURE DROP
AIRSIDE
ACCESSORY
PRESSURE
DROP
RETURN SIDE
DIRTY BLOWER
PRESSURE DROP
DUCTWORK
SUPPLY SIDE
PRESSURE DROP
DUCTWORK
PRESSURE DROP
Introducing
The
Airside Calculator
An automated approach for selecting airside systems
and accessories
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator - Furnace
• What information is required just to
determine airside capacity for a furnace /
coil?
– Dimensions
– Airflow vs Static Pressure (air mover)
– Pressure Drop vs Airflow (air draggers)
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator - Furnace
• What about to assure the system will work
as designed?
– System Capacities
– Airflow vs Temperature Rise
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator - Furnace
*UXB080A9H31A @ 1200 CFM
Med-High 0.57” wg.
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator - Furnace
Med-High 0.57” wg. – 0.28 = 0.29” wg.
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator
Med-High @ 1200 CFM delivers {0.57” wg. – (0.28 + 0.19)} = 0.10” wg
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator - Furnace
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator
• How many literature pieces are required to
determine available airside pressure when
using a furnace, coil and filter?
– Quick Select Handbook?
• Good resource for determining dimensional fit.
WELGUISZ
APPLICATION ENGINEERING
Air-Side Calculator
• How many literature pieces?
– Furnace Product Data
– Coil Product Data
– Filter Product Data
• Which Pages?
– Dimensions
– Airflow VS Static Pressure
WELGUISZ
APPLICATION ENGINEERING
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Entry Screen – Select New System
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Entry Screen – Select New System
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select Furnace and A/C
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select Furnace and A/C
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Nominal Cooling Capacity Pops Up
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Nominal Cooling Capacity Pops Up
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Select 3 Tons From Dropdown
Notice the Dropdown! We do
the math for you in the
appropriate airflow range of
350 to 450 CFM / Ton
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select 3 Tons From Dropdown
Select American Standard
Select American Standard
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Notice the Dropdown! We do
Notice
We
the math
for the
youDropdown!
in the
do the math
forrange
you in
appropriate
airflow
ofthe
appropriate
350 to
450 CFM airflow
/ Ton range
of 350 to 450 CFM / Ton
Airside Calculator - Demo
Select From the Family
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select From the Family
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Select the Air Mover of Your Choice!
Look at this! We provide a
dropdown list for you to select
an Air Mover!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select the Air Mover of Your Choice!
Select American Standard Furnace
Select American
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Look at this! We provide
a dropdown list for you
to select an Air Mover!
Airside Calculator - Demo
Airflow values
populate!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Airflow values
populate!
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airflow values
populate!
Airside Calculator - Demo
Select the Coil from the Dropdown
Dropdown is based on the Model
Family you select!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select the Coil from the Dropdown
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o
Dropdown is based on the Model
Dropdown
Family you
select! is based on
the Model Family you
select!
Airside Calculator - Demo
Program does the math for you!
Pressure drop imposed
by the coil pops up!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Program does the math for you!
Pressure
Pressuredrop
dropimposed
imposed
by
bythe
thecoil
coilpops
popsup!
up!
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Select Filter Type
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select Filter Type
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Select the filter you want!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Select the filter you want!
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Airside Calculator - Demo
Program does the math for you!
Pressure drop imposed
by the filter pops up!
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Program does the math for you!
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
WELGUISZ
APPLICATION ENGINEERING
o Perfect Fit
Pressuredrop
dropimposed
imposed
Pressure
bythe
thefilter
filterpops
popsup!
up!
by
Airside Calculator - Demo
Enter other Static Pressure
Other pops up!
Program does the
math for you!
0.06” wg for typical supply and return
registers and grilles.
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Enter other Static Pressure
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
o Perfect Fit
Otherpops
popsup!
up!
Other
Programdoes
doesthe
the
Program
mathfor
foryou!
you!
math
0.06”wg
wgfor
fortypical
typicalsupply
supplyand
andreturn
return
0.06”
registersand
andgrilles.
grilles.
registers
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Set Ductulator - ductulator represents static pressure per 100 feet of run.
Let’s say Dealer has 350 eq feet of
duct run.
[(0.30”
wg /350 total equivalent feet) X 100 ft of duct)]=0.0857” per 100 feet of duct.
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator - Demo
Set Ductulator - ductulator represents static pressure per 100 feet of run.
Select American Standard Furnace
Select American Standard Coil
Select Filter
o AccuClean
o Perfect Fit
Let’s
Let’ssay
sayDealer
Dealerhas
has350
350eqeqfeet
feetofof
duct
ductrun.
run.
[(0.30”
wg /350 total equivalent feet) X 100 ft of duct)]=0.0857” per 100 feet of duct.
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator Tool
Intentions:
• Provide avenue to easily gain airside
capability.
– Includes factory blower data.
– Includes factory coil data.
– Includes factory accessory data.
– Input blocks for “other” data.
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator Tool
• Web based
– Dealernet / Comfortsite
• New Systems
• Existing Systems
• Troubleshooting
WELGUISZ
APPLICATION ENGINEERING
Airside Calculator Tool
• Extensive Help File
– How to hook up a Magnahelic
– How to run temperature rise
– Sensible heat formulas
• Become a part of a larger
selection program.
– Sell it right the first time.
WELGUISZ
APPLICATION ENGINEERING